Hunter Fan R410A manual Open phase at L3-phaseof 52C primary side

Models: R410A

1 48
Download 48 pages 23.34 Kb
Page 32
Image 32
[Open phase at L3-phase of 52C primary side]

10

Error display : e40 [63H1 operation] (Only case of 301~601 type)

 

Indoor unit

 

Outdoor unit

Red LED

 

Stays OFF

Red LED

 

1 time flash

Green LED

 

Keeps flashing

Green LED

 

Keeps flashing

Is the 63H1 operating?

NO

YES

While the 63H1 is operating

1.During Cooling

Is the outdoor unit fan motor running?

Is there a short circuit in the outdoor unit?

Is there enough space for inlet and outlet?

2. During Heating

Is the indoor unit heat exchanger thermistor separated

from the sensing case?

Is the filter clogged?

The outdoor unit control PCB

is faulty. (The 63H1 input circuit is faulty.) Manual background Replace

3. During Cooling and Heating

Is the refrigerant overcharge?

Is the service valve fully open?

[Open phase at L3-phase of 52C primary side]

 

Indoor unit

 

Outdoor unit

Red LED

 

Stays OFF

Red LED

 

1 time flash

Green LED

 

Keeps flashing

Green LED

 

Keeps flashing

 

 

52C

(1)

YES

primary side L3 phase

 

 

 

Repair

 

 

open?

 

 

Notes (1) Also check if there is voltage at the L3 phase on the 52C primary

 

 

NO

 

 

side, but no voltage on the secondary side (coil wire disconnection

 

 

 

(2)

 

 

 

 

 

or faulty contacts).

The outdoor unit control PCB

 

 

(2) If there is voltage at the L3 phase on the 52C primary side and it is

is faulty.

 

Replace

 

 

not abnormal, the outdoor unit control PCB is faulty.

 

 

 

 

 

 

 

 

11

Error display : e42 [Current cut] (Only case of 151~251 type)

 

Indoor unit

 

Outdoor unit

Red LED

 

Stays OFF

Red LED

 

1 time flash

Green LED

 

Keeps flashing

 

 

 

Is the power

supply voltage

proper?

NO

Check the power supply.

YES

 

Is the service

YES

 

valve fully open?

 

 

 

NO

 

 

 

 

 

 

 

 

Open it fully.

 

 

 

 

 

 

 

Is the high

YES

pressure during operation

 

proper?

 

NO

Check the refrigerant level and refrigerant circuit.

Check the compressor's insulation YES resistance and winding

resistance.

NO

Replace the compressor.

Display conditions

If the inverter’s output current ex-

Check the

 

 

NG

ceeds the set value, the compres-

power transistor module

 

sor stops. After a 3-minute delay, it

(See page 160)

 

 

 

restarts, but if this occurs 3 times

OK

 

within 20 minutes.

 

Is the installation space for the indoor and outdoor

YES

units proper?

 

Is there a short circuit in the indoor or outdoor units?

During cooling: Is FMo operating?

Is the service valve fully open?

During heating: Is FMI operating?

Replace the outdoor unit control PCB.

Does it return to

normal if the power NO supply is reset

(2 of 3 times)?

YES

Replace the outdoor unit control PCB.

Is the service valve fully open?

Is the filter clogged?

Is liquid flowing back to the compressor?

Is the compressor making abnormal noises?

It may be malfunction due to transient noise. If there is a noise source nearby, take measures to eliminate it.

- 30 -