Comfort mode

Energy Saving

Note

Protection mode

4.2Operating modes

Select the thermostat's operating mode via operating mode button on the thermostat or operating mode input (e.g. keycard occupancy sensor, when X1, X2, or D1 set to 3 (P38, P40, P42). A corresponding setpoint is used to maintain the room temperature at the desired level depending on the active operating mode. The following operating modes are available:

In Comfort mode, the thermostat maintains the setpoint which can be adjusted via the rotary knob. The fan can be set to automatic or manual fan speed: Low, medium or high.

Energy Saving mode helps save energy. Select it by pressing the operating mode button if parameter P02 is set accordingly, or if the external operating mode switchover contact is active (e.g. window contact).

If the external operating mode switchover contact is active, user operations are ineffective and “OFF” is displayed. Control will then be according to Energy Saving setpoints (P11 and P12).

In Protection mode, the system is

protected against frost (factory setting 8°C, can be disabled or changed via P65)

protected against overheating (factory setting OFF, can be enabled or changed via P66)

Operating mode button The behavior of the operating mode button can be selected via parameter P02:

#

Sequence

Remark

1

 

Factory setting

2

 

 

 

 

9 / 42

 

 

 

Siemens

RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation

CE1P3182en

Building Technologies

Functions

28 May 2009

Image 9
Contents Edition CE1P3182en 28 May Building TechnologiesTable of contents Revision history About this documentReference documents Before you startDocument use / request to the reader Features Types and featuresSummary Brief descriptionEquipment combinations Use AccessoriesOrdering SSA81 SSP81… SSB81 SSD81 SQS85…Functions Temperature controlGeneral note Described in sectionOperating modes Comfort mode Energy Saving Protection modeSetpoints Setpoints and sequence Comfort mode Energy Saving Protection mode ApplicationSingle duct With min/max Limitation Single duct With Electrical HeaterHeating mode Cooling mode Single duct Comfort mode Energy Saving mode ApplicationProtection mode Heating mode Cooling mode With heating Cooling coilApplications overview Additional features External / return air Temperature sensorFloor heating Limitation functionButton lock Sec after the last adjustmentLocked or unlocked by pressing the right button for 3 sec Comf Extension Prot Absence Not available EcoParameter P01 = Sequence Mode Sequences overview setting via parameter P01Control sequences Applications and sequencesSingle-duct heating / cooling coil Function of the control outputs is set via DIP switches 4DIP Y10 = … 10 10 … 0 V inverted PositionSingle duct Setting the sequence and the control outputsHeating or cooling Modulating control 3-position, PWM or DC 0 … 10Single duct with electrical heater SequencesModulating electrical heater Modulating radiator / floor heating Single duct with radiator or floor heatingSingle duct with heating / cooling coil Control sequenceModulating heating / cooling coil Control outputs Control output for air flowSynchronization ON/OFF control signal Position control SignalPosition actuator Parameter P44 Y1 and Y2AI/DI Multifunctional input, Digital inputDIP switches Handling of faultsTemperature out RangeParameter setting Control parametersChange the parameters as follows Service level Parameters Service levelExpert level Parameters Expert level, diagnostics & testDiagnostics & test Wiring Mounting and installationHandling MountingLayout OperationButton operation User actionLCD display DisposalConnection terminals EngineeringConnection diagrams Dimensions Mechanical designGeneral Power supply Outputs Inputs Operational data Technical dataPage Automatic heating/cooling changeover Index