APC 6000 Connection of auxiliary circuits on the remote relay board, XR1 XR2 XR3 XR4

Page 26

Installation (cont.)

Connection of "Media Contacts 9" standard auxiliary circuits (figure 16)

The standard auxiliary circuits of the rectifier-inverter and Static Switch Cubicles are connected to the remote relay board by 4 connectors (see the location of this board in the figures of the previous section).

recommended cable cross-section: 1 mm2 (use a shielded cable to connect the battery cell);

the male connectors that fit the female connectors on the board (XR1 to XR4) are supplied;

the contacts are volt-free and are shown in the diagram under the following conditions: UPS on, contact at rest;

contact breaking capacity: 250V, 5A.

Connection of auxiliary circuits on the remote relay board

remote

1

12

1

12

1

12

1

12

 

 

 

 

 

 

 

 

 

 

 

 

 

relay board

 

XR1

 

 

 

XR2

 

XR3

 

XR4

connector XR1

 

 

output signals:

 

 

 

 

 

 

 

 

 

connector XR2

connector XR3

+12V

24 V DC

-12V

connector XR4

temperature signal

power -12V

supply +12V earth

earth

1

2

3

4

5

6

7

8

9

10

11

12

1

2

3

4

5

6

7

8

9

10

11

12

1

2

3

4

5

6

7

8

9

10

11

12

1

2

3

4

5

6

7

8

9

10

11

12

low battery shutdown warning (1)

low battery shutdown warning (1)

load on battery (1)

load on battery (1)

output signals:

load on inverter (2)

load on inverter (2)

general alarm (2)

general alarm (2)

input or output signals:

maintenance position (2)

shielded cable (2 twisted

telephone pairs)

maintenance position (2)

battery circuit breaker QF1 opening command (1)

input or output signals:

battery room ventilation fault (1)

and/or harmonics filter temperature fault

connection with the optional electronic board for measuring battery temperature (1)

emergency shutdown button contact (jumper if not used) (1)

(1)for:

single-unit UPS cubicle,

modular UPS cubicle,

parallel UPS cubicle with SSC.

(2)for:

single-unit UPS cubicle,

modular UPS cubicle,

parallel UPS cubicle with SSC,

Static Switch cubicle.

battery cubicle (1)

XR1 terminal block

3

battery circuit

breaker QF1

4

opening command

 

1

battery circuit

 

breaker QF1

2

closing command

 

harmonics filter cubicle

XR1 terminal block

1 temperature

2monitoring of the harmonics filter inductor

Fig. 16

Page 26 - 6739381EN/JD

Image 26
Contents Mgetm GalaxyTM 2 6739381EN/JD Contents Characteristics Characteristics common to all cubiclesRectifier-inverter cubicles Static Switch cubiclesExternal maintenance bypass cubicles Pack Advance cubiclesRemark Electrical parameters for selecting protective devicesElectrical parameters for Mains Electrical parameters for Mains 2Electrical parameters for determining cable cross-sections Heat lossesNumber Total UPS Installation with parallel frequency convertersInstallation with parallel UPSs with a centralised SSC Line current Mm2 KVA Inverters Amps Copper AluminiumKVA Inverters Amps Copper Number Total UPS Mains 2 or loadLine current Side clearances provided by the spacing uprights Rear HandlingPositioning the cubicles FrontCubicle layout on false floor or normal floor figures 6, 7 Layout for a single-unit UPS with one battery cubicleFloor loads figure Cubicle footpads RearSpecial case Power circuit wiring diagramsConnection via the top Rectifier-inverter cubicleStatic Switch Cubicle Diagram for a frequency converter with batteriesDiagram for a frequency converter without batteries Example of a 2 parallel UPS rectifier-inverters with SSCModular UPS cubicle External maintenance bypass cubicle Cross-section AA Connection of power circuitsGeneral 160kVA to 400kVA modular UPS rectifier-inverter cubicle KVA single-unit UPS cubicles see the appendixApoz 600kVA parallel UPS cubicles see the appendixXR2 XR5 XR3 XR6 Acpz XR4 XR7 Off 500kVA single-unit UPS rectifier-inverter cubicle600kVA single-unit UPS cubicles see the appendix XR4 XR7XR4 XR7 XM5 500kVA modular UPS rectifier-inverter cubicleXM7 XR2 XR5 XR1 XR8 Air admission Mains 1, load BatteryL1L2 L3 L1 L2 L3 Mains Battery Load XM133 Q1onXR9 XR2 Q4S 500/800kVA Static Switch CubicleFront Rear XR3 XR4 XR7XR7 XR4 UPS XR6 1200kVA Static Switch CubicleFront view XR3 XR5 XR2 XR9 XR1 XR8Terminal Important noteAuxiliary Block XR11200kVA external maintenance bypass cubicle Key to figureConnection of auxiliary circuits on the remote relay board XR1 XR2 XR3 XR4Emergency shutdown Connection to battery circuit breaker QF1Connections between cubicles Connections between Apoz boards127 128 129 130 131 Connections between Misi boards modular UPSsXM XM XM XM XM XM MisiMisi Acpz board of the Static Switch Cubicle XR8 XR9 XR5 XR6 XR7Connection of the battery Temperature Monitor optional ConnectionsTemperature Monitor installation in a battery room Temperature Monitor installation in a APC bySchneider Electric battery cubicle Installing the Temperature Monitor in a battery cubicleLink to an IBM AS/400→ computer Rauz 1 board XM098 XM097 XR11 XM096 XR10 Connector XR10Connection of the LED remote indications unit Consult manual 6739388XU for further informationConnection to the Media Contacts 9 relay board Final installation stepsConfiguration of the AS/400→ After making the connectionsUPS 250 to 450kVA Mains 2 line protectionRated inverter output Maximum permissible current KVA UPS 500kVAInternal connections between cubicles Cubicle mounting and connection for 600kVA UPSsCubicle mounting Connection of power and auxiliary circuits Left cubicle of 600kVA single-unit or parallel UPS with SSCMains Load L1 L2 L3 Air Admission Right cubicle of a 600kVA single-unit UPSXR2 XR5 XR3 XR6 XR4 XR7 XR3 XR6 XR4 Right cubicle of a 600kVA parallel UPS with SSCAir admission Load Q3BP XF1-XF2 XM1-XM2 Left cubicleRight cubicle Card cageAir admission Air extraction Right cubicle of a 2000kVA Static SwitchCross-section AA Front view Mains OffXR9 XR1 XR8 Left cubicle of a 2000kVA Static SwitchXR6 XR3 XR5 XR2 450 500kVA rectifier-inverter cubicle Details of earthing connections in the various cubicles250 to 400kVA rectifier-inverter cubicle Inverter inputInverter Input 120 to 1200kVA Static Switch Cubicles600kVA rectifier-inverter cubicle Connection with Bolt, nut andmains 2 contact washer 2000kVA Static Switch CubiclesTele-Monitor unit Tele Monitor unit6739381ENPage 46 --JD6739381EN/JD