E6581741
3. Parameters
3.1. Communication parameters
Set up the inverter parameters as follows. It is necessary to reset the inverter to update the parameter. This option doesn't operate if these parameters are not correctly set.
Title | Communi | Function | Description | Factory | |
cation No. | setting | ||||
|
|
| |||
|
|
| 0: Terminal board |
| |
|
|
| 1: Panel keypad (including remote keypad) | 1 | |
cmod | 0003 | Command mode selection | 2: RS485 communication | ||
|
|
| 3: CANopen communication |
| |
|
|
| 4: Communcation option |
| |
|
|
| 0: Setting dial 1 (save even if power is off) |
| |
|
|
| 1: Terminal board VIA |
| |
|
|
| 2: Terminal board VIB |
| |
|
|
| 3: Setting dial 2 (press in center to save) |
| |
|
|
| 4: RS485 communication |
| |
|
| Frequency setting mode | 5: UP/DOWN from external logic input | 0 | |
fmod | 0004 | 6: CANopen communication | |||
selection 1 | |||||
|
| 7: Communication option |
| ||
|
|
|
| ||
|
|
| 8: Terminal board VIC |
| |
|
|
| 9, 10: - |
| |
|
|
| 11: Pulse train input |
| |
|
|
| 12, 13: - (*1) |
| |
|
|
| 14: sr0 (*1) |
| |
|
|
| 1: 2 poles |
| |
|
|
| 2: 4 poles |
| |
|
|
| 3: 6 poles |
| |
f856 | 0856 | Number of motor pole pair for | 4: 8 poles | 2 | |
communication | 5: 10 poles | ||||
|
|
| |||
|
|
| 6: 12 poles |
| |
|
|
| 7: 14 poles |
| |
|
|
| 8: 16 poles |
| |
f899 | 0899 | Communication function reset | 0: - | 0 | |
1: Reset (after execution: 0) | |||||
|
|
|
| ||
(*1): There selections are effective in only |
|
| |||
|
|
|
|
| |
Title | Communi | Function | Description | Factory | |
cation No. | setting | ||||
|
|
| |||
|
|
| 0: - | 1 | |
|
|
| 1: fa06 (Communication command 1) |
| |
|
|
| 2: fa23 (Communication command 2) |
| |
|
|
| 3: fa07 (Frequency command, 0.01Hz) |
| |
|
|
| 5: fa50 (Terminal output data) |
| |
c001 | C001 | Scanner input 1 address (*3) | 6: fa51 (FM analog output) |
| |
8: f601 (Stall prevention level, %) |
| ||||
|
|
|
| ||
|
|
| 13: acc (Acceleration time 1, 0.1s) (*2) |
| |
|
|
| 14: dec (Deceleration time 1, 0.1s) (*2) |
| |
|
|
| 15: ul (Upper limit, 0.01Hz) |
| |
|
|
| 16: vb (Torque boost value 1, 0.1%) |
| |
|
|
| 17: vlv (Base frequency voltage 1, 0.1V) |
| |
c002 | C002 | Scanner input 2 address (*3) | 3 | ||
c003 | C003 | Scanner input 3 address (*3) | 0 | ||
c004 | C004 | Scanner input 4 address (*3) | 0 | ||
c005 | C005 | Scanner input 5 address (*3) | 0 | ||
c006 | C006 | Scanner input 6 address (*3) | 0 |
(*2): The unit depends on the f519 setting.
(*3): This parameter is effective by reset. Please reset (power supply reset or f899=1) after changing a set point.
- 7 -