Toshiba IPE002Z instruction manual Parameter data

Page 72

E6581741

8.9. Parameter data

It is explanation by the reference method of the list of parameters of the VF-MB1 or VF-S15 series as follows. For communication purpose, see the parameter list on inverter's instruction manual regarding the communication number, adjustment range and so forth.

<Example of excerpts from the inverter’s instruction manual>

 

 

 

 

Minimum

 

 

 

 

Communi-

 

 

setting unit

Default

Write during

 

Title

Function

Adjustment range

(Panel/Communi

 

cation No.

-

setting

running

 

 

 

 

 

 

 

 

 

cation)

 

 

 

Refer

ence

au

-

History function

Displays parameters in groups of

1/1

-

-

 

five in the reverse order to that in

 

h

 

 

 

 

 

 

 

 

which their settings were changed.

 

 

 

 

au

0093

Guidance function

0

: -

1/1

0

Disabled

 

1

: -

 

f

 

 

 

 

 

 

 

 

2 : Preset speed guidance

 

 

 

 

 

 

 

3

: Analog signal operation guidance

 

 

 

 

 

 

 

 

 

 

 

au

0094

Overload

0

: -

1/1

-

Disabled

 

1

: Constant torque characteristic

 

l

 

characteristic

 

 

 

 

 

 

(150%-60s)

 

 

 

 

 

 

selection

2

: Variable torque characteristic

 

 

 

 

 

 

 

(120%-60s)

 

 

 

 

 

 

 

 

 

 

 

 

4.3

5.1

4.3

5.2

3.5

5.3

6.14

 

 

de

0010

Deceleration time 1

0.1 to 6000 sec.

0.1/0.1 *2

*1

Enabled

5.2

c

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

: -

 

 

 

 

 

ty

0007

Factory default setting

1

: 50 Hz default setting

1/1

-

Disabled

5.20

p

2

: 60 Hz default setting

 

 

 

3

: Default setting 1 (Initialization)

 

 

 

 

 

 

 

 

 

 

 

 

 

*1: Default values vary depending on the capacity.

*2: Changing the parameter VR enables to set to 0.01 sec. (adjustment range: 0.01 - 600.0 sec.).

(1)“Title” means the display on the inverter panel.

(2)“Communication number” is affixed to each parameter that is necessary for designating the parameter for communication.

(3)"Adjustment range" means a data range adjustable for a parameter, and the data cannot be written outside the range. The data have been expressed in the decimal notation. For writing the data through the communication function, take the minimum setting unit into consideration, and use hexadecimal system.

(4)"Minimum setup unit" is the unit of a single data (when the minimum unit is "-", 1 is equal to 1).

For example, the "minimum setup unit" of acceleration time (CEE) is 0.01, and 1 is equal to 0.01s. For setting a data to 10 seconds, transmit 0x03E8 [10÷0.01=1000d=0x03E8] by communication.

(5)Communication numbers "0xxxxA" to "0xxxxF" don't exist in VF-MB1 or VF-S15. Therefore, these communication numbers are skipped when read or write.

For example:

When the data of two words is read from acc(0009h), 0x000A doesn't exist because of this specification.

Consequently, in this case ACC(0009h) and DEC(0010h) are read.

- 71 -

Image 72
Contents Tosvert VF-MB1/S15 Introduction Handling in generalNetwork control Table of Contents 10.2 10.310.4 12.1Connector to the inverter LED indicator See OverviewNames and functions OutlineRJ45 connector pin layout Ethernet switchExample of connection to an EtherNet/IP and Modbus TCP Daisy chain topology Star topologyLED indicator Parameters Communication parameters0,0 These fields are effective settings at c504 = 0.0 Display onlyMonitor of the EtherNet error No error/clear error C536 Details of the parameter setting Device name c081-c096 Chars No Parameter Character Ex Ascii ExC081 ‘V’ 56H C082 ‘F’ 46H C083 ‘M’ C084 ‘B’ 42H C085 ‘1’ 31H C086 ‘-‘C504 IP mode Comments Assigning IP addresses c504, c505-c516Network error detection c100 c103, c523 Case of EtherNet/IPTM protocolVF-MB1/S15 Parameter ValueEtherNet/IP Master Byte ValueEmergency stop Always enable, E trip Fault reset Reset No data is returned from the drive Frequency priorityBit Function Forced DC Braking Jog run4.3. fa23 Communication command Reserved Electric power quantity4.4. fa07 frequency reference from internal option Specified data outputEmergency stop No emergency Stop status Standby InitializationCompleted, not failure stop 4.9. fd03 Output current Input terminal function selection 7 f117 FE06Bit TB Name Function Parameter Output terminal function selection 1A f130Output TB Function select 2A f131 Output TB Function select F132Objects Class Code Object Class Hex DecSupported Objects Class Service Instance ServicesIdentity Object Class AttributesAttribute 5 State Descriptions Adapted from document CIP the CIP Networks LibraryBit Called Definition UnsupporteedMessage Router Object 0x0E GetAttributeSingle Read one attributeInstance Attribute Assembly Object Output Assembly Instance Type SizeInput Assembly Instance Type Size See belowClass Services Connection Manager ObjectInstance 1 Attribute Motor Data Object Control Supervisor Object Refer to 4.6.1 Run/Stop Event MatrixE6581741 Control Supervisor State Transition Diagram Run/Stop Event MatrixState of the drive AC/DC Drive Object 0x2A 0x0E GetAttributeSingleRange Address accessed Parameter Objects0x4000-0x4FFF 0x0000-0x0FFF 0x7000-0x7FFF 0xF000-0xFFFF 32767Communication No 0003 Instance ID 0x0001-0xFFFF 655350x0E GetAttributeSingle 0x10 SetAttributeSingle Port Object 0xF4 0x01 GetAttributeAll 0x0E GetAttributeSingleRead all attributes Read one attribute Number of services Optional service list List of optional service codesTCP/IP interface Object 0xF5 Bit 5-31 System reserved Only 16 characters in 64 characters can be set in the drive Ethernet link object 0xF6 Bit 7-31 System reserved Shorts Instance 2 Attribute Bit 7-31System reservedConfiguration of the assemblies Output InstanceInput Instance Instance name Number Hex SizeInstance 20 CIP basic speed control output Instance 70 CIP basic speed control inputInstance 21 CIP extended speed control output Instance 71 CIP extended speed control inputInstance 100 Native drive output Instance 150 Native drive inputInstance 100 mapping Byte Bit Instance 150 mapping Byte Bit④ Preset speed 1 with forward running sr1 Instance Byte Hex ⑤ Fault reset Instance Byte HexExamples of Instance 100/150 ① Stop Byte Hex ② Forward running 60Hz Instance Byte 15 14 13 12 HexInstance 101 Native drive output Instance 151 Native drive inputInstance 101 mapping Byte Bit Instance 151 mapping Byte BitExamples of Instance 101/151 Output Instance 0x0003 Input Instance Cmod is 0x0000Output Instance 0x0268 Input Instance F268 is 60.0Hz 0x1770 Instance 102 Native drive output Instance 152 Native drive inputInstance 102 mapping Bit Byte Instance 152 mapping Bit ByteInstance 105 Toshiba specific output Instance 155 Toshiba specific inputInstance 105 mapping Bit Byte Examples of Instance 105/155 Output Instance 0x0000 0x0003 Input Instance Cmod isAbout EDS file Integration in RSLogixCreate a new project Add a EtherNet/IP scanner to the I/O configuration E6581741 Configure the VF-MB1/S15 EtherNet/IP module E6581741 Download the program to the PLC Select the Download Once again, select the Download Edit the I/O scan data E6581741 E6581741 Modbus TCP server Modbus TCP framesDrive Modbus servers List of Modbus functions supported0x03 Read Holding Registers function Function Code = 83h Exception Code =Illegal Function Illegal Data Address Illegal Data Value 0x06 Write Single Register function Byte MeaningFunction Code = 86h Exception Code = 0x10 Write Multiple Registers function 0x17 Read/Write Multiple Registers function Function Code = 17hFunction Code = 97h Exception Code = 0x2B Read Device identification function Obj Length 18-24 Value IPE002Z Obj Length 27-30 Value 0106 Exception response formatFunction Code = ABh Exception Code = Parameter data IO Scanning service PresentationPeriodic variables Example of the setup with PL7 Defining the hardware configurationBootp configuration Configuring Modbus messaging ModeConfiguring periodic variables PLCCommand & Setpoint selection Local/Remote Operation panel FmodWiring EtherNet/IP-Modbus TCPOption error Disconnection error of network cableUnusual diagnosis Access to the webserver WebServerWeb pages structure Drive monitor Main menu Monitoring State of the drive can be confirmed on thisDrive parameters Main menu Monitoring Input the write value to popup window Network parameters Main menu Network Setup Modbus scanner Main menu Network SetupEthIP scanner Main menu Network Setup Administration Main menu Network Setup TCP/IP statistics Main menu Diagnostics You can check TCP/IP status on this 88E