Hunter Fan R410A manual Error display e1, Only case of FDT, Cases of other than FDT

Models: R410A

1 48
Download 48 pages 23.34 Kb
Page 17
Image 17
Error display : e1

3

Error display : e1

[Communication error between remote controller~Indoor unit]

 

Indoor unit

 

Outdoor unit

Red LED

Stays OFF

Red LED

Stays OFF

 

 

 

 

Green LED

Keeps flashing

Green LED

Keeps flashing

 

 

 

 

Note (1) The green LED in the outdoor unit is used in the FDCA301 ~ 601 models only.

Voltage

YES

 

 

 

between X and Z

Replacement remote

 

 

approximately

 

 

controller

10~11 V?

 

 

 

 

 

NO

 

 

 

 

 

Voltage

NO

 

 

YES

 

 

 

fluctuates between

 

 

 

5~11 V between

 

 

 

 

 

Y and Z.

 

 

 

Power supply OFF

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

Remote controller

wire is removed

Is the

resistance between NO Y~Z on the remote controller ●Only case of FDT

approximately

10k?

Replacement

remote controller

Voltage

NO

fluctuates between

5~10 V between

 

 

Y and Z

 

indoors.

 

YES

 

Voltage

NO

fluctuates between

 

5~10 V between

 

 

CNB Y and Z.

 

YES

 

Indoor unit

NO

resets every

 

 

4 minutes.

 

Remote controller wire disconnection

Terminal block CNB harness is defective.

Power supply reset

 

Resistance is

NO

 

 

 

 

approximately 10k

 

 

Replacement indoor

 

between indoor

 

 

unit control PCB

 

Y~Z.

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Remote controller

 

 

 

 

 

wire short circuit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

Noise?

 

Normal?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

Power supply reset

Normal?

NO

Replacement indoor

unit control PCB

After the green LED lights up once, it begins flashing again continuously. The louver moves once in the

close direction.

YES

Noise

NO

Replacement remote

controller

 

Indoor unit

 

Outdoor unit

Red LED

Stays OFF

Red LED

Stays OFF

 

 

 

 

Green LED

Stays OFF or Lights

Green LED

Keeps flashing

continuously

 

 

 

 

 

 

 

Note (1) The green LED in the outdoor unit is used in the FDCA301 ~ 601 models only.

Only case of FDT

Stays OFF

Is the voltage

NO

Check the CNW5-

 

between CNW8

 

 

CNW8 harness.

 

2-312V?

 

 

 

 

 

Lighting YES

●Cases of other than FDTManual background Power supply reset

YES

Disconnection ?

NO

Is the

voltage at the transfomer's NO secondary side (red-red) 15V

or higher?

YES

Replacement indoor unit

power supply PCB

Harness exchange

Transformer

exchange

Normal

NO

Replacement indoor

 

unit control PCB

 

 

 

 

 

YES

The unit is normal.

(The malfunction is due to noise, etc.)

Cases of other than FDT

 

 

 

 

 

 

 

YES

Unit is normal.

 

 

 

 

Is it normalized?

 

(Runaway of indoor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

unit CPU due to

 

 

 

 

 

NO

 

 

 

noise, etc.

 

 

 

 

 

 

 

 

 

 

Transient trouble)

 

 

 

 

 

 

 

 

 

 

 

 

Defective indoor unit control PCB

 

 

 

 

 

 

Power supply

 

 

 

 

 

 

 

 

 

 

 

 

reset

 

 

Replace. (Defective CPU)

 

 

 

 

 

 

- 15 -

Page 17
Image 17
Hunter Fan R410A manual Error display e1, Only case of FDT, Cases of other than FDT