APC 6000 Installation with parallel frequency converters, Number Total UPS, Parallel-connected

Page 8

Characteristics (cont.)

The table opposite serves as an example for an installation comprising up to four frequency converters or four parallel UPSs with a centralised SSC.

for installations with redundant units, take into account only the units required to supply the load power (e.g. for an installation made up of 3 parallel-connected rectifier-inverter cubicles, one being redundant, only 2 rectifier-inverter cubicles are used to determine Mains 2 and load currents and cable cross-sections);

this table has been drawn up for rated phase-to-phase Mains 2 and load voltages of 415V and full rated load with a power factor of 0.8. For voltages of 380 or 400V, multiply the indicated currents by 1.09 and 1.04 respectively, then modify the cable cross-sections accordingly if necessary.

The cable cross-sections in this table are for the parts illustrated in bold on the following block diagrams (installation examples, figures 1 and 2).

Parameters for Mains 2 and load cables for an installation comprising frequency converters or parallel UPSs with a centralised SSC.

rated inverter

number of

total UPS

Mains 2 or load

cable cross-section (1)

output

parallel-connected

rated output

line current

in mm2

 

in kVA

inverters

in kVA

in Amps

Copper

Aluminium

250

2

500

722

2 x 185

2 x 300

 

3

750

1082

3 x 300

4 x 240

 

4

1000

1444

4 x 240

4 x 400

300

2

600

866

2 x 240

4 x 185

 

3

900

1299

4 x 240

4 x 400

 

4

1200

1732

Please consult us*

400

2

800

1298

4 x 185

4 x 300

 

3

1200

1947

Please consult us*

 

4

1600

2596

Please consult us*

 

 

 

 

 

 

450

2

900

1154

4 x 240

4 x 400

 

3

1350

1731

Please consult us*

 

4

1800

2308

Please consult us*

 

 

 

 

 

 

500

2

1000

1444

4 x 240

4 x 400

 

3

1500

2164

Please consult us*

 

4

2000

2888

Please consult us*

600

2

1200

1731

Please consult us*

 

3

1800

2598

Please consult us*

 

4

2400

3462

Please consult us*

(1) cable cross-sections are given for copper

maximum length of 100 m. For greater lengths,

conductors of the U1000 R02V type. They are

the cross-sections should be chosen to limit

calculated according to permissible temperature

voltage drops to 3%.

rise and allow for line voltage drops over a

 

NF C 15-100 authorizes a maximum of 4 cables per phase.

Installation with parallel frequency converters

mains 1

inverter 1

mains 1

inverter 2

load

mains 1

inverter 3

Fig. 1

Installation with parallel UPSs with a centralised SSC

mains 2

mains 1

mains 1

inverter 1

inverter 2

static switch cubicle

load

mains 1

inverter 3

Fig. 2

Page 8 - 6739381EN/JD

Image 8
Contents Mgetm GalaxyTM 2 6739381EN/JD Contents Characteristics Characteristics common to all cubiclesStatic Switch cubicles External maintenance bypass cubiclesRectifier-inverter cubicles Pack Advance cubiclesElectrical parameters for selecting protective devices Electrical parameters for MainsRemark Electrical parameters for Mains 2Electrical parameters for determining cable cross-sections Heat lossesInstallation with parallel frequency converters Installation with parallel UPSs with a centralised SSCNumber Total UPS Line current Mm2 KVA Inverters Amps Copper AluminiumKVA Inverters Amps Copper Number Total UPS Mains 2 or loadLine current Handling Positioning the cubiclesSide clearances provided by the spacing uprights Rear FrontLayout for a single-unit UPS with one battery cubicle Floor loads figureCubicle layout on false floor or normal floor figures 6, 7 Cubicle footpads RearPower circuit wiring diagrams Connection via the topSpecial case Rectifier-inverter cubicleDiagram for a frequency converter with batteries Diagram for a frequency converter without batteriesStatic Switch Cubicle Example of a 2 parallel UPS rectifier-inverters with SSCModular UPS cubicle External maintenance bypass cubicle Cross-section AA Connection of power circuitsGeneral 160kVA to 400kVA modular UPS rectifier-inverter cubicle KVA single-unit UPS cubicles see the appendixApoz 600kVA parallel UPS cubicles see the appendixXR2 XR5 XR3 XR6 Acpz XR4 XR7 500kVA single-unit UPS rectifier-inverter cubicle 600kVA single-unit UPS cubicles see the appendixOff XR4 XR7XR4 XR7 XM5 500kVA modular UPS rectifier-inverter cubicleXM7 XR2 XR5 Air admission Mains 1, load Battery L1L2 L3 L1 L2 L3 Mains Battery LoadXR1 XR8 XM133 Q1on500/800kVA Static Switch Cubicle Front RearXR9 XR2 Q4S XR3 XR4 XR71200kVA Static Switch Cubicle Front viewXR7 XR4 UPS XR6 XR3 XR5 XR2 XR9 XR1 XR8Important note AuxiliaryTerminal Block XR11200kVA external maintenance bypass cubicle Key to figureConnection of auxiliary circuits on the remote relay board XR1 XR2 XR3 XR4Connection to battery circuit breaker QF1 Connections between cubiclesEmergency shutdown Connections between Apoz boardsConnections between Misi boards modular UPSs XM XM XM XM XM XM127 128 129 130 131 MisiMisi Acpz board of the Static Switch Cubicle XR8 XR9 XR5 XR6 XR7Connection of the battery Temperature Monitor optional ConnectionsTemperature Monitor installation in a APC by Schneider Electric battery cubicleTemperature Monitor installation in a battery room Installing the Temperature Monitor in a battery cubicleRauz 1 board XM098 XM097 XR11 XM096 XR10 Connector XR10 Connection of the LED remote indications unitLink to an IBM AS/400→ computer Consult manual 6739388XU for further informationFinal installation steps Configuration of the AS/400→Connection to the Media Contacts 9 relay board After making the connectionsMains 2 line protection Rated inverter output Maximum permissible current KVAUPS 250 to 450kVA UPS 500kVAInternal connections between cubicles Cubicle mounting and connection for 600kVA UPSsCubicle mounting Connection of power and auxiliary circuits Left cubicle of 600kVA single-unit or parallel UPS with SSCMains Load L1 L2 L3 Air Admission Right cubicle of a 600kVA single-unit UPSXR2 XR5 XR3 XR6 XR4 XR7 XR3 XR6 XR4 Right cubicle of a 600kVA parallel UPS with SSCAir admission Load Left cubicle Right cubicleQ3BP XF1-XF2 XM1-XM2 Card cageRight cubicle of a 2000kVA Static Switch Cross-section AA Front viewAir admission Air extraction Mains OffXR9 XR1 XR8 Left cubicle of a 2000kVA Static SwitchXR6 XR3 XR5 XR2 Details of earthing connections in the various cubicles 250 to 400kVA rectifier-inverter cubicle450 500kVA rectifier-inverter cubicle Inverter inputInverter Input 120 to 1200kVA Static Switch Cubicles600kVA rectifier-inverter cubicle 2000kVA Static Switch Cubicles Tele-Monitor unitConnection with Bolt, nut andmains 2 contact washer Tele Monitor unit6739381ENPage 46 --JD6739381EN/JD
Related manuals
Manual 38 pages 11.72 Kb