Hunter Fan R410A manual Error display e6, Display condition, Detective return air thermistor

Models: R410A

1 48
Download 48 pages 23.34 Kb
Page 18
Image 18
Error display : e6

4

Error display : e6

[Defective indoor unit heat exchanger thermistor]

 

Indoor unit

 

Outdoor unit

Red LED

 

1 time flash

Red LED

 

Stays OFF

Green LED

 

Keeps flashing

Green LED

 

Keeps flashing

Note (1) The green LED in the outdoor unit is used in the FDCA301 ~ 601 models only.

 

 

Defective indoor unit control PCB

 

 

 

 

 

 

 

Replace-ment (Defective indoor unit

 

 

heat exchanger thermistor input circuit)

 

 

 

 

YES

Is the indoor

YES

Are characteristics

unit heat exchanger

of indoor unit heat

 

thermistor connector

 

exchanger thermistor OK

connection OK?

 

 

or is there any

 

 

 

broken wire?

NO

 

 

 

NO

Correction

 

Defective indoor unit heat exchanger

 

thermistor

 

Replacement

 

 

 

Return air thermistor (ThI-A)

Indoor unit heat exchanger thermistor (ThI-R1, R2)

Resistance temperature characteristics

(k)

15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Resistance

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

 

 

 

5k

at 25˚C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

10

20

30

40

50

Temperature (˚C)

Note (1) 22.5 kat -6˚C

Display condition

If a temperature of –50ºC or lower is detected continuously for 5 seconds or longer by the thermistor, the compres- sor stops. After a 3 minute delay, the compressor restarts. If this state is detected again within 60 minutes after the first detection.

5

Error display

: e7

[Detective return air thermistor]

 

 

 

 

 

 

Indoor unit

 

 

Outdoor unit

Red LED

 

1 time flash

Red LED

 

Stays OFF

Green LED

 

Keeps flashing

Green LED

 

Keeps flashing

Note (1) The green LED in the outdoor unit is used in the FDCA301 ~ 601 models only.

Is the return air

YES

Is the return air

YES

 

Defective indoor unit control PCB

 

 

 

 

thermistor connector

 

thermistor characteristics

 

 

Replacement (Defective return air

connection OK?

 

OK or is there a

 

 

thermistor input circuit)

 

broken wire?

 

 

NO

 

 

 

NO

 

Note (1) Characteristics as per the above

 

 

Defective return air

 

 

graph.

Correction

 

 

 

 

 

 

 

 

thermistor

 

Replacement

 

 

 

 

 

 

 

 

 

 

 

 

 

Display condition

If a temperature of –50ºC or lower is detected continuously for 5 seconds or longer by the thermistor, the compres- sor stops. After a 3 minute delay, the compressor restarts. If this state is detected again within 60 minutes after the first detection.

- 16 -

Page 18
Image 18
Hunter Fan R410A manual Error display e6, Display condition, Detective return air thermistor