4.12.1Parameters Service level
Parameter | Name | Factory setting | Range |
|
| ||
|
|
|
|
|
| RDG400 | |
| Service level |
|
|
|
|
|
|
P01 | Control sequence | When | 0 | = Heating only |
|
| |
|
| 1 | = Cooling only |
|
| ||
|
| 1 | = Cooling only | 2 | = H/C changeover manual |
|
|
|
| When | 3 | = H/C changeover auto |
|
| |
|
| 4 | = H and C | 4 | = Heating and Cooling |
|
|
|
|
|
|
|
|
|
|
P02 | User operating mode profile (mode button) | 1 |
| 1 | = (Auto) - Comfort - Protection |
|
|
|
|
|
| 2 | = (Auto) - Comfort - E Saving - Prot |
|
|
P04 | Selection of °C or °F | 0 | (°C) | 0 | = Degrees Celsius (°C) |
|
|
|
|
|
| 1 | = Degrees Fahrenheit (°F) |
|
|
P05 | Sensor calibration (intern, extern) | 0 | K | – 3 ... 3 K |
|
| |
P06 | Standard temperature display | 0 |
| 0 | = Room Temperature |
|
|
|
|
|
| 1 | = Setpoint |
|
|
P07 | Display info line | 0 |
| 0 | = |
| 0..1 |
| (2nd line of LCD) |
|
| 1 | = °C and °F |
|
|
P08 | Comfort setpoint | 21 °C | 5 | ... 40 °C |
|
| |
P09 | Minimum setpoint in Comfort mode | 5 | °C | 5 | ... 40 °C |
|
|
P10 | Maximum setpoint in Comfort mode | 35 °C | 5 | ... 40 °C |
|
| |
P11 | Energy Saving heating setpoint | 15 °C | OFF, 5 ... |
|
| ||
|
|
|
|
|
| ||
P12 | Energy Saving cooling setpoint | 30 °C | OFF, |
|
| ||
|
|
|
|
|
| ||
P14 | Button lock function | 0 |
| 0 | = Unlocked |
|
|
|
|
|
| 1 | = Auto locked |
|
|
|
|
|
| 2 | = Manual locked |
|
|
|
|
|
|
|
|
|
|
Note Parameter display depends on selected application and function
|
| 29 / 42 |
|
|
|
Siemens | RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation | CE1P3182en |
Building Technologies | Functions | 28 May 2009 |