
Floor loads (figure 5)
◗the floor supports the weight of each cubicle via the four 60 mm diameter pads at the bottom of the feet screwed into the corners of the frame;
◗the exact locations of the footpads are indicated in the figure;
◗normally the cubicles do not have to be secured to the floor; the footpads nevertheless have holes with an average depth of 12 mm designed for the fitting of M16 anchor bolts;
◗to determine the stresses applied by the cubicle feet on the floor, divide the cubicle weight (see the first 3 tables of this manual) by the total area of the 4 footpads (110 cm2).
Installation (cont.)
Cubicle footpads | 
  | 
  | 
  | 
rear | 33  | cubicle width  | 33  | 
  | 
  | less 66 mm  | 
  | 
  | 33  | 
  | 33  | 
four 60 mm dia.  | 
  | 
  | 
  | 
footpads with  | 
  | 
  | 
  | 
12 mm average  | 
  | 
  | 
  | 
depth holes for  | 
  | 
  | 
  | 
M16 anchor bolts  | 
  | 
  | 
  | 
  | 736  | 
  | 
  | 
  | 33  | 
  | 33  | 
front
Fig. 5
Cubicle layout on false floor or normal floor (figures 6, 7, 8)
◗  | the cubicles can be installed directly  | 
up against the rear wall;  | |
◗  | an overall clearance of 400 mm must  | 
be left above the entire surface of the  | |
Layout for a single-unit  UPS with one battery cubicle
cubicles for ventilation;  | 
◗ a side clearance of 25 mm is  | 
provided by the vertical bars on the  | 
sides of the cubicles to allow door  | 
opening. For cubicles mounted side by  | 
side, the two adjacent bars ensure an  | 
◗ a minimum clearance of 1000 mm is  | 
required in front of the cubicles to allow  | 
complete opening of the doors and  | 
easy access for maintenance work  | 
(replacement of subassemblies);  | 
◗ for extended battery backup times or  | 
high output systems, the UPS may  | 
have several battery cubicles (see the  | 
table at the end of the previous  | 
chapter). If this is the case, install the  | 
battery cubicles on the left side of the  | 
rear
>25  | cubicle width W  | 50  | cubicle width W  | |
(see table)  | (see table)  | |||
  | 
  | |||
  | battery cubicle  | 
  | 
80
 spacing uprights
> 1000
front
cutouts necessary for
cable entry from underneath a false floor:
200 mm x (W – 160 mm)
can equal 0
800
 location of trench under cubicles (if applicable)
containing the battery circuit breaker  | 
QF1 closest to the   | 
cubicle (figure 7);  | 
◗ when an auxiliary cubicle is included  | 
in the UPS, it should be installed to the  | 
left of the battery cubicle(s);  | 
◗ connection via the bottom | 
The connection cables may be run in three ways:
◗in a cable trench running underneath the front of the cubicles (see trench dimensions and layout in figure 6),
◗under a false floor.
A cutout must in this case be made in the floor for cable entry (see figure 6 for dimensions),
Fig. 6
Layout for a 
rear
battery cubicle 1
battery cubicle 2 containing batteryrectifier-inverter cubicle circuit breaker QF1
front
Fig. 7
6739381EN/