1.MAINTENANCE DATA

1.1 Servicing

(1)Evacuation

The evacuation is a procedure to purge impurities, such as noncondensable gas, air, moisture from the refrigerant equipment by using a vacuum pump. Since the refrigerant R410A is very insoluble in water, even a small amount of moisture left in the refriger- ant equipment will freeze, causing what is called ice clogging.

Evacuation procedure

 

Make sure that the both service valves of gas and liquid line are fully opened.

Indoor unit

(a) Check to ensure that there is no internal pres-

 

sure in the unit. If there is an internal pres-

 

sure, it should be relived through the service

 

port.

 

 

 

Gus line

 

 

 

 

 

 

 

 

(b) Connect the charging hose of the gauge mani-

 

Outdoor unit

 

 

 

 

 

 

fold to the service port of the gas piping.

 

 

Liquid line

 

Close high pressure valve 2 of gange mani-

 

Charge port

 

 

 

 

 

 

fold.

 

 

 

 

Gauge manifold

 

 

 

 

 

 

 

(c) Connect the charging hose A to a vacuum

 

 

(for R410A only)

 

 

 

 

 

pump.

 

 

 

1

2

Handle Hi

Repeat evacuation in the following sequence.

 

 

 

Charge hose A

 

Vacuumingcompleted

 

 

 

 

(for R410A only)

 

 

Vacuum gauge check

Handle Lo

 

 

Please run the

No increase in the

Charge hose

 

 

vacuum pump for at

reading of the

(for R410A only)

 

3

least one hour after

vacuum gauge's

 

 

Charge valve

Vacuum

Refrigerant

the vacuum gauge

needle pointer.

cylinder

Vacuum adapter

pump

shows -101kPa or

 

(for R410A only)

 

 

beginsVacuuming

 

 

 

 

lower. (-755mmHg or

 

 

 

 

 

 

lower)

 

 

 

 

 

 

 

 

 

 

Notes (1) Refer to the exterior-view drawing for the position of the service valve.

When the vacuum gauge's needle pointer creeps up, there is moisture left in the system or a leak. Pull air again after you have checked the system for a leak and rectified it. Use a reverse flow stop adapter to prevent the vacuum pump's lubricant oil from flowing into the refrigerant system.

Notes (1) Do not use the refrigerant pressure to expel air.

(2)Do not use the compressor for evacuation.

(3)Do not operate the compressor in a vacuum condition.

(2)When connecting of ther service valve, flare connection for both the indoor and outdoor unit.

- 2 -

Page 4
Image 4
Hunter Fan R410A manual Evacuation procedure