4.12Control parameters

A number of control parameters can be readjusted to optimize control performance. These parameters can also be set during operation without opening the unit. In the event of a power failure, all control parameter settings are retained.

The control parameters are divided in two levels:

“Service” level, and

“Expert” level and "Diagnostics & test"

The “Service” level contains a small set of parameters to set up the thermostat for the HVAC system and to adjust the user interface. These parameters can usually be adjusted any time.

Change parameters in the “Expert” level only carefully, as they impact control performance and functionality of the thermostat.

Parameter setting

Change the parameters as follows:

Enter only “Service”

1.

Press left + right button simultaneously >3sec, release,

level

 

then press right button >3sec

 

 

The display shows “P01” (or P02 when P01 is not available).

 

 

Continue with Step 2.

Enter “Expert” level

1.

Press left button + right button simultaneously >3sec, release,

and

 

press left button >3sec,

"Diagnostics & test"

 

then rotate rotary knob anti-clockwise min ½ rotation

 

 

The display shows “Pxx”.

 

 

Continue with Step 2.

Adjust parameters

2.

Select the required parameter by turning the rotary knob.

 

3.

Press

 

(OK); the current value of the selected parameter starts to flash and

 

 

 

 

can be changed by turning the rotary knob.

 

4.

Press

 

(OK) to confirm the adjusted value or (Esc) to cancel the change.

 

 

 

5.

If you wish to adjust additional parameters, repeat steps 2 through 4

 

6.

Press

 

(Esc) to leave the parameter mode.

Reset parameters

The factory setting for the control parameters can be reloaded via parameter P71,

 

by changing the value to “ON”, and confirming by pressing the right button.

 

The display shows “8888” during reload.

28 / 42

Siemens

RDG100…/RDG110…/RDG140.../RDG160… Basic Documentation

CE1P3182en

Building Technologies

Functions

28 May 2009

Image 28
Contents Building Technologies Edition CE1P3182en 28 MayTable of contents About this document Revision historyReference documents Before you startDocument use / request to the reader Types and features FeaturesSummary Brief descriptionEquipment combinations Accessories UseOrdering SSA81 SSP81… SSB81 SSD81 SQS85…Temperature control FunctionsGeneral note Described in sectionComfort mode Energy Saving Protection mode Operating modesSetpoints Comfort mode Energy Saving Protection mode Application Setpoints and sequenceSingle duct With min/max Limitation Single duct With Electrical HeaterComfort mode Energy Saving mode Application Heating mode Cooling mode Single ductProtection mode Heating mode Cooling mode With heating Cooling coilApplications overview Additional features Temperature sensor External / return airFloor heating Limitation functionSec after the last adjustment Button lockLocked or unlocked by pressing the right button for 3 sec Comf Extension Prot Absence Not available EcoSequences overview setting via parameter P01 Parameter P01 = Sequence ModeControl sequences Applications and sequencesFunction of the control outputs is set via DIP switches 4 Single-duct heating / cooling coilDIP Y10 = … 10 10 … 0 V inverted PositionSetting the sequence and the control outputs Single ductHeating or cooling Modulating control 3-position, PWM or DC 0 … 10Sequences Single duct with electrical heaterModulating electrical heater Single duct with radiator or floor heating Modulating radiator / floor heatingControl sequence Single duct with heating / cooling coilModulating heating / cooling coil Control output for air flow Control outputsSynchronization ON/OFF control signal Signal Position controlPosition actuator Parameter P44 Y1 and Y2Multifunctional input, Digital input AI/DIHandling of faults DIP switchesTemperature out RangeControl parameters Parameter settingChange the parameters as follows Parameters Service level Service levelParameters Expert level, diagnostics & test Expert levelDiagnostics & test Mounting and installation WiringHandling MountingOperation LayoutButton operation User actionDisposal LCD displayEngineering Connection terminalsConnection diagrams Mechanical design DimensionsGeneral Technical data Power supply Outputs Inputs Operational dataPage Index Automatic heating/cooling changeover