4.12.2Parameters Expert level, diagnostics & test
Parameter | Name | Factory setting | Range |
|
|
| ||
|
|
|
|
|
|
| RDG400 | |
| Expert level |
|
|
|
|
|
|
|
P30 | 2 K | 0.5 … 6 K |
|
|
| |||
|
|
|
|
|
|
| ||
P31 | 1 K | 0.5 … 6 K |
|
|
| |||
|
|
|
|
|
|
| ||
P32 | 2 K | 0.5 … 6 K |
|
|
| |||
|
|
|
|
|
|
| ||
P33 | Dead zone in Comfort mode | 2 K | 0.5 … 5 K |
|
|
| ||
P34 | Setpoint differential (wD) | 2 K | 0.5 … 5 K |
|
|
| ||
P35 | Integral time | 5 min | 0…10 min |
|
|
| ||
P36 | Heating / cooling changeover switching point | 16 °C | 10…25 °C |
|
|
| ||
| cooling (X1/X2) |
|
|
|
|
|
|
|
P37 | Heating / cooling changeover switching point | 28 °C | 27…40 °C |
|
|
| ||
| heating (X1/X2) |
|
|
|
|
|
|
|
P38 | Functionality of X1 | 1: = Ext. sensor | 0 | = |
|
| 0..6 | |
|
|
| 1 | = Room temp ext / Return temp (AI) |
| |||
|
|
| 2 | = H/C changeover (AI/DI) |
|
| ||
|
|
| 3 | = Operating mode contact [DI) |
|
| ||
|
|
| 4 | = Dew point sen. (DI) |
|
| ||
|
|
| 5 | = Enable electric heater (DI) |
|
| ||
|
|
| 6 | = Fault input (DI) |
|
|
| |
|
|
|
|
|
|
|
| |
P39 | Operating action of X1 if digital input | 0 (N.O.) | 0 | = Normally open | / Open |
|
| |
|
|
| 1 | = Normally closed | / Closed |
|
| |
P40 | Functionality of X2 | 2 = H/C changeover | 0 | = |
|
| 0..6 | |
|
|
| 1 | = Room temp ext / Return temp (AI) |
| |||
|
|
| 2 | = H/C changeover (AI/DI) |
|
| ||
|
|
| 3 | = Operating mode contact [DI) |
|
| ||
|
|
| 4 | = Dew point sen. (DI) |
|
| ||
|
|
| 5 | = Enable electric heater (DI) |
|
| ||
|
|
| 6 | = Fault input (DI) |
|
|
| |
|
|
|
|
|
|
|
| |
P41 | Operating action of X2 if digital input | 0 (N.O.) | 0 | = Normally open | / Open |
|
| |
|
|
| 1 | = Normally closed | / Closed |
|
| |
P42 | Functionality of D1 | 3 = Op. mode | 0 | = |
|
| 0..6 | |
|
| changeover | 2 | = H/C changeover (DI) |
| |||
|
|
| 3 | = Operating mode contact [DI) |
|
| ||
|
|
| 4 | = Dew point sen. (DI) |
|
| ||
|
|
| 5 | = Enable electric heater (DI) |
|
| ||
|
|
| 6 | = Fault input (DI) |
|
|
| |
|
|
|
|
|
|
| ||
P43 | Operating action of D1 if digital input | 0 (N.O.) | 0 | = Normally open / Open |
|
| ||
|
|
| 1 | = Normally closed / Closed |
|
| ||
P44 | Running time of Y1/Y2 output | 150 s | 20…300 sec |
|
|
| ||
| (only when modulating PI control) |
|
|
|
|
|
|
|
P46 | Output Y1/Y2 (if not parameterized as | ON/OFF (1) | 1 | = |
|
|
| |
|
|
| 2 | = PWM |
|
|
| |
P51 | Floor heating limit temperature | OFF | OFF, 10..50 °C |
|
|
| ||
|
|
|
|
|
|
| ||
P63 | Minimum output limitation air flow signal | 0% | 0…P64 (%) |
|
|
| ||
|
|
|
|
|
|
| ||
P64 | Maximum output limitation air flow signal | 100% | P63…100 (%) |
|
|
| ||
|
|
|
|
|
| |||
P65 | Protection heating setpoint | 8 °C | OFF, 5 … W Cool Prot; |
|
| |||
|
|
| (W Cool Prot = 40 °C max) |
|
| |||
P66 | Protection cooling setpoint | OFF | OFF, W Heat Prot … 40; |
|
| |||
|
|
| (W Heat Prot = 5 °C min.) |
|
| |||
P68 | Prolong Comfort period | OFF | OFF; 15 ... 360 min |
|
|
| ||
|
|
|
|
|
|
| ||
P69 | Temporary setpoint Comfort | OFF | OFF = Disabled |
|
|
| ||
| (see also Comfort setpoint P08) |
| ON = Enable |
|
|
| ||
P71 | Reload factory settings | OFF | OFF | = Disabled |
|
|
| |
|
|
| ON | = Reload start |
|
|
|
Note P46: Setting to
30 / 42
Siemens | RDG100…/RDG110…/RDG140.../RDG160… Basic Documentation | CE1P3182en |
Building Technologies | Functions | 28 May 2009 |