(2)Refrigerant charging

(2)Refrigerant charging

(a)After the evacuation shown in the above, change the connection of the charge hose A to the refrigerant cylinder.

(b)Purge air from the charge hose A .

First loosen the connecting portion of the charge hose at the gauge manifold side and open valve 3 for a few seconds, and then immediately retighten it after observing that gas has blown out from loosened connecting portion.

(c)Open valves 1 and 3 then gas refrigerant begins flowing from the cylinder into the unit.

When refrigerant has been charged into the unit to some extent, refrigerant flow becomes stagnant. When that happens, start the compressor in cooling cycle until the system is filled with the specified amount of gas, then close valves 1 and 3 and remove the gauge manifold. Cover the service port with caps and tighten them securely.

(d)Check for gas leakage by applying a gas leak detector around the piping connection.

(e)Start the air conditioner and make sure of its operating condition.

1.2 Trouble shooting for refrigerant circuit

(1)Judgement of operating condition by operation pressure and temperature difference

Making an accurate judgement requires a skill that is acquired only after years of experience, one trouble may lead to an another trouble from a single trouble source and several other troubles may exist at the same time which comes from a undetected different trouble source.

Filtering out the trouble sources can be done easier by comparing with daily operating conditions. Some good guides are to judge the operating pressure and the temperature difference between suction air and delivery air.

Following are some pointers,

Pressure

Indi-

lowToo

lowlittleA

 

 

cation

 

 

Circuit

 

 

High side

 

 

Low side

 

 

High side

¡

 

Low side

 

 

High side

 

¡

Low side

¡

 

High side

Low side

High side

Low side

Normal

Alittle high

Toohigh

 

 

¡

 

 

¡

 

 

¡

¡

¡

¡

¡

Trouble cause

1)Excessive overcharging of refrigerant

2)Mixture of non condensable gas (air etc.)

Ineffective compression (defective compressor)

1)Insufficient refrigerant in circuit

2)Clogging of strainer

3)Gas leakage

4)Clogging of air filter (in cooling)

5)Decrease in heat load (in cooling)

6)Locking of indoor fan (in cooling)

1)Locking of outdoor unit fan (in cooling)

2)Dirty outdoor heat exchanger (in cooling)

3)Mixture of non condensable gas (air etc.)

1) Too high temperature of room