E6581741
Introduction
Thank you for purchasing the “EtherNet/IP™ - Modbus® TCP option (IPE002Z)” for TOSVERT
This option needs the option adaptor to connect
After reading this function manual, please keep it handy for future reference.
For details of its general handling, see an instruction manual attached with the option unit.
-TOSVERT
-TOSVERT
-TOSVERT
-TOSVERT
-TOSVERT
EtherNet/IP™ is a trademark of ControlNet International, Ltd.
Modbus® TCP is a registered trademark of AEG Schneider Automation International S.A.S.
Handling in general
|
|
| Warning |
|
|
| Do not connect or disconnect a network cable while the Inverter power is on. |
| Prohibited | It may lead to electric shocks or fire. | |
|
| ||
|
|
| See the instruction manual attached with the option unit for cautions the handling. |
| Mandatory | Otherwise, it may lead to electric shocks, fire, injuries or damage to product. | |
|
| ||
|
| Network control | |
|
| ||
|
| ||
|
|
| Warning |
|
|
| Do not send the value out of the valid range to objects and attributes. |
| Prohibited | Otherwise, the motor may suddenly start/stop and that may result in injuries. | |
|
| ||
|
|
| Use an additional safety device with your system to prevent a serious accident due to the |
| Mandatory | network malfunctions. Usage without an additional safety device may cause an accident. | |
|
|
Caution
Mandatory
Set up “Communication error trip function (see below)” to stop the Inverter when the option unit is deactivated by an unusual event such as tripping, an operating error, power outage, failure, etc.
-Network
(Refer to "3.2.3 Network error detection (c100 - c103, c523)" for details)
Deactivated the option module may cause an accident, if the “Communication error trip function” is not properly set up.
Make sure that the operation signals are STOP before resetting Inverter’s fault. The motor may suddenly start and that may result in injuries.
Notes on operation
Notes
When the control power is shut off by the instantaneous power failure, communication will be unavailable for a while.
The Life of EEPROM is approximately 100,000 times. Avoid writing a command more than 100,000 times to the same parameter of the Inverter and the option module.