Hunter Fan R410A manual Model FDUR series, Change by the jumper wire, Name, Function, Switch

Models: R410A

1 48
Download 48 pages 23.34 Kb
Page 13
Image 13
Model: FDUR series

Model: FDUR series

Heat exchanger thermistor,

 

 

Return air thermistor

Address swith

J6

(Thl-R1, Thl-A)

(SW2)

(SW8)

 

 

 

Heat exchanger thermistor

DIP switch

 

DIP switch

 

 

 

 

(Thl-R2)

(SW5)

 

(SW9)

 

 

Connector

 

Remote controller

J10~J11

 

J1~J4

Float switch

 

 

 

 

 

(CNT)

 

 

(SW10)

 

(SW7)

 

CNT

CNV

CNH

CNN1 CNN2 CNF CNB CNQ

SW2 SW10 SW8

SW9

CNZ CNI

 

 

 

 

 

Drain motor

CNO

 

 

SW5

SW7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L2 L3

CNR

 

 

52X4

CNJ2

52X5

52X3 52X2 52X1 52X6

F1

CNW1CNM3

L1

CNW0

LED2

 

 

CNO

 

 

 

LED1

 

 

CNA

L4

F2

F3

CNE

CNG

CNW2

CNK1 CNK2

PCB power supply connector

Power supply

PCB power supply connector

(Primary side)

 

(Secondary side)

Change by the jumper wire

 

Name

Function

J1 (SW7-1)

 

With

Input signal - Reverse invalid

 

None (1)

Input signal - Rus stop

 

 

J2 (SW7-2)

 

With

Heating thermostat OFF-Lo

 

None (1)

Heating thermostat OFF-Stop, Lo

 

 

J3 (SW7-3)

 

With

Normal operation operable

 

None (1)

Operation permission prohibited

 

 

J4 (SW7-4)

 

With

Normal

 

None (1)

Heating temp. +3

 

 

J6 (SW8-2)

 

With

Freeze prevention fan control activated

 

None (1)

Freeze prevention fan control deactivated

 

 

Note (1) “None” means that jumper wire is not provided on the PCB or the connection is cut

(2)The replacement board is not equipped with jumpers J1 ~ J4, J6. Instead, SW7 and 8, with the same functions as jumpers J1~J4, J6, are used in the position where the jumpers were previously. Set SW7 and 8 locally in accordance with the above table.

Control change switch (SW5, SW9, SW10)

Function of DIP switch SW5 (Usually all turned OFF)

 

Switch

 

Function

 

ON

 

ON

Setting time : 1000hrs. (Unit stop)

SW5-3

SW5-4

OFF

Setting time : 1000hrs. (Display)

 

OFF

ON

Setting time : 600hrs. (Display)

 

 

 

 

OFF

Setting time : 180hrs. (when shipped from factory)

 

 

 

Function of DIP switch SW9 (Usually all turned OFF)

 

Switch

Function

SW9-3

 

ON

Emergency operation

 

OFF

Normal

 

 

SW9-4

 

ON

Fan control : High speed (High Ceiling)

 

OFF

Fan control : Standard

 

 

Function of DIP switch SW10 (Usually all turned OFF)

 

Switch

 

Function

 

OFF

 

OFF

Remote controller air flow

SW10-2

SW10-3

ON

Remote controller air flow

1 speed

 

(J10)

ON

(J11)

OFF

Remote controller air flow

2 speed

ON

Remote controller air flow

3 speed

 

 

 

- 11 -

Page 13
Image 13
Hunter Fan R410A manual Model FDUR series, Change by the jumper wire, Control change switch SW5, SW9, SW10, Name, Function