4.9Multifunctional input, Digital input

The thermostat offers two multifunctional inputs X1 and X2 and a digital input D1. A sensor of type NTC like QAH11.1 (AI, analog input) or a switch (DI, digital input) can be connected to the input terminals. The functionality of the inputs can be configured via parameters P38 for X1, P40 for X2, and P42 for D1.

#

Function of input

Description

Type

Type

 

 

 

X1/X2

DI

0

Not used

No function.

--

--

1

External/Return

Sensor input for external room temperature sensor or

AI

 

 

air temp.

return air temperature sensor to measure the current

 

 

 

 

room temperature, or floor heating temperature

 

 

 

 

sensor to limit the heating output.

 

 

 

 

Note: The room temperature is measured by the built-

 

 

 

 

in sensor if the floor heating limitation function is

 

 

 

 

enabled via parameter P51.

 

 

2

Heat/cool

Sensor input for automatic heating / cooling

AI/(DI)

DI

 

changeover

changeover function.

 

 

 

 

A switch can also be connected rather than a sensor

 

 

 

 

(switch closed = cooling, see section 4.6).

 

 

3

Operating mode

Digital input to switch over the operating mode to

DI

DI

 

switchover

Energy Saving.

 

 

 

 

If the operating mode switchover contact is active,

 

 

 

 

user operations are ineffective and “OFF” is displayed.

 

 

4

Dewpoint monitor

Digital input for a dewpoint sensor to detect

DI

DI

 

 

condensation. Cooling is stopped if condensation

 

 

 

 

occurs.

 

 

5

Enable electrical

Digital input to enable/disable the electrical heater via

DI

DI

 

heater

remote control.

 

 

6

Fault

Digital input to signal a fault.

DI

DI

 

 

If the input is active, “ALx” is displayed

 

 

 

 

(Alarm x, with x = 1 for X1, x = 2 for X2, x = 3 for D1).

 

 

 

 

Note: Fault displays do not influence the thermostat's

 

 

 

 

operation. They merely represent a visual signal.

 

 

 

 

Example: dirty air filter

 

 

Operational action can be changed between normally open (N.O.) and normally closed (N.C.) via parameter P39, P41 (or P43 if it is a digital input).

Each input X1, X2 or D1 must be configured with a different function (1 … 5). Exception: one or two or three inputs may be configured as alarm inputs (6)

X1 is factory-set to “External sensor” (1), X2 to “Heating/Cooling changeover” (2), and D1 to Operating mode changeover (3).

For more information see section 4.5 “Applications”.

26 / 42

Siemens

RDG100…/RDG110…/RDG140.../RDG160… Basic Documentation

CE1P3182en

Building Technologies

Functions

28 May 2009

Image 26
Contents Building Technologies Edition CE1P3182en 28 MayTable of contents Reference documents About this documentRevision history Before you startDocument use / request to the reader Summary Types and featuresFeatures Brief descriptionEquipment combinations Ordering AccessoriesUse SSA81 SSP81… SSB81 SSD81 SQS85…General note Temperature controlFunctions Described in sectionComfort mode Energy Saving Protection mode Operating modesSetpoints Single duct With min/max Limitation Comfort mode Energy Saving Protection mode ApplicationSetpoints and sequence Single duct With Electrical HeaterProtection mode Heating mode Cooling mode Comfort mode Energy Saving mode ApplicationHeating mode Cooling mode Single duct With heating Cooling coilApplications overview Additional features Floor heating Temperature sensorExternal / return air Limitation functionLocked or unlocked by pressing the right button for 3 sec Sec after the last adjustmentButton lock Comf Extension Prot Absence Not available EcoControl sequences Sequences overview setting via parameter P01Parameter P01 = Sequence Mode Applications and sequencesDIP Y10 = … 10 10 … 0 V inverted Function of the control outputs is set via DIP switches 4Single-duct heating / cooling coil PositionHeating or cooling Setting the sequence and the control outputsSingle duct Modulating control 3-position, PWM or DC 0 … 10Modulating electrical heater Single duct with electrical heaterSequences Single duct with radiator or floor heating Modulating radiator / floor heatingModulating heating / cooling coil Single duct with heating / cooling coilControl sequence Synchronization Control outputsControl output for air flow ON/OFF control signal Position actuator SignalPosition control Parameter P44 Y1 and Y2Multifunctional input, Digital input AI/DITemperature out Handling of faultsDIP switches RangeChange the parameters as follows Parameter settingControl parameters Parameters Service level Service levelParameters Expert level, diagnostics & test Expert levelDiagnostics & test Handling Mounting and installationWiring MountingButton operation OperationLayout User actionDisposal LCD displayEngineering Connection terminalsConnection diagrams General DimensionsMechanical design Technical data Power supply Outputs Inputs Operational dataPage Index Automatic heating/cooling changeover