Error display : e59

[Abnormalities in compressor starting] (Only case of 151~251 type)

 

Indoor unit

 

Outdoor unit

Red LED

 

Stays OFF

Red LED

 

1 time, 2 time, 3 time flash

Green LED

 

Keeps flashing

 

 

 

 

 

 

 

 

 

 

 

Check

 

 

 

Check of

Inverter

 

Is the power

 

 

 

Is the balance

 

 

 

 

 

 

power transistor

 

YES

YES

the compressor’s

OK

 

module

 

NG

Replacement

supply voltage

 

 

 

pressure appropriate

 

 

 

insulation resistance

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

correct proper?

 

 

 

during starting?

 

 

 

and winding

 

 

 

(Reference to 160)

 

 

 

control PCB

 

 

 

 

 

 

 

 

resistance.

 

 

 

 

 

 

 

 

NO

 

 

 

NO

 

 

 

NG

 

 

 

Inverter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OK

(1)

 

 

 

Check of power supply

 

 

 

Check the refrigerant level

 

 

 

Replacement

 

 

 

Carry out test operation

 

 

 

 

 

 

 

and refrigerant circuit.

 

 

 

compressor

 

 

 

(starting) another 2 or 3 times.

 

 

 

 

 

 

 

 

 

 

 

 

Did it improve?

NO

Replacement

compressor

Note (1) If the test operation is repeated 2 or 3 times, the liquid re- frigerant inside the compressor may be expelled from the compressor may recover from its starting abnormality.

Display conditions

(1)If it won’t start 2 times out of 7 attempted starts.

(2)Remote controller reset is possible after 3 minutes have passed.

18

Error display : e60

[Compressor loader position detection error] (Only case of 151~251 type)

 

Indoor unit

 

Outdoor unit

Red LED

 

Stays OFF

Red LED

 

1 time flash

Green LED

 

Keeps flashing

 

 

 

Note (1) Check if the power supply system is normal.

Again

 

 

 

 

It

Does the

 

It

Does it

It doesn’t

 

YES

doesn’t.

doesn’t.

 

Operation

Does E42 occur?

 

 

compressor make

 

 

 

return to normal

 

recur.

It is possible that

Does the compressor

 

 

 

 

 

any abnormal

 

 

 

when the power

 

 

 

transient noise

 

 

 

 

 

 

 

 

 

 

 

 

start?

 

 

 

 

 

 

noise?

 

 

 

is reset?

 

 

 

could be causing

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

malfunction. If

NO (E59)

 

 

 

It does.

It does.

 

 

 

E60 recurs.

 

 

 

there is a noise

 

 

 

 

 

 

 

 

 

 

source, take coun-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Replacement

 

 

 

termeasures to

E59 diagnosis

 

 

 

E42 diagnosis

Compressor check

 

 

 

 

 

 

prevent it.

 

 

 

 

 

 

control PCB

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Display conditions

(1)If a rotor position detection operation is conducted, then the rotor position cannot be detected again after that (4 times in 15 minutes), an abnormal state is displayed.

(2)After 3 minutes passes, it is reset with the remote controller is possible.

-33 -

Page 35
Image 35
Hunter Fan R410A manual Refrigerant circuit, Did it improve? Replacement Compressor, Could be causing, Malfunction. If