Model: FDEN series

PCB power supply connector

(Primary side)

Power supply

Fan motor

 

L2

CNW1

CNW0

CNM1

 

 

 

 

 

CNM3 CNJ2

52X6 52X2 52X2 52X3 52X5

L3

F1

 

 

 

 

 

 

PCB power supply

 

 

IC7

IC8

 

connector

 

ZNR

 

 

 

 

 

(Secondary side)

 

 

 

 

 

CNB CNW2

L1

 

 

 

 

Remote controller

 

 

 

 

 

 

CNE

 

 

 

 

 

 

 

 

 

CNR

52X4

 

 

 

LED1

LED2

 

 

 

 

 

 

52X8-2

 

 

 

 

 

 

 

DIP switch

 

 

52X7 52X8-1

 

 

 

 

 

 

 

(SW5)

CNV

KN1

 

 

SW2

SW5

 

SW8

 

 

 

 

 

 

 

 

 

J5, J6

 

 

 

SW10

SW9

SW7

 

(SW8)

 

C57

 

 

 

 

 

 

 

 

 

CNH CNN1

 

 

 

 

J1~J4

 

 

 

CNQ

CNT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(SW7)

 

 

 

 

 

 

 

 

 

 

DIP switch

 

 

Connector

 

Address switch

 

 

 

(SW9)

 

 

 

 

 

J9~J11

 

 

 

 

(SW2)

 

 

 

 

 

(CNT)

 

 

 

 

 

 

 

 

 

(SW10)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heat exchanger thermistor,

Heat exchanger thermistor

Return air thermistor

(Thl-R2)

(Thl-R1, Thl-A)

 

Change by the jumper wire

 

Name

Function

J1 (SW7-1)

 

With

Input signal - Reverse invalid

 

None (1)

Input signal - Rus stop

 

 

J2 (SW7-2)

 

With

Heating thermostat OFF-Lo

 

None (1)

Heating thermostat OFF-Stop, Lo

 

 

J3 (SW7-3)

 

With

Normal operation operable

 

None (1)

Operation permission prohibited

 

 

J4 (SW7-4)

 

With

Normal

 

None (1)

Heating temp. +3

 

 

J5 (SW8-1)

 

With

Louver free stop control - Invalid

 

None (1)

Louver free stop control - Effective

 

 

J6 (SW8-2)

 

With

Freeze prevention fan control activated.

 

None (1)

Freeze prevention fan control deactivated.

 

 

Note (1) “None” means that jumper wire is not provided on the PCB or the connection is cut

(2)The replacement board is not equipped with jumpers J1 ~ J6. Instead, SW7 and 8, with the same functions as jumpers J1~J6, are used in the position where the jumpers were previously. Set SW7 and 8 locally in accordance with the above table.

Control change switch (SW5, SW9, SW10)

Function of DIP switch SW5 (Usually all turned OFF)

 

Switch

 

Function

 

ON

 

ON

Setting time : 1000hrs. (Unit stop)

SW5-3

SW5-4

OFF

Setting time : 1000hrs. (Display)

 

OFF

ON

Setting time : 600hrs. (Display)

 

 

 

 

OFF

Setting time : 180hrs. (when shipped from factory)

 

 

 

Function of DIP switch SW9 (Usually all turned OFF)

 

Switch

Function

SW9-3

 

ON

Emergency operation

 

OFF

Normal

 

 

SW9-4

 

ON

Fan control : Powerful mode

 

OFF

Fan control : Mild mode

 

 

Note (1) It is normally ON only in the case of SW9-4.

Function of DIP switch SW10 (Usually all turned OFF)

 

Switch

 

Function

SW10-1 (J9)

 

OFF

Auto swing fanction - None

 

 

ON

Auto swing function - With

 

 

 

 

 

 

OFF

 

OFF

Remote controller air flow

SW10-2

SW10-3

ON

Remote controller air flow

1 speed

(J10)

ON

(J11)

OFF

Remote controller air flow

2 speed

 

 

ON

Remote controller air flow

3 speed

 

 

 

- 9 -