15

Error display : e56

[Power transistor thermistor faulty.] (Only case of 151~251 type)

 

 

Indoor unit

 

Outdoor unit

 

 

 

 

 

 

Red LED

 

Stays OFF

Red LED

 

1 time flash

 

 

 

 

 

Green LED

 

Keeps flashing

 

 

 

 

 

 

 

 

 

 

Is the

 

 

Are the

 

 

 

Defective outdoor unit control

 

 

YES

power transistor

YES

 

power transistor thermistor

thermistor characteristics

 

PCB

 

Replacement (Defective

 

 

connector connection

 

 

OK, is there no

 

 

 

power transistor thermistor input

 

OK?

 

 

broken wire?

 

 

 

circuit)

 

 

NO

 

 

 

NO

 

 

 

 

 

Temperature-resistance

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

characteristics of power

 

 

 

 

 

 

 

 

 

 

 

 

 

 

transistor thermistor (ThO-D)

Repair

Defective power transistor

°C]

100

 

 

 

 

10

°C]

thermistor

Replacement

 

 

 

 

 

 

 

80

 

 

 

 

 

 

80

 

 

 

<

 

 

T< 80°C

 

 

 

>

 

 

 

)[T

 

 

 

 

T> 80°C

)[T

Display conditions

 

 

(k

 

 

 

 

 

 

(k

 

 

resistance

50

 

 

 

 

5

resistance

If the temperature sensed by the thermistor is –10ºC or lower con-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

tinuously for 5 seconds between 10 minutes and 10 minutes 20

Thermistor

0

 

 

 

 

0

Thermistor

seconds after the compressor goes ON, the compressor stops. Af-

 

 

 

 

 

 

 

 

 

 

 

 

ter a 3 minute delay, the compressor restarts. If this state is de-

 

 

 

 

 

 

 

 

tected 3 times in 40 minutes.

 

 

 

0

20

50

80

100

120

 

 

 

 

 

 

 

Temperature [T] (°C)

 

16

 

Error display :

e57

[Insufficient refrigerant volume.]

 

 

 

 

 

 

 

 

 

Indoor unit

 

Outdoor unit

 

Red LED

 

Stays OFF

Red LED

 

1 time flash

 

Green LED

 

Keeps flashing

Green LED

 

Keeps flashing

Note (1) The green LED in the outdoor unit is used in the FDCA301 ~ 601 models only.

Is the service valve

opened fully?

YES

Are the

connections of the connectors

to the indoor heat exchanger and return

air thermistor OK?

YES

Are the

characteristics of the indoor heat exchanger and return air thermistor OK?

YES

Is the low pressure during

operation normal?

NO

Fully opened.

NO

Normal

NO

Indoor heat exchanger and

 

return air thermistor faulty

 

 

Replace

 

 

 

 

 

 

 

 

NO

Charge with refrigerant.

Return air thermistor (ThI-A)

Indoor unit heat exchanger thermistor (ThI-R1, R2)

Resistance temperature characterisics

(k)

15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Resistance

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

 

 

 

5kat 25°

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0 10 20 30 40 50 Temperature (°C)

YES

Indoor control PCB faulty Replace

(The indoor heat exchanger and return air thermistor input circuits are faulty.)

Display conditions

If insufficient refrigerant protection (See page 92) is implemented 3 times within 30 minutes.

- 32 -

Page 34