Appendix (to be carried out by qualified personnel only)

Mains 2 line protection

The rating of the mains 2 line upstream protection circuit-breaker must be chosen:

to protect the static switch thyristors with respect to maximum permissible currents. Refer to the table opposite for a 400V mains 2 voltage;

to ensure discrimination with respect to the UPS output fuses (refer to fuse time-current curves below) and to the downstream protective devices.

rated inverter output

maximum permissible current

(kVA)

 

250 to 300

10 In for 20 ms

400 to 450

13 In for 20 ms

500 to 600

27 In for 20 ms

UPS 250 to 450kVA

t(s)

104

103

102

101

1

10-1

10-2

10-3

10-4

102103104

Time-current curve 630A fuse

UPS 500kVA

t(s)

104

103

102

101

1

10-1

10-2

10-3

I(A) 10-4

102103104

Time-current curve 800A fuse

UPS 600kVA

t(s)

104

103

102

101

1

10-1

10-2

10-3

10-4

103

104

I(A)

102

I(A)

Time-current curve 1250A fuse

6739381EN/

Image 35
Contents Mgetm GalaxyTM 2 6739381EN/JD Contents Characteristics common to all cubicles CharacteristicsPack Advance cubicles Static Switch cubiclesExternal maintenance bypass cubicles Rectifier-inverter cubiclesElectrical parameters for Mains 2 Electrical parameters for selecting protective devicesElectrical parameters for Mains RemarkHeat losses Electrical parameters for determining cable cross-sectionsLine current Mm2 KVA Inverters Amps Copper Aluminium Installation with parallel frequency convertersInstallation with parallel UPSs with a centralised SSC Number Total UPSKVA Inverters Amps Copper Number Total UPS Mains 2 or loadLine current Front HandlingPositioning the cubicles Side clearances provided by the spacing uprights RearCubicle footpads Rear Layout for a single-unit UPS with one battery cubicleFloor loads figure Cubicle layout on false floor or normal floor figures 6, 7Rectifier-inverter cubicle Power circuit wiring diagramsConnection via the top Special caseExample of a 2 parallel UPS rectifier-inverters with SSC Diagram for a frequency converter with batteriesDiagram for a frequency converter without batteries Static Switch CubicleModular UPS cubicle External maintenance bypass cubicle Cross-section AA Connection of power circuitsGeneral KVA single-unit UPS cubicles see the appendix 160kVA to 400kVA modular UPS rectifier-inverter cubicleApoz 600kVA parallel UPS cubicles see the appendixXR2 XR5 XR3 XR6 Acpz XR4 XR7 XR4 XR7 500kVA single-unit UPS rectifier-inverter cubicle600kVA single-unit UPS cubicles see the appendix OffXR4 XR7 XM5 500kVA modular UPS rectifier-inverter cubicleXM7 XR2 XR5 XM133 Q1on Air admission Mains 1, load BatteryL1L2 L3 L1 L2 L3 Mains Battery Load XR1 XR8XR3 XR4 XR7 500/800kVA Static Switch CubicleFront Rear XR9 XR2 Q4SXR3 XR5 XR2 XR9 XR1 XR8 1200kVA Static Switch CubicleFront view XR7 XR4 UPS XR6Block XR1 Important noteAuxiliary TerminalKey to figure 1200kVA external maintenance bypass cubicleXR1 XR2 XR3 XR4 Connection of auxiliary circuits on the remote relay boardConnections between Apoz boards Connection to battery circuit breaker QF1Connections between cubicles Emergency shutdownMisi Connections between Misi boards modular UPSsXM XM XM XM XM XM 127 128 129 130 131Misi XR8 XR9 XR5 XR6 XR7 Acpz board of the Static Switch CubicleConnections Connection of the battery Temperature Monitor optional Installing the Temperature Monitor in a battery cubicle Temperature Monitor installation in a APC by Schneider Electric battery cubicle Temperature Monitor installation in a battery roomConsult manual 6739388XU for further information Rauz 1 board XM098 XM097 XR11 XM096 XR10 Connector XR10Connection of the LED remote indications unit Link to an IBM AS/400→ computerAfter making the connections Final installation stepsConfiguration of the AS/400→ Connection to the Media Contacts 9 relay boardUPS 500kVA Mains 2 line protectionRated inverter output Maximum permissible current KVA UPS 250 to 450kVAInternal connections between cubicles Cubicle mounting and connection for 600kVA UPSsCubicle mounting Left cubicle of 600kVA single-unit or parallel UPS with SSC Connection of power and auxiliary circuitsMains Load L1 L2 L3 Air Admission Right cubicle of a 600kVA single-unit UPSXR2 XR5 XR3 XR6 XR4 XR7 XR3 XR6 XR4 Right cubicle of a 600kVA parallel UPS with SSCAir admission Load Card cage Left cubicleRight cubicle Q3BP XF1-XF2 XM1-XM2Mains Off Right cubicle of a 2000kVA Static SwitchCross-section AA Front view Air admission Air extractionXR9 XR1 XR8 Left cubicle of a 2000kVA Static SwitchXR6 XR3 XR5 XR2 Inverter input Details of earthing connections in the various cubicles250 to 400kVA rectifier-inverter cubicle 450 500kVA rectifier-inverter cubicleInverter Input 120 to 1200kVA Static Switch Cubicles600kVA rectifier-inverter cubicle Tele Monitor unit 2000kVA Static Switch CubiclesTele-Monitor unit Connection with Bolt, nut andmains 2 contact washer6739381ENPage 46 --JD6739381EN/JD