Toshiba IPE002Z instruction manual These fields are effective settings at c504 = 0.0, Display only

Page 10

 

 

 

 

E6581741

 

 

 

 

 

 

Title

Communi

Function

 

Description

Factory

cation No.

 

setting

 

 

 

 

 

 

 

This parameter is used to set the protocol of the option

 

c500

C500

Protocol (*3)

card.

0

0: Modbus TCP (default)

 

 

 

 

 

 

 

1: EtherNet/IP

 

 

 

 

This field is used to set the transmission speed and the

 

 

 

 

transmission mode of the card.

 

 

 

Rate Setting (*3)

0: Autodetect(default)

0

c501

C501

1: 10Mbps Full

 

 

 

2: 10Mbps Half

 

 

 

 

3: 100Mbps Full

 

 

 

 

4: 100Mbps Half

 

 

 

 

This field displays the baud rate and the transmission

 

c502

C502

Actual Rate (L port)

mode currently used by the communication card.

 

(Display only)

 

 

 

 

 

 

 

 

0: unconnected

-

 

 

 

1: 10Mbps Full

 

 

 

 

c503

C503

Actual Rate (R port)

2: 10Mbps Half

 

3: 100Mbps Full

 

 

 

 

 

 

 

 

4: 100Mbps Half

 

 

 

 

 

 

 

 

 

Use this parameter to select the IP address assignment

 

 

 

 

method.

 

c504

C504

IP mode (*3)

0: Manual

0

1: BOOTP

 

 

 

 

 

 

 

2: DHCP

 

 

 

 

Refer to "3.2.2 Assigning IP addresses" for the details.

 

c505-

C505-

 

The IP address of the option module.

 

IP address (*3)

These fields are effective settings at c504 = 0.

0.0.0.0

c508

C508

 

Refer to "3.2.2 Assigning IP addresses" for the details.

 

 

 

 

 

c509-

C509-

 

The subnet mask of the option module.

 

Subnet Mask (*3)

These fields are effective settings at c504 = 0.

0.0.0.0

c512

C512

 

Refer to "3.2.2 Assigning IP addresses" for the details.

 

 

 

 

 

c513-

C513-

 

The gateway IP address of the option module.

 

IP Gate (*3)

These fields are effective settings at c504 = 0.

0.0.0.0

c516

C516

 

Refer to "3.2.2 Assigning IP addresses" for the details.

 

 

 

 

 

c517-

C517-

MAC address (*5)

The MAC address of the option module.

----

c522

C522

[C517 - C518 - C519 - C520 - C521 - C522]

 

 

 

 

 

The waiting time from the occurrence of the

2

 

 

 

network error to detection can be adjusted.

 

 

 

 

* When you are using unconnected

 

c523

C523

Time out

communication of the EtherNet/IP protocol, time

 

 

 

 

out is not detected.

 

 

 

 

0.0: Disable

 

 

 

 

0.5 - 60 sec.

 

c524-

C524-

IP address actual

The current IP address of the option module.

-

c527

C527

Refer to "3.2.2 Assigning IP addresses" for the details.

 

 

c528-

C528-

IP Mask actual

The subnet mask actual of the option module.

-

c531

C531

Refer to "3.2.2 Assigning IP addresses" for the details.

 

 

 

 

 

 

 

c532-

C532-

IP Gate actual

The gateway IP address actual of the option module.

-

c535

C535

Refer to "3.2.2 Assigning IP addresses" for the details.

 

 

(*3): This parameter is effective by reset. Please reset (power supply reset or f899=1) after changing a set point.

(*5): .These values are displayed by decimal number format on panel of VFMB1/S15.

- 9 -

Image 10
Contents Tosvert VF-MB1/S15 Handling in general IntroductionNetwork control Table of Contents 10.4 10.210.3 12.1Names and functions Connector to the inverter LED indicator SeeOverview OutlineExample of connection to an EtherNet/IP and Modbus TCP RJ45 connector pin layoutEthernet switch Daisy chain topology Star topologyLED indicator Parameters Communication parameters0,0 These fields are effective settings at c504 = 0.0 Display onlyMonitor of the EtherNet error No error/clear error C536 C081 ‘V’ 56H C082 ‘F’ 46H C083 ‘M’ Details of the parameter setting Device name c081-c096Chars No Parameter Character Ex Ascii Ex C084 ‘B’ 42H C085 ‘1’ 31H C086 ‘-‘C504 IP mode Comments Assigning IP addresses c504, c505-c516Network error detection c100 c103, c523 Case of EtherNet/IPTM protocolEtherNet/IP Master VF-MB1/S15Parameter Value Byte ValueBit Function Emergency stop Always enable, E trip Fault resetReset No data is returned from the drive Frequency priority Forced DC Braking Jog run4.3. fa23 Communication command Reserved Electric power quantity4.4. fa07 frequency reference from internal option Specified data outputStandby Initialization Emergency stop No emergency Stop statusCompleted, not failure stop 4.9. fd03 Output current Input terminal function selection 7 f117 FE06Output TB Function select 2A f131 Bit TB Name Function ParameterOutput terminal function selection 1A f130 Output TB Function select F132Class Code Object Class Hex Dec ObjectsSupported Objects Identity Object Class ServiceInstance Services Class AttributesBit Called Definition Attribute 5 State DescriptionsAdapted from document CIP the CIP Networks Library Unsupporteed0x0E GetAttributeSingle Read one attribute Message Router ObjectInstance Attribute Input Assembly Instance Type Size Assembly ObjectOutput Assembly Instance Type Size See belowConnection Manager Object Class ServicesInstance 1 Attribute Motor Data Object Control Supervisor Object Refer to 4.6.1 Run/Stop Event MatrixE6581741 Run/Stop Event Matrix Control Supervisor State Transition DiagramState of the drive AC/DC Drive Object 0x2A 0x0E GetAttributeSingle0x4000-0x4FFF 0x0000-0x0FFF 0x7000-0x7FFF 0xF000-0xFFFF Range Address accessedParameter Objects 32767Communication No 0003 Instance ID 65535 0x0001-0xFFFF0x0E GetAttributeSingle 0x10 SetAttributeSingle 0x01 GetAttributeAll 0x0E GetAttributeSingle Port Object 0xF4Read all attributes Read one attribute List of optional service codes Number of services Optional service listTCP/IP interface Object 0xF5 Bit 5-31 System reserved Only 16 characters in 64 characters can be set in the drive Ethernet link object 0xF6 Bit 7-31 System reserved Shorts Instance 2 Attribute Bit 7-31System reservedInput Instance Configuration of the assembliesOutput Instance Instance name Number Hex SizeInstance 20 CIP basic speed control output Instance 70 CIP basic speed control inputInstance 21 CIP extended speed control output Instance 71 CIP extended speed control inputInstance 100 mapping Byte Bit Instance 100 Native drive outputInstance 150 Native drive input Instance 150 mapping Byte BitExamples of Instance 100/150 ① Stop Byte Hex ④ Preset speed 1 with forward running sr1 Instance Byte Hex⑤ Fault reset Instance Byte Hex ② Forward running 60Hz Instance Byte 15 14 13 12 HexInstance 101 mapping Byte Bit Instance 101 Native drive outputInstance 151 Native drive input Instance 151 mapping Byte BitOutput Instance 0x0003 Input Instance Cmod is 0x0000 Examples of Instance 101/151Output Instance 0x0268 Input Instance F268 is 60.0Hz 0x1770 Instance 102 mapping Bit Byte Instance 102 Native drive outputInstance 152 Native drive input Instance 152 mapping Bit ByteInstance 155 Toshiba specific input Instance 105 Toshiba specific outputInstance 105 mapping Bit Byte Examples of Instance 105/155 Output Instance 0x0000 0x0003 Input Instance Cmod isIntegration in RSLogix About EDS fileCreate a new project Add a EtherNet/IP scanner to the I/O configuration E6581741 Configure the VF-MB1/S15 EtherNet/IP module E6581741 Download the program to the PLC Select the Download Once again, select the Download Edit the I/O scan data E6581741 E6581741 Drive Modbus servers Modbus TCP serverModbus TCP frames List of Modbus functions supportedFunction Code = 83h Exception Code = 0x03 Read Holding Registers functionIllegal Function Illegal Data Address Illegal Data Value Byte Meaning 0x06 Write Single Register functionFunction Code = 86h Exception Code = 0x10 Write Multiple Registers function Function Code = 17h 0x17 Read/Write Multiple Registers functionFunction Code = 97h Exception Code = 0x2B Read Device identification function Obj Length 27-30 Value 0106 Exception response format Obj Length 18-24 Value IPE002ZFunction Code = ABh Exception Code = Parameter data Presentation IO Scanning servicePeriodic variables Example of the setup with PL7 Defining the hardware configurationBootp configuration Configuring Modbus messaging ModeConfiguring periodic variables PLCCommand & Setpoint selection Local/Remote Operation panel FmodWiring EtherNet/IP-Modbus TCPDisconnection error of network cable Option errorUnusual diagnosis Access to the webserver WebServerWeb pages structure Drive monitor Main menu Monitoring State of the drive can be confirmed on thisDrive parameters Main menu Monitoring Input the write value to popup window Network parameters Main menu Network Setup Modbus scanner Main menu Network SetupEthIP scanner Main menu Network Setup Administration Main menu Network Setup TCP/IP statistics Main menu Diagnostics You can check TCP/IP status on this 88E