Installation (cont.)
500/800kVA Static Switch Cubicle
| front view |
front | rear | spacing |
|
|
|
| A | spacing |
|
|
|
|
|
| |||
|
| uprights |
|
|
|
|
| uprights |
|
|
|
|
| static |
|
| |
|
|
|
| card | switch |
|
| |
|
|
|
|
|
|
|
| |
|
|
|
| cage |
|
|
|
|
XM127 to 132 |
| XM127 to 132 |
|
|
|
|
| |
|
|
|
|
|
|
|
| |
|
|
| XR1 | XR8 | off |
|
|
|
|
|
| XR9 |
|
|
| ||
|
|
| XR2 |
| Q4S |
|
| |
| remote relay | XR5 | on |
|
| |||
mains 2 |
|
|
|
| ||||
| XR6 |
|
|
|
| |||
board |
| XR3 |
|
|
|
| ||
|
|
|
|
|
| |||
|
|
| XR4 | XR7 |
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
| off |
| N L1 L2 L3 |
|
|
|
|
|
|
| mains 2 |
| |
| additional relay |
|
|
| Q3BP |
| ||
|
|
| on |
|
| |||
| board (optional) |
|
|
|
|
| ||
|
|
|
|
|
|
| ||
inverter |
|
|
|
|
|
|
|
|
outputs |
|
|
| N L1 L2 L3 | off |
| N L1 L2 L3 |
|
and load |
|
|
|
|
| |||
|
|
| inverter |
| load |
| ||
|
|
|
|
|
| |||
|
|
|
|
| Q5N |
| ||
|
|
|
| outputs | on |
|
| |
|
|
|
|
|
|
| ||
earth |
|
|
|
|
|
|
| mass |
|
|
|
|
|
|
| bar | |
bar |
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| |
| connection |
|
|
|
|
| A |
|
| from below |
|
|
|
|
|
| |
|
| power cable routing via the top |
|
|
| |||
| trough (if applicable) |
|
|
|
| |||
|
|
|
|
|
|
|
| |
|
|
| power cable routing via the bottom |
|
|
500kVA Static Switch Cubicle:
Cables connected by lugs to 80 x 5 mm copper terminals and 13 mm diameter holes.
800kVA Static Switch Cubicle:
Cables connected by lugs to 80 x 8 mm copper terminals and 13 mm diameter holes.
Height of connections relative to floor:
◗mains 2: 1050 mm max.;
◗inverter outputs and load: 570 mm;
◗remote relay board: 1190 mm max.
Page 22 - 6739381EN/JD