Hunter Fan R410A Aaaaaaaaaaaaaaaaaaaaaaaa, Error display e35, Cooling overload operation

Models: R410A

1 48
Download 48 pages 23.34 Kb
Page 29
Image 29
AAAAAAAAAAAAAAAAAAAAAAAA

4

Error display :

e34

 

[Open phase at L3 phase of 52C secondary side] (Only case of 301~601 type)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor unit

 

 

 

Outdoor unit

 

 

 

 

Red LED

 

Stays OFF

 

Red LED

 

1 time flash

 

 

 

Green LED

 

Keeps flashing

 

Green LED

 

Keeps flashing

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Notes (1)

Also check if there is voltage at the L3 phase on the 52C primary

52C

(1)

YES

 

 

 

 

 

side, but no voltage on the secondary side (coil wire disconnec-

 

 

 

 

 

 

 

 

 

secondary side L3 phase

 

Repair

 

tion or faulty contacts).

 

 

 

 

 

open?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(2)

If there is voltage at the L3 phase on the 52C primary side and it

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

(2)

 

 

 

is not abnormal, the outdoor unit control PCB is faulty.

 

The outdoor unit control PCB is faulty.

 

 

 

 

 

 

 

 

(The CT circuit is faulty)

 

 

 

Replace

 

 

 

AAAAAAAAAAAAAAAAAAAAAAAA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AAA

If the unit is operated with the service valve closed, 49C (internal ther-

AAA

 

 

 

 

 

 

 

 

 

 

 

 

mostat) operates. E34 may also be displayed. Check the service valve.

AAAAAAAAAAAAAAAAAAAAAAAA

5

Error display : e35

[Cooling overload operation]

 

Indoor unit

 

Outdoor unit

Red LED

Stays OFF

Red LED

 

1 time flash

Green LED

Keeps flashing

Green LED

 

Keeps flashing

Note (1) The green LED in the outdoor unit is used in the FDCA301 ~ 601 models only.

Are the

YES

 

 

 

 

 

 

characteristics of the

 

 

Is there cooling overload

outdoor heat exchanger thermistor

 

 

 

 

operation?

normal?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

Replace the outdoor heat

 

 

 

 

 

 

 

 

 

 

 

 

Is high pressure control

exchanger thermistor.

 

 

 

 

 

 

 

 

normal?

 

 

 

 

 

Is the unit normal?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Abnormal temperature detection

NO

 

 

 

 

Is it (the actual measurement) correct?

 

 

 

 

 

 

 

 

Abnormal Temperature Detection

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

The outdoor control PCB

 

 

 

 

 

Error stop

 

 

 

 

is faulty.

 

Replace

 

 

 

 

 

Return

Check the unit side.

Is there a short circuit in the outdoor unit?

Is the installation space proper?

Is the refrigerant level too high?

• Is the heat exchanger dirty or clogged?

(1) The compressor’s speed drops when all the following conditions are met (151~251). In the case of the 301~601, expansion valve control is performed.

1Outdoor heat exchanger temperature: A˚C or higher

2Outdoor air temperature: 41ºC or higher

3The outdoor unit’s fan runs at 7 speed (UHi)(1) continuously for 30 seconds or longer.

(2)Control is cancelled when the temperature drops to BºC or lower.

Model

 

Item

A

B

 

 

 

Compressor

less than 88

58.5

53.5

 

 

 

 

151~251 type

speed 88 to less than 108

53.5

48.5

 

(rps)

108 or higher

48.5

43.5

 

 

301~601 type

 

 

58

53

Note (1) Values in ( ) show for the case of the 301~601 models.

48

65(1)

 

 

Compressor speed

Indoor heat exchanger

Outdoor air temp. (ºC)

(rps)

temprature (˚C)

 

 

Note (1) In the case of the 151 ~

less than 88

65 or more

251, the abnormal stop

 

 

temperature differs

88 to less than 108

60 or more

depending on the

108 or higher

55 or more

compressor’s speed.

 

 

 

 

Display Conditions If the outdoor heat exchanger temperature becomes 65ºC 5 times within 60 minutes, including while the compressor is stopped, or if it continues at that temperature for 10 minutes or longer.

Resistance(k)

15

10

5

Outdoor unit heat exchanger themistor (Tho-R) Resistancetemperature characteristics

5kat 25°C

0 10 20 30 40 50 Temperature (°C)

- 27 -

Page 29
Image 29