Installation (cont.)
1200kVA Static Switch Cubicle
cross-section AA
front |
| rear |
mains 2
load
UPS outputs
connection | earth bar | |
from below | ||
| ||
trough (if applicable) |
front view
spacing uprights |
|
|
| spacing uprights | |||
|
|
|
|
| A |
|
|
|
|
|
|
| on |
|
|
|
|
|
|
| Q4S |
|
|
|
| static switch |
|
| off |
|
|
|
| bypass switch K2S |
|
|
|
|
|
|
|
|
| N | L1 | L2 | L3 |
|
|
|
|
|
| mains 2 | |
|
|
|
|
| on |
|
|
|
| static |
|
| Q3BP |
|
|
|
|
|
| off |
|
| |
|
| switch |
|
|
|
| |
|
|
|
|
|
|
| |
|
|
| ACPZ |
|
|
|
|
|
|
| board |
|
|
|
|
|
|
|
| N | L1 | L2 | L3 |
|
|
| XM |
|
|
| load |
|
|
|
|
|
|
| |
|
|
| 127 |
| on |
|
|
|
|
| to |
|
|
| |
|
| card |
| Q5N |
|
| |
|
| cage | 132 |
|
|
| |
|
|
|
|
| off |
|
|
N | L1 | L2 L3 | XR7 | XR4 |
|
|
|
| UPS |
| XR6 |
|
|
| |
| outputs | XR3 |
|
|
| ||
| XR5 |
|
|
| |||
|
|
| XR2 |
|
|
| |
|
|
|
|
|
|
| |
|
|
| XR9 | XR1 |
|
|
|
|
|
| XR8 |
|
|
| |
|
|
|
|
|
|
| |
|
|
|
|
| A |
|
|
|
| additional relay |
| remote relay |
| earth bar | |
|
| board (optional) |
| board |
|
|
|
power cable routing via the top
power cable routing via the bottom
Cables connected by lugs to 80 x 8 mm copper terminals and 14 mm diameter holes.
Height of connections relative to floor:
◗mains 2: 1310 mm;
◗inverter outputs: 550 mm;
◗load: 850 mm;
◗remote relay board: 570 mm max.
6739381EN/