Toshiba IPE002Z instruction manual Wiring, EtherNet/IP-Modbus TCP

Page 79

E6581741

<Example of setting>

The example below shows how to configure the local/remote operation.

F terminal

Operating command

R terminal

EtherNet/IP-Modbus TCP local/remote

 

(Terminal in this example) switching

VIA terminal

Operation frequency command

<Wiring>

Variable resistor for adjustment 10k ohm

Operation command

EtherNet/IP-Modbus TCP

/local Switch

 

VF-MB1

PP

 

VIA

SW1*

 

CC

SOURCE

PLC

 

F

SINK

 

R

 

CC

 

<Parameter setting>

cmod(Command mode selection) = 0 (Terminal board) fmod(Frequency setting mode selection 1) = 1 (VIA)

f112(Input terminal selection 2 (R)) = 48 (Remote/Local control)

<Operation>

R-CC terminal open: VF-MB1 is controlled as a slave device of the EtherNet/IP™ - Modbus® TCP.

R-CC terminal closed:

F-CC terminal short to RUN F-CC terminal open to STOP

Output frequency is set up by the VIA signal input.

(Note)

When the local(HAND) / remote key (f750=2) is chosen as EASY key selection and the EASY key lamp of an inverter front panel is on, priority is most given to operation by a panel. (Refer to the inverter instruction manual for details).

- 78 -

Image 79
Contents Tosvert VF-MB1/S15 Handling in general IntroductionNetwork control Table of Contents 12.1 10.210.3 10.4Outline Connector to the inverter LED indicator SeeOverview Names and functionsDaisy chain topology Star topology RJ45 connector pin layoutEthernet switch Example of connection to an EtherNet/IP and Modbus TCPLED indicator Communication parameters Parameters0,0 Display only These fields are effective settings at c504 = 0.0Monitor of the EtherNet error No error/clear error C536 C084 ‘B’ 42H C085 ‘1’ 31H C086 ‘-‘ Details of the parameter setting Device name c081-c096Chars No Parameter Character Ex Ascii Ex C081 ‘V’ 56H C082 ‘F’ 46H C083 ‘M’Assigning IP addresses c504, c505-c516 C504 IP mode CommentsCase of EtherNet/IPTM protocol Network error detection c100 c103, c523Byte Value VF-MB1/S15Parameter Value EtherNet/IP MasterForced DC Braking Jog run Emergency stop Always enable, E trip Fault resetReset No data is returned from the drive Frequency priority Bit FunctionReserved Electric power quantity 4.3. fa23 Communication commandSpecified data output 4.4. fa07 frequency reference from internal optionStandby Initialization Emergency stop No emergency Stop statusCompleted, not failure stop 4.9. fd03 Output current FE06 Input terminal function selection 7 f117Output TB Function select F132 Bit TB Name Function ParameterOutput terminal function selection 1A f130 Output TB Function select 2A f131Class Code Object Class Hex Dec ObjectsSupported Objects Class Attributes Class ServiceInstance Services Identity ObjectUnsupporteed Attribute 5 State DescriptionsAdapted from document CIP the CIP Networks Library Bit Called Definition0x0E GetAttributeSingle Read one attribute Message Router ObjectInstance Attribute See below Assembly ObjectOutput Assembly Instance Type Size Input Assembly Instance Type SizeConnection Manager Object Class ServicesInstance 1 Attribute Motor Data Object Refer to 4.6.1 Run/Stop Event Matrix Control Supervisor ObjectE6581741 Run/Stop Event Matrix Control Supervisor State Transition DiagramState of the drive 0x0E GetAttributeSingle AC/DC Drive Object 0x2A32767 Range Address accessedParameter Objects 0x4000-0x4FFF 0x0000-0x0FFF 0x7000-0x7FFF 0xF000-0xFFFFCommunication No 0003 Instance ID 65535 0x0001-0xFFFF0x0E GetAttributeSingle 0x10 SetAttributeSingle 0x01 GetAttributeAll 0x0E GetAttributeSingle Port Object 0xF4Read all attributes Read one attribute List of optional service codes Number of services Optional service listTCP/IP interface Object 0xF5 Bit 5-31 System reserved Only 16 characters in 64 characters can be set in the drive Ethernet link object 0xF6 Bit 7-31 System reserved Shorts Bit 7-31System reserved Instance 2 AttributeInstance name Number Hex Size Configuration of the assembliesOutput Instance Input InstanceInstance 70 CIP basic speed control input Instance 20 CIP basic speed control outputInstance 71 CIP extended speed control input Instance 21 CIP extended speed control outputInstance 150 mapping Byte Bit Instance 100 Native drive outputInstance 150 Native drive input Instance 100 mapping Byte Bit② Forward running 60Hz Instance Byte 15 14 13 12 Hex ④ Preset speed 1 with forward running sr1 Instance Byte Hex⑤ Fault reset Instance Byte Hex Examples of Instance 100/150 ① Stop Byte HexInstance 151 mapping Byte Bit Instance 101 Native drive outputInstance 151 Native drive input Instance 101 mapping Byte BitOutput Instance 0x0003 Input Instance Cmod is 0x0000 Examples of Instance 101/151Output Instance 0x0268 Input Instance F268 is 60.0Hz 0x1770 Instance 152 mapping Bit Byte Instance 102 Native drive outputInstance 152 Native drive input Instance 102 mapping Bit ByteInstance 155 Toshiba specific input Instance 105 Toshiba specific outputInstance 105 mapping Bit Byte Output Instance 0x0000 0x0003 Input Instance Cmod is Examples of Instance 105/155Integration in RSLogix About EDS fileCreate a new project Add a EtherNet/IP scanner to the I/O configuration E6581741 Configure the VF-MB1/S15 EtherNet/IP module E6581741 Download the program to the PLC Select the Download Once again, select the Download Edit the I/O scan data E6581741 E6581741 List of Modbus functions supported Modbus TCP serverModbus TCP frames Drive Modbus serversFunction Code = 83h Exception Code = 0x03 Read Holding Registers functionIllegal Function Illegal Data Address Illegal Data Value Byte Meaning 0x06 Write Single Register functionFunction Code = 86h Exception Code = 0x10 Write Multiple Registers function Function Code = 17h 0x17 Read/Write Multiple Registers functionFunction Code = 97h Exception Code = 0x2B Read Device identification function Obj Length 27-30 Value 0106 Exception response format Obj Length 18-24 Value IPE002ZFunction Code = ABh Exception Code = Parameter data Presentation IO Scanning servicePeriodic variables Defining the hardware configuration Example of the setup with PL7Bootp configuration Mode Configuring Modbus messagingPLC Configuring periodic variablesOperation panel Fmod Command & Setpoint selection Local/RemoteEtherNet/IP-Modbus TCP WiringDisconnection error of network cable Option errorUnusual diagnosis WebServer Access to the webserverWeb pages structure State of the drive can be confirmed on this Drive monitor Main menu MonitoringDrive parameters Main menu Monitoring Input the write value to popup window Modbus scanner Main menu Network Setup Network parameters Main menu Network SetupEthIP scanner Main menu Network Setup Administration Main menu Network Setup You can check TCP/IP status on this 88E TCP/IP statistics Main menu Diagnostics