APC 6000 installation manual Acpz board of the Static Switch Cubicle, XR8 XR9 XR5 XR6 XR7

Page 30

Installation (cont.)

Connection of "Media Contacts 15" additional auxiliary circuits (option) (figure 22)

The additional auxiliary circuits of the rectifier-inverter and Static Switch Cubicles are connected to additional remote relay board by means of the 4 connectors (see location of this board in the figures of the "connection of power circuits" section).

ACPZ board of the Static Switch Cubicle

recommended cable cross-section: 1 mm2;

the male connectors that fit the female connectors on the board (XR5 to XR9) are supplied;

the contacts are volt-free and are shown in the diagram under the following conditions: UPS on, contact at rest;

contact breaking capacity: 250V, 5A.

Note:

In a parallel-connected UPS installation the "load" and "mains 2" signals are provided by the Static Switch Cubicle.

additional remote relay board

connector XR5

(option)

connector XR6

(option)

connector XR7

(option)

connector XR8

(option)

connector XR9

(option)

1

 

10

1

10

1

12

1

12

1

12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

XR8

 

 

 

XR9

 

XR5

 

 

XR6

 

 

 

XR7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(1) for:

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

 

 

overload (2)

 

 

 

 

 

 

single-unit UPS cubicle,

 

 

 

3

 

 

 

 

 

 

 

 

 

 

 

modular UPS cubicle,

 

 

 

4

 

 

 

 

overload (2)

 

 

 

 

 

 

parallel UPS cubicle with SSC.

 

 

 

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

(2) for:

 

 

 

 

 

 

7

 

 

 

 

inverter function fault (1)

 

 

 

 

single-unit UPS cubicle,

 

 

 

8

 

 

 

 

 

 

 

 

modular UPS cubicle,

 

 

 

9

 

 

 

 

 

 

 

 

 

 

 

parallel UPS cubicle with SSC,

 

 

 

10

 

 

 

 

inverter function fault (1)

 

 

 

 

Static Switch cubicle.

 

 

 

11

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

 

 

 

 

 

 

 

 

 

 

 

(3) for:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

single-unit UPS cubicle,

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

modular UPS cubicle,

 

 

 

2

 

 

 

 

rectifier-charger operating (1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Static Switch cubicle.

 

 

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

 

(4) in modular UPSs, these functions are

 

 

 

5

 

 

 

 

rectifier-charger operating (1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

available via the "auxiliary information" contact

 

 

 

6

 

 

 

 

 

 

 

output signals:

 

 

 

 

 

 

 

 

 

 

 

 

(connector XR9, terminals 7-8).

 

 

 

7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

rectifier-charger function fault (1)

 

 

 

 

 

 

 

 

 

 

 

 

8

 

 

 

 

 

 

 

 

(5) for:

 

 

 

 

 

 

9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

single-unit UPS cubicle,

 

 

 

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Static Switch cubicle.

 

 

 

11

 

 

 

 

rectifier-charger function fault (1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

 

 

transfer to Mains 2 inhibited (3)

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

transfer to Mains 2 inhibited (3)

 

 

 

 

 

 

 

 

 

 

 

 

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

 

 

 

 

transfer function fault (2)

 

 

 

 

 

 

 

 

 

 

 

 

9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11

 

 

 

 

transfer function fault (2)

 

 

 

 

 

 

 

 

 

 

 

 

12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

transfer to Mains 2 inhibited (4) (5)

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

 

 

transfer to Mains 2 with interruption inhibited (4) (5)

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5desynchronization with Mains 2 (3)

6

7

battery charge current limiting (1)

 

8

 

 

 

9

gradual rectifier-charger shutdown (1)

input signals:

10

 

1

current limiting on generator power (1)

 

2

 

 

 

3

remote inverter on (1)

 

4

 

 

 

5

 

 

6remote inverter off (1)

7

auxiliary signal (2)

8

 

Fig. 22

Page 30 - 6739381EN/JD

Image 30
Contents Mgetm GalaxyTM 2 6739381EN/JD Contents Characteristics Characteristics common to all cubiclesRectifier-inverter cubicles Static Switch cubiclesExternal maintenance bypass cubicles Pack Advance cubiclesRemark Electrical parameters for selecting protective devicesElectrical parameters for Mains Electrical parameters for Mains 2Electrical parameters for determining cable cross-sections Heat lossesNumber Total UPS Installation with parallel frequency convertersInstallation with parallel UPSs with a centralised SSC Line current Mm2 KVA Inverters Amps Copper AluminiumNumber Total UPS Mains 2 or load Line currentKVA Inverters Amps Copper Side clearances provided by the spacing uprights Rear HandlingPositioning the cubicles FrontCubicle layout on false floor or normal floor figures 6, 7 Layout for a single-unit UPS with one battery cubicleFloor loads figure Cubicle footpads RearSpecial case Power circuit wiring diagramsConnection via the top Rectifier-inverter cubicleStatic Switch Cubicle Diagram for a frequency converter with batteriesDiagram for a frequency converter without batteries Example of a 2 parallel UPS rectifier-inverters with SSCModular UPS cubicle External maintenance bypass cubicle Connection of power circuits GeneralCross-section AA 160kVA to 400kVA modular UPS rectifier-inverter cubicle KVA single-unit UPS cubicles see the appendix600kVA parallel UPS cubicles see the appendix XR2 XR5 XR3 XR6 Acpz XR4 XR7Apoz Off 500kVA single-unit UPS rectifier-inverter cubicle600kVA single-unit UPS cubicles see the appendix XR4 XR7500kVA modular UPS rectifier-inverter cubicle XM7 XR2 XR5XR4 XR7 XM5 XR1 XR8 Air admission Mains 1, load BatteryL1L2 L3 L1 L2 L3 Mains Battery Load XM133 Q1onXR9 XR2 Q4S 500/800kVA Static Switch CubicleFront Rear XR3 XR4 XR7XR7 XR4 UPS XR6 1200kVA Static Switch CubicleFront view XR3 XR5 XR2 XR9 XR1 XR8Terminal Important noteAuxiliary Block XR11200kVA external maintenance bypass cubicle Key to figureConnection of auxiliary circuits on the remote relay board XR1 XR2 XR3 XR4Emergency shutdown Connection to battery circuit breaker QF1Connections between cubicles Connections between Apoz boards127 128 129 130 131 Connections between Misi boards modular UPSsXM XM XM XM XM XM MisiMisi Acpz board of the Static Switch Cubicle XR8 XR9 XR5 XR6 XR7Connection of the battery Temperature Monitor optional ConnectionsTemperature Monitor installation in a battery room Temperature Monitor installation in a APC bySchneider Electric battery cubicle Installing the Temperature Monitor in a battery cubicleLink to an IBM AS/400→ computer Rauz 1 board XM098 XM097 XR11 XM096 XR10 Connector XR10Connection of the LED remote indications unit Consult manual 6739388XU for further informationConnection to the Media Contacts 9 relay board Final installation stepsConfiguration of the AS/400→ After making the connectionsUPS 250 to 450kVA Mains 2 line protectionRated inverter output Maximum permissible current KVA UPS 500kVACubicle mounting and connection for 600kVA UPSs Cubicle mountingInternal connections between cubicles Connection of power and auxiliary circuits Left cubicle of 600kVA single-unit or parallel UPS with SSCRight cubicle of a 600kVA single-unit UPS XR2 XR5 XR3 XR6 XR4 XR7Mains Load L1 L2 L3 Air Admission Right cubicle of a 600kVA parallel UPS with SSC Air admission LoadXR3 XR6 XR4 Q3BP XF1-XF2 XM1-XM2 Left cubicleRight cubicle Card cageAir admission Air extraction Right cubicle of a 2000kVA Static SwitchCross-section AA Front view Mains OffLeft cubicle of a 2000kVA Static Switch XR6 XR3 XR5 XR2XR9 XR1 XR8 450 500kVA rectifier-inverter cubicle Details of earthing connections in the various cubicles250 to 400kVA rectifier-inverter cubicle Inverter input120 to 1200kVA Static Switch Cubicles 600kVA rectifier-inverter cubicleInverter Input Connection with Bolt, nut andmains 2 contact washer 2000kVA Static Switch CubiclesTele-Monitor unit Tele Monitor unit6739381ENPage 46 --JD6739381EN/JD
Related manuals
Manual 38 pages 11.72 Kb