APC 6000 Number Total UPS Mains 2 or load, Line current, KVA Inverters Amps Copper

Page 9

Characteristics (cont.)

The table opposite serves as an example for an installation with up to four modular UPSs with an external maintenance bypass.

for installations with redundant units, take into account only the units required to supply the load power (e.g. for an installation made up of 3 parallel-connected rectifier-inverter cubicles, one being redundant, only 2 units are used to determine the currents on the maintenance bypass line and the load, and the cross- sectional areas of cables);

this table has been drawn up for rated phase-to-phase Mains 2 and load voltages of 415V and full rated load with a power factor of 0.8. For voltages of 380 or 400V, multiply the indicated currents by 1.09 and 1.04 respectively, then modify the cable cross-sections accordingly if necessary.

The cable cross-sections in this table are for the parts illustrated in bold on the following block diagrams (installation example, figure 3);

important. In an installation with an external maintenance bypass, the power cables between each UPS and the upstream protection devices must be the same length. The same holds for the power cables between each UPS cubicle and the external maintenance bypass.

Parameters for connection of the external maintenance bypass circuit and the load in an installation comprising modular UPSs

rated inverter

number of

total UPS

Mains 2 or load

cable cross-section

output

parallel-connected

rated output

line current

(1) in mm2

 

in kVA

inverters

in kVA

in Amps

Copper

 

Aluminium

250

2

500

722

2 x 185

 

2 x 300

 

3

750

1082

3 x 300

 

4 x 240

 

4

1000

1444

4 x 240

 

4 x 400

300

2

600

866

2 x 240

 

4 x 185

 

3

900

1299

4 x 240

 

4 x 400

 

4

1200

1732

Please consult us*

400

2

800

1154

4 x 185

 

4 x 300

 

3

1200

1731

Please consult us*

 

4

1600

2308

Please consult us*

450

2

900

1299

4 X 240

 

4 x 400

 

3

1350

1948

Please consult us*

500

2

1000

1444

4 X 240

 

 

4 x 400

 

3

1500

2166

Please consult us*

(1) cable cross-sections are given for copper

NF C 15-100 authorizes a maximum of 4

conductors of the U1000 R02V type. They are

 

 

 

 

 

calculated according to permissible temperature

cables per phase.

 

rise and allow for line voltage drops over a

 

maximum length of 100 m. For greater lengths,

 

the cross-sections should be chosen to limit

 

voltage drops to 3%.

 

Installation comprising modular UPSs with an external maintenance bypass

maintenance Bypass cubicle

mains 1

inverter 1

 

 

 

mains 2

 

 

mains 1

inverter 2

load

 

mains 2

 

 

mains 1

inverter 3

 

 

 

mains 2

 

 

Fig. 3

6739381EN/

Image 9
Contents Mgetm GalaxyTM 2 6739381EN/JD Contents Characteristics common to all cubicles CharacteristicsExternal maintenance bypass cubicles Static Switch cubiclesRectifier-inverter cubicles Pack Advance cubicles Electrical parameters for Mains Electrical parameters for selecting protective devices Remark Electrical parameters for Mains 2Heat losses Electrical parameters for determining cable cross-sectionsInstallation with parallel UPSs with a centralised SSC Installation with parallel frequency convertersNumber Total UPS Line current Mm2 KVA Inverters Amps Copper AluminiumNumber Total UPS Mains 2 or load Line currentKVA Inverters Amps Copper Positioning the cubicles HandlingSide clearances provided by the spacing uprights Rear FrontFloor loads figure Layout for a single-unit UPS with one battery cubicleCubicle layout on false floor or normal floor figures 6, 7 Cubicle footpads RearConnection via the top Power circuit wiring diagramsSpecial case Rectifier-inverter cubicleDiagram for a frequency converter without batteries Diagram for a frequency converter with batteriesStatic Switch Cubicle Example of a 2 parallel UPS rectifier-inverters with SSCModular UPS cubicle External maintenance bypass cubicle Connection of power circuits GeneralCross-section AA KVA single-unit UPS cubicles see the appendix 160kVA to 400kVA modular UPS rectifier-inverter cubicle600kVA parallel UPS cubicles see the appendix XR2 XR5 XR3 XR6 Acpz XR4 XR7Apoz 600kVA single-unit UPS cubicles see the appendix 500kVA single-unit UPS rectifier-inverter cubicleOff XR4 XR7500kVA modular UPS rectifier-inverter cubicle XM7 XR2 XR5XR4 XR7 XM5 L1L2 L3 L1 L2 L3 Mains Battery Load Air admission Mains 1, load BatteryXR1 XR8 XM133 Q1onFront Rear 500/800kVA Static Switch CubicleXR9 XR2 Q4S XR3 XR4 XR7Front view 1200kVA Static Switch CubicleXR7 XR4 UPS XR6 XR3 XR5 XR2 XR9 XR1 XR8Auxiliary Important noteTerminal Block XR1Key to figure 1200kVA external maintenance bypass cubicleXR1 XR2 XR3 XR4 Connection of auxiliary circuits on the remote relay boardConnections between cubicles Connection to battery circuit breaker QF1Emergency shutdown Connections between Apoz boardsXM XM XM XM XM XM Connections between Misi boards modular UPSs127 128 129 130 131 MisiMisi XR8 XR9 XR5 XR6 XR7 Acpz board of the Static Switch CubicleConnections Connection of the battery Temperature Monitor optionalSchneider Electric battery cubicle Temperature Monitor installation in a APC byTemperature Monitor installation in a battery room Installing the Temperature Monitor in a battery cubicleConnection of the LED remote indications unit Rauz 1 board XM098 XM097 XR11 XM096 XR10 Connector XR10Link to an IBM AS/400→ computer Consult manual 6739388XU for further informationConfiguration of the AS/400→ Final installation stepsConnection to the Media Contacts 9 relay board After making the connectionsRated inverter output Maximum permissible current KVA Mains 2 line protectionUPS 250 to 450kVA UPS 500kVACubicle mounting and connection for 600kVA UPSs Cubicle mountingInternal connections between cubicles Left cubicle of 600kVA single-unit or parallel UPS with SSC Connection of power and auxiliary circuitsRight cubicle of a 600kVA single-unit UPS XR2 XR5 XR3 XR6 XR4 XR7Mains Load L1 L2 L3 Air Admission Right cubicle of a 600kVA parallel UPS with SSC Air admission LoadXR3 XR6 XR4 Right cubicle Left cubicleQ3BP XF1-XF2 XM1-XM2 Card cageCross-section AA Front view Right cubicle of a 2000kVA Static SwitchAir admission Air extraction Mains OffLeft cubicle of a 2000kVA Static Switch XR6 XR3 XR5 XR2XR9 XR1 XR8 250 to 400kVA rectifier-inverter cubicle Details of earthing connections in the various cubicles450 500kVA rectifier-inverter cubicle Inverter input120 to 1200kVA Static Switch Cubicles 600kVA rectifier-inverter cubicleInverter Input Tele-Monitor unit 2000kVA Static Switch CubiclesConnection with Bolt, nut andmains 2 contact washer Tele Monitor unit6739381ENPage 46 --JD6739381EN/JD