APC 6000 Temperature Monitor installation in a APC by, Schneider Electric battery cubicle

Page 32

Installation (cont.)

"Temperature Monitor" installation in a APC by

Installing the "Temperature Monitor" in a battery cubicle

Schneider Electric battery cubicle

The "Temperature Monitor" is fitted on mounting brackets inside the left-hand door of the battery cubicle containing circuit breaker QF1 (see figure 25). The unit is self-adhesive and is secured simply by pressing it against the door:

before mounting the unit, break the

knock-out in its base plate provided for

feeding through the connecting cable;

clean the mounting location on the

door using isopropyl alcohol or heptane

to obtain a clean, dry adhesion surface

(comply with supplier safety

recommendations for handling

solvents);

it is essential, for correct temperature

sensor operation, for the unit to be

positioned as shown in figure 25 ("on"

light in the top left hand corner and

cable fed through from the right-hand

side);

"on" light

self-adhesive

mounting brackets

tie the cable to the cubicle upright

battery cubicle

tie

the

cable

 

 

 

QF1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

to the

cubicle

 

 

 

 

 

upright

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

to rectifier-inverter

firm pressure is required to ensure

that the unit is bonded over the full

adhesive surface;

the door should be at a temperature

of at least 10°C;

after installation, fold up the

mounting bracket tabs to fully secure

the unit;

tie the connecting cable to the

cubicle upright so that it does not pull

on the unit.

Fig. 25

"Temperature Monitor" installation in a battery room

The "Temperature Monitor" should be secured against a wall or any vertical support:

choose a location near the batteries and away from draughts which adversely affect the accuracy of temperature measurements;

position the unit correctly ("on" light in the top left hand corner and cable fed through from the right-hand side);

use the holes provided in the base plate to screw the unit to the vertical support (see figure 26);

unless the connecting cable runs on the surface, break the knock-out in the unit base plate provided for cable entry;

secure the cable by suitable means so that it does not pull on the unit.

"Temperature Monitor" base

 

oblong holes

 

for fastening screws

board

knock-out for

 

lateral cable

 

entry

oblong holes

for fastening screws

dimensions of the "Temperature Monitor": 75 x 75 x 21 mm

Fig. 26

Page 32 - 6739381EN/JD

Image 32
Contents Mgetm GalaxyTM 2 6739381EN/JD Contents Characteristics Characteristics common to all cubiclesStatic Switch cubicles External maintenance bypass cubiclesRectifier-inverter cubicles Pack Advance cubiclesElectrical parameters for selecting protective devices Electrical parameters for MainsRemark Electrical parameters for Mains 2Electrical parameters for determining cable cross-sections Heat lossesInstallation with parallel frequency converters Installation with parallel UPSs with a centralised SSCNumber Total UPS Line current Mm2 KVA Inverters Amps Copper AluminiumKVA Inverters Amps Copper Number Total UPS Mains 2 or loadLine current Handling Positioning the cubiclesSide clearances provided by the spacing uprights Rear FrontLayout for a single-unit UPS with one battery cubicle Floor loads figureCubicle layout on false floor or normal floor figures 6, 7 Cubicle footpads RearPower circuit wiring diagrams Connection via the topSpecial case Rectifier-inverter cubicleDiagram for a frequency converter with batteries Diagram for a frequency converter without batteriesStatic Switch Cubicle Example of a 2 parallel UPS rectifier-inverters with SSCModular UPS cubicle External maintenance bypass cubicle Cross-section AA Connection of power circuitsGeneral 160kVA to 400kVA modular UPS rectifier-inverter cubicle KVA single-unit UPS cubicles see the appendixApoz 600kVA parallel UPS cubicles see the appendixXR2 XR5 XR3 XR6 Acpz XR4 XR7 500kVA single-unit UPS rectifier-inverter cubicle 600kVA single-unit UPS cubicles see the appendixOff XR4 XR7XR4 XR7 XM5 500kVA modular UPS rectifier-inverter cubicleXM7 XR2 XR5 Air admission Mains 1, load Battery L1L2 L3 L1 L2 L3 Mains Battery LoadXR1 XR8 XM133 Q1on500/800kVA Static Switch Cubicle Front RearXR9 XR2 Q4S XR3 XR4 XR71200kVA Static Switch Cubicle Front viewXR7 XR4 UPS XR6 XR3 XR5 XR2 XR9 XR1 XR8Important note AuxiliaryTerminal Block XR11200kVA external maintenance bypass cubicle Key to figureConnection of auxiliary circuits on the remote relay board XR1 XR2 XR3 XR4Connection to battery circuit breaker QF1 Connections between cubiclesEmergency shutdown Connections between Apoz boardsConnections between Misi boards modular UPSs XM XM XM XM XM XM127 128 129 130 131 MisiMisi Acpz board of the Static Switch Cubicle XR8 XR9 XR5 XR6 XR7Connection of the battery Temperature Monitor optional ConnectionsTemperature Monitor installation in a APC by Schneider Electric battery cubicleTemperature Monitor installation in a battery room Installing the Temperature Monitor in a battery cubicleRauz 1 board XM098 XM097 XR11 XM096 XR10 Connector XR10 Connection of the LED remote indications unitLink to an IBM AS/400→ computer Consult manual 6739388XU for further informationFinal installation steps Configuration of the AS/400→Connection to the Media Contacts 9 relay board After making the connectionsMains 2 line protection Rated inverter output Maximum permissible current KVAUPS 250 to 450kVA UPS 500kVAInternal connections between cubicles Cubicle mounting and connection for 600kVA UPSsCubicle mounting Connection of power and auxiliary circuits Left cubicle of 600kVA single-unit or parallel UPS with SSCMains Load L1 L2 L3 Air Admission Right cubicle of a 600kVA single-unit UPSXR2 XR5 XR3 XR6 XR4 XR7 XR3 XR6 XR4 Right cubicle of a 600kVA parallel UPS with SSCAir admission Load Left cubicle Right cubicleQ3BP XF1-XF2 XM1-XM2 Card cageRight cubicle of a 2000kVA Static Switch Cross-section AA Front viewAir admission Air extraction Mains OffXR9 XR1 XR8 Left cubicle of a 2000kVA Static SwitchXR6 XR3 XR5 XR2 Details of earthing connections in the various cubicles 250 to 400kVA rectifier-inverter cubicle450 500kVA rectifier-inverter cubicle Inverter inputInverter Input 120 to 1200kVA Static Switch Cubicles600kVA rectifier-inverter cubicle 2000kVA Static Switch Cubicles Tele-Monitor unitConnection with Bolt, nut andmains 2 contact washer Tele Monitor unit6739381ENPage 46 --JD6739381EN/JD