Siemens RDG400 manual Button lock, Locked or unlocked by pressing the right button for 3 sec

Page 16

Button lock

If the button lock function is enabled by parameter P14, then the buttons will be

 

locked or unlocked by pressing the right button for 3 sec.

 

If “Auto lock” is configured, then the thermostat will automatically lock the buttons

 

10 sec after the last adjustment.

Operating mode switchover contact (Window contact)

Extended Comfort mode (operating mode switchover contact closed)

Temporary timer for extension of presence / absence

The thermostat can be forced into Energy Saving mode, e.g. when a window is opened. The window contact can be connected to digital input D1 (or multifunctional input X1, X2). Set parameter P42 (P38, P40) to 3.

The left button switches the operating mode from Energy Saving to Comfort for the period preset in P68, if the following conditions are fulfilled:

The operating mode switchover contact is closed (connected to input X1, X2, D1, parameter P38, P40, P42 set to 3)

Parameter P68 (extend Comfort period) is greater than 0

During the temporary Comfort mode extension, timer symbol appears.

If parameter P68 (extend Comfort period) = 0, extended Comfort cannot be activated; pressing the left button will show “OFF” (blinking 3 times)

The current operating mode can be forced temporarily into Comfort or Energy Saving / Protection mode. The time period is adjusted via the rotary knob:

Extend presence: Set the device to Comfort mode for the selected time period

Extend absence: Set the device to Energy Saving / Protection mode for the selected time period

To activate the function, keep the left button pressed and, within 3 seconds, turn the rotary knob

clockwise for extended presence

counterclockwise for extended absence The rotary knob adjusts the time period:

Extend presence: 0.00…+9:30 in steps of 30 minutes; symbol appears

Extend absence: 0.00…–9:30 in steps of 30 minutes; symbol or appears

During the extended presence / absence period, timer symbol appears.

Function

User operating mode

Operating

Function

Operating mode

Operating mode at

selection

mode when

 

during function

the end of function

 

activating

 

 

 

 

function

 

 

 

Comf

Extension

Comf

Prot

Comf

Absence

Prot

Comf

Prot

Not available

-

-

Comf

Extension

Comf

Eco

Comf

Absence

Eco

Comf

 

Eco

Extension

Comf

Eco

 

Eco

Absence

Eco

Comf

 

Prot

Not available

-

-

16 / 42

Siemens

RDG100…/RDG110…/RDG140.../RDG160… Basic Documentation

CE1P3182en

Building Technologies

Functions

28 May 2009

Image 16
Contents Building Technologies Edition CE1P3182en 28 MayTable of contents About this document Revision historyReference documents Before you startDocument use / request to the reader Types and features FeaturesSummary Brief descriptionEquipment combinations Accessories UseOrdering SSA81 SSP81… SSB81 SSD81 SQS85…Temperature control FunctionsGeneral note Described in sectionComfort mode Energy Saving Protection mode Operating modesSetpoints Comfort mode Energy Saving Protection mode Application Setpoints and sequenceSingle duct With min/max Limitation Single duct With Electrical HeaterComfort mode Energy Saving mode Application Heating mode Cooling mode Single ductProtection mode Heating mode Cooling mode With heating Cooling coilApplications overview Additional features Temperature sensor External / return airFloor heating Limitation functionSec after the last adjustment Button lockLocked or unlocked by pressing the right button for 3 sec Comf Extension Prot Absence Not available EcoSequences overview setting via parameter P01 Parameter P01 = Sequence ModeControl sequences Applications and sequencesFunction of the control outputs is set via DIP switches 4 Single-duct heating / cooling coilDIP Y10 = … 10 10 … 0 V inverted PositionSetting the sequence and the control outputs Single ductHeating or cooling Modulating control 3-position, PWM or DC 0 … 10Sequences Single duct with electrical heaterModulating electrical heater Single duct with radiator or floor heating Modulating radiator / floor heatingControl sequence Single duct with heating / cooling coilModulating heating / cooling coil Control output for air flow Control outputsSynchronization ON/OFF control signal Signal Position controlPosition actuator Parameter P44 Y1 and Y2Multifunctional input, Digital input AI/DIHandling of faults DIP switchesTemperature out RangeControl parameters Parameter settingChange the parameters as follows Parameters Service level Service levelParameters Expert level, diagnostics & test Expert levelDiagnostics & test Mounting and installation WiringHandling MountingOperation LayoutButton operation User actionDisposal LCD displayEngineering Connection terminalsConnection diagrams Mechanical design DimensionsGeneral Technical data Power supply Outputs Inputs Operational dataPage Index Automatic heating/cooling changeover