Sunway NT 10000 user manual Structure of NT

Page 12

Structure of NT 10000

The Solar Inverter NT 10000 is made up of three energy units that are controlled independently of each other. Each energy unit has its own DC inlet.

Energy Unit

DC Inlet

Energy unit 1

DC inlet 1

Energy unit 2

DC inlet 2

Energy unit 3

DC inlet 3

Control Circuit Board

Control circuit board 1

Control circuit board 2

Control circuit board 3

AC Grid Connection

Phase L1

Phase L2

Phase L3

The following illustration shows the con- nection of the DC inlet and the layout of the energy unit:

96

Image 12
Contents Sunways Solar Inverter NT Solar Safety Instructions Basic SettingsInstallation Sunways Solar InverterConfiguration of the Solar Inverter Dismantling the Solar InverterOperating the Display Internal Data MemoryError Display Error DiagnosisTyco Solarlok Connectors Abbreviations Technical Data NTGeneral information General Safety Instructions Opening the Device Sunways Solar Inverter NT Scope of DeliveryChecking the Consignment Page Standard Components of a PV System Standard components of the PV systemStructure of NT Page Error No Description Error DescriptionProtection Concept Page Installation Instructions Electrical Safety Mechanical SafetyCleaning Instructions Basic Settings Fixed voltage level 420 540Country Settings Page Ceiling 300 mm Min mm · Thermal Interaction · Protection from Moisture and Foreign ObjectsMechanical Installation Grid Connection DC+ USBThree-phase grid connection 25 aPage Connecting the PV Generator · Preparation · Connection Important InformationPage Communication Interfaces · RS485 Wiring · Connecting a cable to the spring-loaded terminalSpare RS485MATCH RS485GND Connecting the Alarm Relay · Important InformationParalleled alarm relays of several Solar Inverters Alarm relay terminal allocationConnecting the Insolation Temperature Sensor · Allocation of the cable terminal block Sensor pin nameSolar inverter pin name Start-up with DC main switch Commissioning the Solar InverterStarting-Up and Shutting-Down Solar Inverter Start-up without DC main switch Shut-down with DC main switchShut-down without DC main switch Operating Instructions · Setting Values · Menu Guide· Navigating with the Arrow Keys Page Page Configuring the Solar Inverter Internal Data Memory Sunways Monitor 2.0 Software Sunways Portal and Sunways Communicator Modem LinkInterface Cables Interface TransformerSunways Monitor DirectLink Monitor Local134 Modem Ad 5 Local Link for up to 99 Solar Inverters Spare RS485MATCH USBInverter 3 RS485 Ad 6 Remote Link for up to 99 Solar Inverters Finding the Jumper «RS485 MATCH» Solar InverterErrors 001 to Errors 004 toErrors 007 to Errors 013 toErrors 010 to ErrorErrors 017 to Errors 020 toErrors 023 to Errors 031 to Errors 028 toErrors 034 to Illustr. Operation indicator LED 143 Error Causes RemediesErrorCauses Remedies Error Causes ErrorCauses Error Causes Error Causes Error Causes 152 Appendix Tyco Solarlok Connectors Page LCD Designation Description MPPTechnical Data NT 10000 Model Solar Inverter NT159 Conformity and Safety Declarations 161 162 Terms and Conditions of Guarantee · Duration of Guarantee· Conditions · Exclusion of Liability General Exclusion of Liability All rights reserved. Sunways AGRegistered trademark Version 11/05