ErrorCauses
Objects have been deposi- ted on the heat sink, obstructing the convection.
Remedies
Remove the objects.
Errors 010 to 012 Grid under- voltage
The grid voltage of the injecting phase is too low. The Solar Inverter monitors the lower and upper admis- sible grid voltage limits. If the voltage drops below the
lower limit (Umin = 184 V), the Solar Inverter will auto-
matically switch off and will only restart when the volta- ge value rises above the lower limit again. The shut- down can already be trig- gered if the voltage drops below the lower limit for a short time.
Ask your power supply company about the stability and design of the grid.
Check the rating of your grid connection (power meter) or the grid injection point to your power supply company.
Errors 013 to 015 Grid overvoltage
The grid voltage of the injecting phase is too high. The Solar Inverter monitors the lower and upper admis- sible grid voltage limits.
Ask your power supply company about the stability and design of the grid.
145