Parameter

d01

d02

d03

d04

d05

Name

Factory setting

Range

 

 

 

Diagnostics & test

 

 

 

 

 

 

 

 

 

RDG400

 

 

 

 

 

 

 

 

 

 

Application type

Diagnostics

0:= --- (No application)

 

 

 

 

1:= Single-duct

 

 

 

 

2:= Single-duct with el. heater

 

 

 

 

3:= Single-duct with radiator

 

 

 

 

4:= Single-duct with h/c coil

 

 

X1 status

Diagnostics

0

= Not activated (for DI)

 

 

 

 

1

= activated (DI)

 

 

 

 

0…49 °C = cur. temp. value (for AI)

 

 

 

 

00

 

 

 

 

= HC input short

 

 

 

 

 

 

 

 

 

 

 

 

 

100

 

= HC input open

 

 

X2 status

Diagnostics

0

= Not activated (for DI)

 

 

 

 

1

= activated (DI)

 

 

 

 

0…49 °C = cur. temp. value (for AI)

 

 

 

 

00

 

 

 

 

= HC input short

 

 

 

 

 

 

 

 

 

 

 

 

100

 

 

 

= HC input open

 

 

D1 status

Diagnostics

0

= Not activated (for DI)

 

 

 

 

1

= activated (DI)

 

 

 

 

00

 

 

 

 

= HC input short

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100 = HC input open

 

 

 

 

 

 

 

 

 

Test mode for checking the Y1/Y2

---

“---“ = no signal on outputs Y1 and Y2

 

 

actuator direction

 

OPE = output Y1 forced open

 

 

(press left button to escape)

 

CLO = output Y2 forced closing

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

31 / 42

 

 

 

Siemens

RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation

CE1P3182en

Building Technologies

Functions

28 May 2009

Image 31
Contents Edition CE1P3182en 28 May Building TechnologiesTable of contents Before you start About this documentRevision history Reference documentsDocument use / request to the reader Brief description Types and featuresFeatures SummaryEquipment combinations SSA81 SSP81… SSB81 SSD81 SQS85… AccessoriesUse OrderingDescribed in section Temperature controlFunctions General noteOperating modes Comfort mode Energy Saving Protection modeSetpoints Single duct With Electrical Heater Comfort mode Energy Saving Protection mode ApplicationSetpoints and sequence Single duct With min/max LimitationWith heating Cooling coil Comfort mode Energy Saving mode ApplicationHeating mode Cooling mode Single duct Protection mode Heating mode Cooling modeApplications overview Additional features Limitation function Temperature sensorExternal / return air Floor heatingComf Extension Prot Absence Not available Eco Sec after the last adjustmentButton lock Locked or unlocked by pressing the right button for 3 secApplications and sequences Sequences overview setting via parameter P01Parameter P01 = Sequence Mode Control sequencesPosition Function of the control outputs is set via DIP switches 4Single-duct heating / cooling coil DIP Y10 = … 10 10 … 0 V invertedModulating control 3-position, PWM or DC 0 … 10 Setting the sequence and the control outputsSingle duct Heating or coolingSequences Single duct with electrical heaterModulating electrical heater Modulating radiator / floor heating Single duct with radiator or floor heatingControl sequence Single duct with heating / cooling coilModulating heating / cooling coil Control output for air flow Control outputsSynchronization ON/OFF control signal Parameter P44 Y1 and Y2 SignalPosition control Position actuatorAI/DI Multifunctional input, Digital inputRange Handling of faultsDIP switches Temperature outControl parameters Parameter settingChange the parameters as follows Service level Parameters Service levelExpert level Parameters Expert level, diagnostics & testDiagnostics & test Mounting Mounting and installationWiring HandlingUser action OperationLayout Button operationLCD display DisposalConnection terminals EngineeringConnection diagrams Mechanical design DimensionsGeneral Power supply Outputs Inputs Operational data Technical dataPage Automatic heating/cooling changeover Index