American Power Conversion PD150L6F, PD150G6F manual PDU Alarms, Alarm Condition Explanation

Page 32

PDU Display Interface: Alarms Screen

PDU Alarms

This table lists all alarms that can be generated by the InfraStruXure PDU, as displayed by the All Possible Alarms option, with numeric variables between the < > characters. Logged alarms will display specific numbers instead.

Alarm Condition

Explanation

 

 

Input V <Ln-N> =<Value>

Input voltage of the phase indicated has dropped below the

Voltage Under Limit

configured lower limit.

 

 

Input V <Ln-N> =<Value>

Input voltage of the phase indicated exceeded the configured

Voltage Over Limit

upper limit.

 

 

Output V <Ln-N> =<Value>

Phase-to-neutral output voltage for phase <L-N> dropped below

Voltage Under Limit

the configured limit.

 

 

Output V <Ln-N>=<Value>

Phase-to-neutral output voltage for phase <L-N> exceeded the

Voltage Over Limit

configured limit.

 

 

Output I L<n>=<Value>

Current of output phase <N> exceeded the configured limit.

Current Over Limit

 

 

 

Output I L<n>=<Value>

Current of output phase<N> dropped below the configured limit.

Current Under Limit

 

 

 

Output Neut=<Value>

Current on the neutral wire for the output phases exceeded the

Current Over Limit

configured limit.

 

 

Output FDev=<Value>

Frequency of the output current is above or below the range that

Freq Out of Range

is configured as acceptable.

 

 

Input Transformer Temperature

The temperature of the PDU transformer exceeded the normal

Too High

limit, if applicable.

 

 

Main Breaker Open

The Main Input Switch is Off.

Alarm Active

 

 

 

<User Contact Name>

A user-configured contact connected to the PDU monitoring unit

Alarm Active

is reporting an alarm condition.

 

 

No UPS Input

The Main circuit breaker is open, and the PDU is not receiving

Breaker Q1 Open

power from the UPS.

 

 

Branch Ckt Pos: <nn>

Current on one of the poles of branch circuit breaker nn exceeded

Current Over Limit

the configured limit.

 

 

Branch Ckt Pos: <nn>

Current on one of the poles of branch circuit breaker nn dropped

Current Under Limit

below the configured limit.

 

 

Fan Rotation Failure

There is a failure in one of the fans. The fan needs to be replaced,

Alarm Active

if applicable.

 

 

24

150kW InfraStruXure PDU—Operation and Configuration

Image 32
Contents 150kW InfraStruXure PDU Page About this Manual Page Contents Operation Customizing and Updating the PDU Product Information Overview Safety symbols used in this manualCross-reference symbols used in this manual Installation/maintenance Receiving/movingTotal power off procedure Emergency Power Off EPOEMI Overview InfraStruXure PDU ComponentsInfraStruXure PDU Front viewFront view interior Rear view Rear view interior PDU monitoring unit Left = 43..83 lower right = User connection plate PDU Display Interface Navigating through screens Top-level status screensTop-level menu screen Password-protected screens Power Factor Load-Meter ScreenVolt-Meter Screen Contacts Screen Input ContactsOpen or Closed Relay OutputsAlarm Relay Map How to connect contacts to the PDU monitoring unit Breakers Screen Main InputAlarms Screen New Logged ItemsEntire Log Clear LogGlobal Alarm ConfigLoading Limits Voltage LimitsPDU Alarms Alarm Condition ExplanationBranch Ckt Limits Panel ScreenBranch Ckt Loading Top right distribution panel Panel ConfigurationCircuit breakers occupying positions 08, 10, and 12 on Global Panel Config Config Screen System PasswordBeeper Volume Select High , Medium , Low , or Off to adjust Date/TimeElectrical Config Input ConfigOutput Config Manufacturer DataSystem ID Factory DefaultsFirmware Updates How to Apply Power to the System OperationOperation How to Apply Power to the System How to Ensure Total Power Off Page InfraStruXure PDU Management Options OverviewInfraStruXure Manager Network management interfacesConfiguring the InfraStruXure Manager Connect the InfraStruXure PDU to the InfraStruXure ManagerConnect the InfraStruXure PDU to your network Configuring the Network Management InterfaceConfiguration Overview TCP/IP configuration methods Device IP Configuration WizardBootp & Dhcp configuration Option 43 = 01 04 31 41 50 43 where 150kW InfraStruXure PDU-Operation and Configuration Remote access to the control console Local access to the control consoleUse apc for the User Name and Password Choose Network from the Control Console menu Use apc for both User Name and PasswordControl console Web interface Snmp FTP and SCP 150kW InfraStruXure PDU-Operation and Configuration Page Important Safety Instructions Customizing and Updating the PDUPDU Orderable Part List BreakersCustomizing and Updating the PDU Add a circuit breaker on the PDU How to Add Circuit Breakers and Power CablesAdd a power cable to the PDU Customizing and Updating the PDU Overview How to attach the circuit breaker to the mounting brackets How to connect the sub-feed cable to the circuit breaker ATS 0 ATS 1 ATS Atsen How to connect contacts to the PDU monitoring unit How to Connect an EPO Switch to the PDU and Test the Switch Contact closure 24VAC 24VDC Contact closure is recommended24VAC/VDC-Normally Open Contact Closure-Normally OpenContact Closure-Normally Closed Problem Action Safety warnings How to Download Firmware Updates From a local computerPage Specifications 150kW InfraStruXure PDUPhysical PD150G6F PD150L6F Warranty InfraStruXure Standard WarrantyProduct Information Warranty APC Three-Phase Systems Life-Support PolicyHow to Obtain Service How to contact APCIndex SSH Page Page Page 990-1984