4.9Multifunctional input, Digital input
The thermostat offers two multifunctional inputs X1 and X2 and a digital input D1. A sensor of type NTC like QAH11.1 (AI, analog input) or a switch (DI, digital input) can be connected to the input terminals. The functionality of the inputs can be configured via parameters P38 for X1, P40 for X2, and P42 for D1.
# | Function of input | Description | Type | Type |
|
|
| X1/X2 | DI |
0 | Not used | No function. | ||
1 | External/Return | Sensor input for external room temperature sensor or | AI |
|
| air temp. | return air temperature sensor to measure the current |
|
|
|
| room temperature, or floor heating temperature |
|
|
|
| sensor to limit the heating output. |
|
|
|
| Note: The room temperature is measured by the built- |
|
|
|
| in sensor if the floor heating limitation function is |
|
|
|
| enabled via parameter P51. |
|
|
2 | Heat/cool | Sensor input for automatic heating / cooling | AI/(DI) | DI |
| changeover | changeover function. |
|
|
|
| A switch can also be connected rather than a sensor |
|
|
|
| (switch closed = cooling, see section 4.6). |
|
|
3 | Operating mode | Digital input to switch over the operating mode to | DI | DI |
| switchover | Energy Saving. |
|
|
|
| If the operating mode switchover contact is active, |
|
|
|
| user operations are ineffective and “OFF” is displayed. |
|
|
4 | Dewpoint monitor | Digital input for a dewpoint sensor to detect | DI | DI |
|
| condensation. Cooling is stopped if condensation |
|
|
|
| occurs. |
|
|
5 | Enable electrical | Digital input to enable/disable the electrical heater via | DI | DI |
| heater | remote control. |
|
|
6 | Fault | Digital input to signal a fault. | DI | DI |
|
| If the input is active, “ALx” is displayed |
|
|
|
| (Alarm x, with x = 1 for X1, x = 2 for X2, x = 3 for D1). |
|
|
|
| Note: Fault displays do not influence the thermostat's |
|
|
|
| operation. They merely represent a visual signal. |
|
|
|
| Example: dirty air filter |
|
|
Operational action can be changed between normally open (N.O.) and normally closed (N.C.) via parameter P39, P41 (or P43 if it is a digital input).
Each input X1, X2 or D1 must be configured with a different function (1 … 5). Exception: one or two or three inputs may be configured as alarm inputs (6)
X1 is
For more information see section 4.5 “Applications”.