Installation (cont.)
Connection of "Media Contacts 9" standard auxiliary circuits (figure 16)
The standard auxiliary circuits of the
◗recommended cable
◗the male connectors that fit the female connectors on the board (XR1 to XR4) are supplied;
◗the contacts are
◗contact breaking capacity: 250V, 5A.
Connection of auxiliary circuits on the remote relay board
remote | 1 | 12 | 1 | 12 | 1 | 12 | 1 | 12 | |||||
|
|
|
|
|
|
|
|
|
|
|
|
| |
relay board |
| XR1 |
|
|
| XR2 |
| XR3 |
| XR4 | |||
connector XR1 |
|
| output signals: |
|
|
|
|
|
|
|
|
|
connector XR2
connector XR3
+12V
24 V DC
connector XR4
temperature signal
power
supply +12V earth
earth
1
2
3
4
5
6
7
8
9
10
11
12
1
2
3
4
5
6
7
8
9
10
11
12
1
2
3
4
5
6
7
8
9
10
11
12
1
2
3
4
5
6
7
8
9
10
11
12
low battery shutdown warning (1)
low battery shutdown warning (1)
load on battery (1)
load on battery (1)
output signals:
load on inverter (2)
load on inverter (2)
general alarm (2)
general alarm (2)
input or output signals:
maintenance position (2)
shielded cable (2 twisted
telephone pairs)
maintenance position (2)
battery circuit breaker QF1 opening command (1)
input or output signals:
battery room ventilation fault (1)
and/or harmonics filter temperature fault
connection with the optional electronic board for measuring battery temperature (1)
emergency shutdown button contact (jumper if not used) (1)
(1)for:
◗
◗modular UPS cubicle,
◗parallel UPS cubicle with SSC.
(2)for:
◗
◗modular UPS cubicle,
◗parallel UPS cubicle with SSC,
◗Static Switch cubicle.
battery cubicle (1)
XR1 terminal block
3 | battery circuit | |
breaker QF1 | ||
4 | ||
opening command | ||
|
1 | battery circuit | |
| breaker QF1 | |
2 | ||
closing command | ||
|
harmonics filter cubicle
XR1 terminal block
1 temperature
2monitoring of the harmonics filter inductor
Fig. 16