American Power Conversion PD150G6F, PD150L6F manual Customizing and Updating the PDU

Page 59

Customizing and Updating the PDU

Power Cables

30A, 3-wire power cables

20A, 3-wire power cables

 

 

 

 

SKU Number

Description

SKU Number

Description

PDW49L6-30C

49-foot power cable

PDW47L21-20R

47-foot power cable

PDW51L6-30C

51-foot power cable

PDW49L21-20R

49-foot power cable

PDW53L6-30C

53-foot power cable

PDW51L21-20R

51-foot power cable

PDW55L6-30C

55-foot power cable

PDW53L21-20R

53-foot power cable

PDW57L6-30C

57-foot power cable

PDW55L21-20R

55-foot power cable

PDW59L6-30C

59-foot power cable

PDW57L21-20R

57-foot power cable

PDW61L6-30C

61-foot power cable

PDW59L21-20R

59-foot power cable

PDW63L6-30C

63-foot power cable

PDW61L21-20R

61-foot power cable

PDW65L6-30C

65-foot power cable

PDW63L21-20R

63-foot power cable

PDW67L6-30C

67-foot power cable

 

 

PDW69L6-30C

69-foot power cable

 

 

PDW71L6-30C

71-foot power cable

 

 

PDW73L6-30C

73-foot power cable

 

 

PDW75L6-30P

75-foot power cable

 

 

 

 

 

 

150kW InfraStruXure PDU—Operation and Configuration

51

Image 59
Contents 150kW InfraStruXure PDU Page About this Manual Page Contents Operation Customizing and Updating the PDU Product Information Overview Safety symbols used in this manualCross-reference symbols used in this manual Receiving/moving Installation/maintenanceEmergency Power Off EPO Total power off procedureEMI InfraStruXure PDU Components OverviewFront view InfraStruXure PDUFront view interior Rear view Rear view interior PDU monitoring unit Left = 43..83 lower right = User connection plate PDU Display Interface Navigating through screens Top-level status screensTop-level menu screen Password-protected screens Load-Meter Screen Power FactorVolt-Meter Screen Relay Outputs Contacts ScreenInput Contacts Open or ClosedAlarm Relay Map How to connect contacts to the PDU monitoring unit Main Input Breakers ScreenClear Log Alarms ScreenNew Logged Items Entire LogVoltage Limits Global AlarmConfig Loading LimitsAlarm Condition Explanation PDU AlarmsBranch Ckt Limits Panel ScreenBranch Ckt Loading Top right distribution panel Panel ConfigurationCircuit breakers occupying positions 08, 10, and 12 on Global Panel Config Date/Time Config ScreenSystem Password Beeper Volume Select High , Medium , Low , or Off to adjustManufacturer Data Electrical ConfigInput Config Output ConfigSystem ID Factory DefaultsFirmware Updates Operation How to Apply Power to the SystemOperation How to Apply Power to the System How to Ensure Total Power Off Page Network management interfaces InfraStruXure PDU Management OptionsOverview InfraStruXure ManagerConnect the InfraStruXure PDU to the InfraStruXure Manager Configuring the InfraStruXure ManagerConnect the InfraStruXure PDU to your network Configuring the Network Management InterfaceConfiguration Overview Device IP Configuration Wizard TCP/IP configuration methodsBootp & Dhcp configuration Option 43 = 01 04 31 41 50 43 where 150kW InfraStruXure PDU-Operation and Configuration Remote access to the control console Local access to the control consoleUse apc for the User Name and Password Choose Network from the Control Console menu Use apc for both User Name and PasswordControl console Web interface Snmp FTP and SCP 150kW InfraStruXure PDU-Operation and Configuration Page Customizing and Updating the PDU Important Safety InstructionsBreakers PDU Orderable Part ListCustomizing and Updating the PDU Add a circuit breaker on the PDU How to Add Circuit Breakers and Power CablesAdd a power cable to the PDU Customizing and Updating the PDU Overview How to attach the circuit breaker to the mounting brackets How to connect the sub-feed cable to the circuit breaker ATS 0 ATS 1 ATS Atsen How to connect contacts to the PDU monitoring unit Contact closure 24VAC 24VDC Contact closure is recommended How to Connect an EPO Switch to the PDU and Test the Switch24VAC/VDC-Normally Open Contact Closure-Normally OpenContact Closure-Normally Closed Problem Action Safety warnings From a local computer How to Download Firmware UpdatesPage 150kW InfraStruXure PDU SpecificationsPhysical PD150G6F PD150L6F InfraStruXure Standard Warranty WarrantyProduct Information Warranty Life-Support Policy APC Three-Phase SystemsHow to contact APC How to Obtain ServiceIndex SSH Page Page Page 990-1984