3.2.4.7. fd01 (Inverter operating status 1)
bit | Function | 0 | 1 | Note | |
0 | Failure FL | No output | Under in | - | |
progress | |||||
|
|
| Trip status includes rtry and | ||
|
|
|
| ||
1 | Failure | Not tripped | Tripped | the trip retention status are also | |
|
|
|
| regarded as tripped statuses. | |
2 | Alarm | No alarm | Alarm issued | - | |
3 | Under voltage (moff) | Normal | Under voltage | - | |
|
|
|
| THR1: pt = setting value, vl, | |
4 | Motor selection (1 or 2) | Motor 1 (THR1) | Motor 2 (THR2) | vlv, vb, thr | |
(THR 2 selection) | THR2: pt = 0, f170, f171, | ||||
|
| PID control | PID control | f172, f173 | |
5 | PID control off | - | |||
permitted | prohibits | ||||
|
|
| |||
| Acceleration/deceleratio | Acceleration/dec | Acceleration/dec | AD1: acc, dec | |
6 | n pattern selection (1 or | eleration pattern | eleration pattern | AD2: f500, f501 | |
| 2) | 1 (AD1) | 2 (AD2) |
| |
7 | DC braking | OFF | Forced DC | - | |
braking | |||||
|
|
|
| ||
8 | Jog run | OFF | Jog run | - | |
9 | Forward / reverse run | Forward run | Reverse run | - | |
10 | Run/stop | Stop | Run | - | |
11 | Coast stop (ST = OFF) | ST=ON | ST=OFF | - | |
12 | Emergency stop | No emergency | Emergency | - | |
stop status | stop status | ||||
|
| Standby: Initialization | |||
|
|
|
| ||
|
|
|
| completed, not failure stop | |
13 | Standby ST=ON | Standby | status, not alarm stop status | ||
|
|
|
| (moff, ll forced stop), | |
|
|
|
| ST=ON, and RUN=ON | |
|
|
|
| Standby: Initialization completed, | |
14 | Standby | Standby | not failure stop status and not | ||
alarm stop status (moff, ll | |||||
|
|
|
| ||
|
|
|
| forced stop) | |
15 | (Reserved) | Undefined | - |
Note: Don’t use the reserved bit for the judgment.
3.2.4.8. fd00 (Output frequency)
The current output frequency is read into 0.01Hz of units and by the hexadecimal number. For example, when the output frequency is 80Hz, 0x1F40 (hexadecimal number) are read.
Since the minimum unit is 0.01%,
0x1F40 (Hex.) = 8000(Dec.) * 0.01 = 80 (Hz) |
|
Also about the following parameters, these are the same as this. |
|
- fd22 (Feedback value of PID) | Unit: 0.01Hz |
- fd16 (Estimated speed) | Unit: 0.01Hz |
- fd29 (Input power) | Unit: 0.01kW |
- fd30 (Output power) | Unit: 0.01kW |