1

Error display

: e5

[Communications error during operation]

 

 

 

 

 

 

 

 

Indoor unit

 

 

Outdoor unit

 

Red LED

 

2 time flash

Red LED

 

2 time flash

Green LED

 

Keeps flashing

Green LED

 

Keeps flashing

 

Note (1) The green LED in the outdoor unit is used in the FDCA301 ~ 601 models only.

(1)

 

(2)

 

Is the connection

NO

Is the connection

NO

of the signal wires at the

of the signal wires at the

 

 

outdoor unit poor?

 

indoor unit poor?

 

 

YES

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Repair

 

 

 

Repair

 

 

 

 

 

 

 

 

 

 

 

Reset power

supply.

Did the remote

 

WAIT

 

 

 

controller’s LCD return

 

 

to normal?

 

 

 

 

 

YES

The unit is normal. Malfunction was due to transient noise, etc.

WAIT

Go to display diagnosis (page 140).

Notes (1) Check for poor connections (disconnection, looseness) on the outdoor unit’s terminal block.

(2) Check for poor connections or disconnection of the signal lines between the indoor and outdoor units.

 

Indoor unit

 

Outdoor unit

Red LED

2 time flash

Red LED

 

Stays OFF

Green LED

Keeps flashing

Green LED

 

Keeps flashing

Note (1) The green LED in the outdoor unit is used in the FDCA301 ~ 601 models only.

Reset power supply.

Malfunction is due to noise, etc.

Did it return to normal? YES (The outdoor unit’s CPU went out of control due to noise during

power on.)

NO

Outdoor unit’s control PCB is faulty. (Network communications

circuit is faulty.) Replace

2

Error display

: e32

 

[Power supply phases reversed] [Only case of 301~601 type]

 

 

 

 

 

 

 

 

Indoor unit

 

 

Outdoor unit

 

Red LED

 

Stays OFF

 

Red LED

 

1 time flash

 

Green LED

 

Keeps flashing

Green LED

 

Keeps flashing

 

Are the power supply phases reversed?

NO

Are the connections

to the reverse phase detection circuit lines correct?

YES

YES

NO

Repair

Repair

Outdoor unit’s control PCB is faulty.

Replace

(Reverse phase detection circuit is faulty.)

- 25 -