Hunter Fan R410A manual Error display

Models: R410A

1 48
Download 48 pages 23.34 Kb
Page 28
Image 28
Manual background

3

Error display

: e33

 

[Inverter primary current abnormal] [Only case of 151~251 type]

 

 

 

 

 

 

 

 

Indoor unit

 

 

Outdoor unit

 

Red LED

 

Stays OFF

 

Red LED

 

1 time flash

Green LED

 

Keeps flashing

 

 

 

 

Is the power supply normal? NO

YES

Is the voltage within

NO

the specified range?

 

 

YES

 

 

 

 

 

 

Is there any foreign matter

NO

such as dust or dirt on the control

 

 

PCB soldered surfaces?

 

 

YES

 

 

 

 

Restore it to the

normal state.

Restore it to the

normal state.

Remove any foreign matter

such as dust or dirt.

Display Conditions

If the inverter’s primary current exceeds the set value for 3 sec- onds, the compressor stops. After a 3 minute delay, it restarts, but when this occurs 5 times within 60 minutes.

Replace the control PCB.

[Compressor overcurrent trouble] [Only case of 301~601 type]

 

Indoor unit

 

Outdoor unit

Red LED

Stays OFF

Red LED

 

1 time flash

Green LED

Keeps flashing

Green LED

 

Keeps flashing

Is the voltage

AC220/240V between the NO L1 and L3 phases and between the L2

and L3 phases on the 52C

secondary side?

YES

 

 

• 52C is faulty.

Out of phase between the

 

• There is a disconnection between

L1 and L2 phases.

 

52C and CM or in the L1 and L2

 

 

 

 

phases between TB1 and 52C.

 

 

Check the unit side.

 

(1)

Is there overcurrent

YES

at the compressor?

 

NO

 

Outdoor unit control PCB is

faulty. Manual background Replace

(The CT input circuit is faulty.)

Is the power supply voltage proper? (Isn’t it too low?)

Are the power lines proper? (Aren’t they too thin?)

Is the overcurrent setting correct? (SW3 setting)

Is the compressor running with an overload?

Is the compressor locked?

During cooling: Is FMo turning?

During heating: Is FMI turning?

Is the service valve (gas side) fully open?

Is the filter clogged?

Is there an overcharge?

Is the installation space for the indoor and outdoor units proper?

Is there a short circuit in the indoor or outdoor units?

Compressor is faulty. Manual background Replace

Notes (1) Measure the overcurrent value to make sure.

Also make sure the overcurrent setting set with SW3 and SW4-1 on the outdoor unit control PCB

is not incorrect.

- 26 -

Page 28
Image 28
Hunter Fan R410A manual Error display