10
Error display : e40 [63H1 operation] (Only case of 301~601 type)
| Indoor unit |
| Outdoor unit | ||
Red LED |
| Stays OFF | Red LED |
| 1 time flash |
Green LED |
| Keeps flashing | Green LED |
| Keeps flashing |
Is the 63H1 operating?
NO
YES
While the 63H1 is operating
1.During Cooling
•Is the outdoor unit fan motor running?
•Is there a short circuit in the outdoor unit?
• Is there enough space for inlet and outlet?
2. During Heating |
• Is the indoor unit heat exchanger thermistor separated |
from the sensing case? |
• Is the filter clogged? |
The outdoor unit control PCB
is faulty. (The 63H1 input circuit is faulty.) Replace
3. During Cooling and Heating |
• Is the refrigerant overcharge? |
• Is the service valve fully open? |
[Open phase at L3-phase of 52C primary side]
| Indoor unit |
| Outdoor unit | ||
Red LED |
| Stays OFF | Red LED |
| 1 time flash |
Green LED |
| Keeps flashing | Green LED |
| Keeps flashing |
|
| 52C | (1) | YES | |
primary side L3 phase |
| ||||
|
| Repair | |||
|
| open? |
|
| Notes (1) Also check if there is voltage at the L3 phase on the 52C primary |
|
| NO |
|
| side, but no voltage on the secondary side (coil wire disconnection |
|
|
| (2) | ||
|
|
|
|
| or faulty contacts). |
The outdoor unit control PCB |
| ||||
| (2) If there is voltage at the L3 phase on the 52C primary side and it is | ||||
is faulty. |
| Replace |
|
| not abnormal, the outdoor unit control PCB is faulty. |
|
|
| |||
|
|
|
|
|
11
Error display : e42 [Current cut] (Only case of 151~251 type)
| Indoor unit |
| Outdoor unit | ||
Red LED |
| Stays OFF | Red LED |
| 1 time flash |
Green LED |
| Keeps flashing |
|
|
|
Is the power
supply voltage
proper?
NO
Check the power supply.
YES |
| Is the service | YES | |
| valve fully open? |
| ||
|
| NO |
| |
|
|
|
|
|
|
| Open it fully. |
|
|
|
|
|
|
|
Is the high | YES | |
pressure during operation | ||
| ||
proper? |
|
NO
Check the refrigerant level and refrigerant circuit.
Check the compressor's insulation YES resistance and winding
resistance.
NO
Replace the compressor.
● Display conditions
If the inverter’s output current ex- | Check the |
| |
| NG | ||
ceeds the set value, the compres- | power transistor module | ||
| |||
sor stops. After a | (See page 160) |
| |
|
| ||
restarts, but if this occurs 3 times | OK |
|
within 20 minutes. |
| |
• Is the installation space for the indoor and outdoor | YES | |
units proper? | ||
|
•Is there a short circuit in the indoor or outdoor units?
•During cooling: Is FMo operating?
Is the service valve fully open?
•During heating: Is FMI operating?
Replace the outdoor unit control PCB.
Does it return to
normal if the power NO supply is reset
(2 of 3 times)?
YES
Replace the outdoor unit control PCB.
Is the service valve fully open?
Is the filter clogged?
•Is liquid flowing back to the compressor?
•Is the compressor making abnormal noises?
It may be malfunction due to transient noise. If there is a noise source nearby, take measures to eliminate it.
- 30 -