Appendix (to be carried out by qualified personnel only)
Mains 2 line protection
The rating of the mains 2 line upstream protection
◗to protect the static switch thyristors with respect to maximum permissible currents. Refer to the table opposite for a 400V mains 2 voltage;
◗to ensure discrimination with respect to the UPS output fuses (refer to fuse
rated inverter output | maximum permissible current |
(kVA) |
|
250 to 300 | 10 In for 20 ms |
400 to 450 | 13 In for 20 ms |
500 to 600 | 27 In for 20 ms |
UPS 250 to 450kVA
t(s)
104
103
102
101
1
102103104
UPS 500kVA
t(s)
104
103
102
101
1
I(A)
102103104
UPS 600kVA
t(s)
104
103
102
101
1
103 | 104 | I(A) | |
102 |
I(A)
6739381EN/