5 Handling

5.1Mounting and installation

Do not mount on a wall in niches or bookshelves, behind curtains, above or near heat sources, or exposed to direct solar radiation. Mount about 1.5 m above the floor.

Mounting

The room thermostat must be mounted in a clean, dry indoor place and must not be

 

exposed to drip or splash water

Wiring

See Mounting Instructions (M3182) enclosed with the thermostat.

 

Comply with local regulations to wire, fuse and earth the thermostat

 

The power supply line must have an external fuse or circuit breaker with a

 

rated current of no more than 10 A

 

Inputs X1-M, X2-M or D1-GND of different units (e.g. summer / winter

 

 

switch) may be connected in parallel with an external switch. Consider

 

 

overall maximum contact sensing current for switch rating

 

Disconnect power supply before removing the thermostat from the mounting

 

 

plate!

Commissioning

Select the application and type of control output via the DIP switches before fitting

 

the thermostat to the mounting plate.

 

After power is applied, the thermostat carries out a reset during which all LCD

 

segments flash, indicating that the reset was correct. After the reset, which takes

 

about 3 seconds, the thermostat is ready for commissioning by qualified HVAC

 

staff. The control parameters of the thermostat can be set to ensure optimum

 

performance of the entire system (see Basic Documentation P3182).

Control sequence

The control sequence may need to be set via parameter P01 depending on the

 

application. The factory setting for the single-duct application is “Cooling only”

Calibrate sensor

Recalibrate the temperature sensor if the room temperature displayed on the

 

thermostat does not match the room temperature measured. To do this, change

 

parameter P05

Setpoint and setpoint

We recommend to review the setpoints and setpoint ranges (parameters

range limitation

P08…P12) and change them as needed to achieve maximum comfort and save

 

energy

32 / 42

Siemens

RDG100…/RDG110…/RDG140.../RDG160… Basic Documentation

CE1P3182en

Building Technologies

Handling

28 May 2009

Image 32
Contents Building Technologies Edition CE1P3182en 28 MayTable of contents About this document Revision historyReference documents Before you startDocument use / request to the reader Types and features FeaturesSummary Brief descriptionEquipment combinations Accessories UseOrdering SSA81 SSP81… SSB81 SSD81 SQS85…Temperature control FunctionsGeneral note Described in sectionComfort mode Energy Saving Protection mode Operating modesSetpoints Comfort mode Energy Saving Protection mode Application Setpoints and sequenceSingle duct With min/max Limitation Single duct With Electrical HeaterComfort mode Energy Saving mode Application Heating mode Cooling mode Single ductProtection mode Heating mode Cooling mode With heating Cooling coilApplications overview Additional features Temperature sensor External / return airFloor heating Limitation functionSec after the last adjustment Button lockLocked or unlocked by pressing the right button for 3 sec Comf Extension Prot Absence Not available EcoSequences overview setting via parameter P01 Parameter P01 = Sequence ModeControl sequences Applications and sequencesFunction of the control outputs is set via DIP switches 4 Single-duct heating / cooling coilDIP Y10 = … 10 10 … 0 V inverted PositionSetting the sequence and the control outputs Single ductHeating or cooling Modulating control 3-position, PWM or DC 0 … 10Modulating electrical heater Single duct with electrical heaterSequences Single duct with radiator or floor heating Modulating radiator / floor heatingModulating heating / cooling coil Single duct with heating / cooling coilControl sequence Synchronization Control outputsControl output for air flow ON/OFF control signal Signal Position controlPosition actuator Parameter P44 Y1 and Y2Multifunctional input, Digital input AI/DIHandling of faults DIP switchesTemperature out RangeChange the parameters as follows Parameter settingControl parameters Parameters Service level Service levelParameters Expert level, diagnostics & test Expert levelDiagnostics & test Mounting and installation WiringHandling MountingOperation LayoutButton operation User actionDisposal LCD displayEngineering Connection terminalsConnection diagrams General DimensionsMechanical design Technical data Power supply Outputs Inputs Operational dataPage Index Automatic heating/cooling changeover