APC 6000 Floor loads figure, Cubicle layout on false floor or normal floor figures 6, 7

Page 11

Floor loads (figure 5)

the floor supports the weight of each cubicle via the four 60 mm diameter pads at the bottom of the feet screwed into the corners of the frame;

the exact locations of the footpads are indicated in the figure;

normally the cubicles do not have to be secured to the floor; the footpads nevertheless have holes with an average depth of 12 mm designed for the fitting of M16 anchor bolts;

to determine the stresses applied by the cubicle feet on the floor, divide the cubicle weight (see the first 3 tables of this manual) by the total area of the 4 footpads (110 cm2).

Installation (cont.)

Cubicle footpads

 

 

 

rear

33

cubicle width

33

 

 

less 66 mm

 

 

33

 

33

four 60 mm dia.

 

 

 

footpads with

 

 

 

12 mm average

 

 

 

depth holes for

 

 

 

M16 anchor bolts

 

 

 

 

736

 

 

 

33

 

33

front

Fig. 5

Cubicle layout on false floor or normal floor (figures 6, 7, 8)

the cubicles can be installed directly

up against the rear wall;

an overall clearance of 400 mm must

be left above the entire surface of the

Layout for a single-unit UPS with one battery cubicle

cubicles for ventilation;

a side clearance of 25 mm is

provided by the vertical bars on the

sides of the cubicles to allow door

opening. For cubicles mounted side by

side, the two adjacent bars ensure an

inter-cubicle clearance of 50 mm;

a minimum clearance of 1000 mm is

required in front of the cubicles to allow

complete opening of the doors and

easy access for maintenance work

(replacement of subassemblies);

for extended battery backup times or

high output systems, the UPS may

have several battery cubicles (see the

table at the end of the previous

chapter). If this is the case, install the

battery cubicles on the left side of the

rear

>25

cubicle width W

50

cubicle width W

(see table)

(see table)

 

 

 

battery cubicle

 

rectifier-inverter cubicle

80

spacing uprights

> 1000

front

cutouts necessary for

cable entry from underneath a false floor:

200 mm x (W – 160 mm)

can equal 0

800

location of trench under cubicles (if applicable)

rectifier-inverter cubicle with the cubicle

containing the battery circuit breaker

QF1 closest to the rectifier-inverter

cubicle (figure 7);

when an auxiliary cubicle is included

in the UPS, it should be installed to the

left of the battery cubicle(s);

connection via the bottom

The connection cables may be run in three ways:

in a cable trench running underneath the front of the cubicles (see trench dimensions and layout in figure 6),

under a false floor.

A cutout must in this case be made in the floor for cable entry (see figure 6 for dimensions),

Fig. 6

Layout for a single-unit UPS with several battery cubicles

rear

battery cubicle 1

battery cubicle 2 containing batteryrectifier-inverter cubicle circuit breaker QF1

front

Fig. 7

6739381EN/

Image 11
Contents Mgetm GalaxyTM 2 6739381EN/JD Contents Characteristics common to all cubicles CharacteristicsPack Advance cubicles Static Switch cubiclesExternal maintenance bypass cubicles Rectifier-inverter cubiclesElectrical parameters for Mains 2 Electrical parameters for selecting protective devicesElectrical parameters for Mains RemarkHeat losses Electrical parameters for determining cable cross-sections Line current Mm2 KVA Inverters Amps Copper Aluminium Installation with parallel frequency converters Installation with parallel UPSs with a centralised SSC Number Total UPSKVA Inverters Amps Copper Number Total UPS Mains 2 or loadLine current Front HandlingPositioning the cubicles Side clearances provided by the spacing uprights RearCubicle footpads Rear Layout for a single-unit UPS with one battery cubicleFloor loads figure Cubicle layout on false floor or normal floor figures 6, 7Rectifier-inverter cubicle Power circuit wiring diagramsConnection via the top Special caseExample of a 2 parallel UPS rectifier-inverters with SSC Diagram for a frequency converter with batteriesDiagram for a frequency converter without batteries Static Switch CubicleModular UPS cubicle External maintenance bypass cubicle Cross-section AA Connection of power circuitsGeneral KVA single-unit UPS cubicles see the appendix 160kVA to 400kVA modular UPS rectifier-inverter cubicleApoz 600kVA parallel UPS cubicles see the appendixXR2 XR5 XR3 XR6 Acpz XR4 XR7 XR4 XR7 500kVA single-unit UPS rectifier-inverter cubicle600kVA single-unit UPS cubicles see the appendix OffXR4 XR7 XM5 500kVA modular UPS rectifier-inverter cubicleXM7 XR2 XR5 XM133 Q1on Air admission Mains 1, load BatteryL1L2 L3 L1 L2 L3 Mains Battery Load XR1 XR8XR3 XR4 XR7 500/800kVA Static Switch CubicleFront Rear XR9 XR2 Q4SXR3 XR5 XR2 XR9 XR1 XR8 1200kVA Static Switch CubicleFront view XR7 XR4 UPS XR6Block XR1 Important noteAuxiliary TerminalKey to figure 1200kVA external maintenance bypass cubicleXR1 XR2 XR3 XR4 Connection of auxiliary circuits on the remote relay boardConnections between Apoz boards Connection to battery circuit breaker QF1Connections between cubicles Emergency shutdownMisi Connections between Misi boards modular UPSsXM XM XM XM XM XM 127 128 129 130 131Misi XR8 XR9 XR5 XR6 XR7 Acpz board of the Static Switch CubicleConnections Connection of the battery Temperature Monitor optionalInstalling the Temperature Monitor in a battery cubicle Temperature Monitor installation in a APC bySchneider Electric battery cubicle Temperature Monitor installation in a battery roomConsult manual 6739388XU for further information Rauz 1 board XM098 XM097 XR11 XM096 XR10 Connector XR10Connection of the LED remote indications unit Link to an IBM AS/400→ computerAfter making the connections Final installation stepsConfiguration of the AS/400→ Connection to the Media Contacts 9 relay boardUPS 500kVA Mains 2 line protectionRated inverter output Maximum permissible current KVA UPS 250 to 450kVAInternal connections between cubicles Cubicle mounting and connection for 600kVA UPSsCubicle mounting Left cubicle of 600kVA single-unit or parallel UPS with SSC Connection of power and auxiliary circuitsMains Load L1 L2 L3 Air Admission Right cubicle of a 600kVA single-unit UPSXR2 XR5 XR3 XR6 XR4 XR7 XR3 XR6 XR4 Right cubicle of a 600kVA parallel UPS with SSCAir admission Load Card cage Left cubicleRight cubicle Q3BP XF1-XF2 XM1-XM2Mains Off Right cubicle of a 2000kVA Static SwitchCross-section AA Front view Air admission Air extractionXR9 XR1 XR8 Left cubicle of a 2000kVA Static SwitchXR6 XR3 XR5 XR2 Inverter input Details of earthing connections in the various cubicles250 to 400kVA rectifier-inverter cubicle 450 500kVA rectifier-inverter cubicleInverter Input 120 to 1200kVA Static Switch Cubicles600kVA rectifier-inverter cubicle Tele Monitor unit 2000kVA Static Switch CubiclesTele-Monitor unit Connection with Bolt, nut andmains 2 contact washer6739381ENPage 46 --JD6739381EN/JD
Related manuals
Manual 38 pages 11.72 Kb