E6581741
<Example of setting>
The example below shows how to configure the local/remote operation.
F terminal | Operating command |
R terminal | |
| (Terminal in this example) switching |
VIA terminal | Operation frequency command |
<Wiring>
Variable resistor for adjustment 10k ohm
Operation command
EtherNet/IP-Modbus TCP
/local Switch
| ||
PP |
| |
VIA | SW1* | |
| ||
CC | SOURCE | |
PLC | ||
| ||
F | SINK | |
| ||
R |
| |
CC |
|
<Parameter setting>
cmod(Command mode selection) = 0 (Terminal board) fmod(Frequency setting mode selection 1) = 1 (VIA)
f112(Input terminal selection 2 (R)) = 48 (Remote/Local control)
<Operation>
Output frequency is set up by the VIA signal input.
(Note)
When the local(HAND) / remote key (f750=2) is chosen as EASY key selection and the EASY key lamp of an inverter front panel is on, priority is most given to operation by a panel. (Refer to the inverter instruction manual for details).
- 78 -