E6581741
3.2.3.Network error detection (c100 - c103, c523)
▼Display of trip information
err8 (Optional unit fault 1: 1BH): Network error stop
▼Related parameter
Title | Function | Setting range |
Description
c100 | Communication error | ||
detection delay time | |||
|
|
c101 | Inverter operation at the | ||
communications loss action | |||
|
| ||
c102 | Preset speed operation | ||
selection | |||
|
| ||
|
|
| |
c103 | Communication | ||
condition selection | |||
|
| ||
c523 | Time out | 0.0: Disable | |
0.5 - 60 sec. | |||
|
|
The waiting time from when a network error occurs can be adjusted. If a network error continues past the time set in c100, it is recognized as a communication error and the operation of the inverter follows the setting of c101.
When normal communication returns during the setting time, a communication error is not displayed and operation is continued.
*The case of Modbus® TCP protocol
The
Disconnection detection time = c523 (Time out) +
c100 (Communication error detection delay time)
*The case of EtherNet/IPTM protocol
-At I/O scanning and connected communication Time-out time =
RPI 4 2Connection Timeout Multiplier [μs] + c100
(communication error detection delay time) [0.1s] RPI: Request Packet Interval
-At Unconnected communication Time-out is not operating.
The operation of the inverter when the communication fault occurs can be specified. The operation frequency of the inverter when the communication fault occurs can be specified. (Only when c101 is set to 5)
Select the communication
The waiting time from the occurrence of the network error to detection can be adjusted.
*When you are using unconnected communication of the EtherNet/IP protocol,