8

Error display : e38

[Defective outdoor air temperature thermistor]

 

Indoor unit

 

Outdoor unit

Red LED

 

Stays OFF

Red LED

 

1 time flash

Green LED

 

Keeps flashing

Green LED

 

Keeps flashing

Note (1) The green LED in the outdoor unit is used in the FDCA301 ~ 601 models only.

Is the outdoor

YES

Is the outdoor

air temperature thermistor

air temperature thermistor

connector connection

 

 

 

characteristics OK, is there

 

 

 

no broken wire?

OK?

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Defective outdoor air

Repairtemperature thermistor Replacement

Display conditions

If the temperature sensed by the thermistor is –30ºC or lower continu- ously for 5 seconds between 2 minutes and 2 minutes 20 seconds after the compressor goes ON, the compressor stops. After a 3 minute delay, the compressor restarts. If this state is detected 3 times in 40 (60) min-

utes.

Note (1) Values in ( ) show for the case of the 301~601 models.

YES

Defective outdoor unit control PCB

 

Replacement (Defective outdoor air

 

 

 

temperature thermistor input circuit)

Temperature-resistance characteristics of outdoor air temperature thermistor (ThO-A)

 

400

 

 

40

 

°C]

 

 

 

 

°C]

(k)[T<0

300

 

 

30

(k)[T>0

 

 

 

 

resistance

200

T < 0°C

 

20

resistance

 

 

T > 0°C

 

Thermistor

 

 

 

Thermistor

100

 

 

10

 

 

 

 

 

0

0

50

0

 

 

---50

 

 

 

 

Temperature [T](°C)

 

 

9

Error display : e39 [Defective discharge pipe thermistor]

 

Indoor unit

Outdoor unit

Red LED

 

Stays OFF

Red LED

1 time flash

Green LED

 

Keeps flashing

Green LED

Keeps flashing

Note (1) The green LED in the outdoor unit is used in the FDCA301 ~ 601 models only.

Is the discharge

YES

Are the discharge

YES

Defective outdoor unit control

pipe thermistor

pipe thermistor characteristics

PCB

 

Replacement (Defective

 

connector connection

 

OK, is there no

 

discharge pipe thermistor

OK?

 

broken wire?

 

input circuit)

 

NO

 

 

NO

 

 

 

Temperature-resistance

 

 

 

 

 

 

 

 

 

 

 

 

 

 

characteristics of discharge

 

 

 

 

 

 

 

 

pipe thermistor (ThO-D)

Repair

Defective discharge pipe

°C]

100

 

 

 

 

10

°C]

thermistor

Replacement

 

 

 

 

 

 

 

80

 

 

 

 

 

 

80

 

 

 

<

 

 

T< 80°C

 

 

 

>

 

 

 

)[T

 

 

 

 

T> 80°C

)[T

 

 

 

(k

 

 

 

 

 

 

(k

Display conditions

 

resistance

50

 

 

 

 

5

resistance

 

 

 

 

 

 

 

If the temperature sensed by the thermistor is –10ºC or lower con-

 

 

 

 

 

 

 

 

tinuously for 5 seconds between 10 minutes and 10 minutes 20

Thermistor

0

 

 

 

 

0

Thermistor

goes ON, the compressor stops. After a 3 minute delay, the com-

 

 

 

 

seconds (2minutes and 2minutes 20seconds) after the compressor

 

 

 

 

 

 

 

 

pressor restarts. If this state is detected 3 times in 40 (60) minutes.

 

0

20

50

80

100

120

 

Note (1) Values in (

) show for the case of the 301~601 models.

 

 

 

Temperature [T] (°C)

 

 

 

 

 

 

 

 

 

- 29 -

Page 31
Image 31
Hunter Fan R410A manual Utes, Error display e39 Defective discharge pipe thermistor, 100, 80 C