4.8.2Control output for electrical heater, radiator and heating / cooling coil

ON/OFF control signal

(2-position)

Electrical heater control signal (2-position)

Caution

DC 0 ... 10 V for el. heaters

The valve receives an OPEN/ON command via control output Y1

1.When the acquired room temperature is below “setpoint” (heating mode) or above the setpoint (cooling mode)

2.When the control outputs have been inactive for more than the “Minimum output off-time” (factory setting 1 minute, adjustable via parameter P48).

OFF command for valve output:

1.When the acquired room temperature is above the setpoint (heating mode) or below the setpoint (cooling mode).

2.When the valve has been active for more than the “Minimum output on-time” (factory setting 1 minute, adjustable via parameter P49).

The electrical heater receives an ON command via the auxiliary heating control output (Y1):

1.When the acquired room temperature is below “setpoint for electric heater”.

2.When the electrical heater has been switched off for at least 1 minute.

The OFF command for the electrical heater is output:

1.When the acquired room temperature is above the setpoint (electric heater).

2.When the electrical heater has been switched on for at least 1 minute.

A safety thermostat (to prevent overheating) must be provided externally.

The demand calculated by PI control from the current room temperature and setpoint is provided via Y10 as a continuous DC 0 ... 10 V signal.

The signal converter (SEM61.4) converts the DC 0 ... 10 V signal to AC 24 V PDM pulses for the current valve

The current valve (SEA45.1) supplies the el. heater with AC 50 … 660 V pulsed current.

L

 

 

 

 

 

 

 

3181D21

G

 

 

 

 

 

 

FF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

G Y

 

 

 

 

 

 

 

 

 

 

 

 

 

E

 

F...

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Y

N1

PWM

 

 

 

 

 

 

 

 

 

 

 

 

U1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC 24 V

 

 

 

 

 

 

 

 

 

G0 Y1 G

 

 

 

 

 

 

 

 

 

DC 0 ... 10 V

 

 

 

 

L

 

 

 

 

 

 

 

 

 

Y1

G

 

Q

Y1

G0

N

K...

5.7kW

max.

 

N1

RDG400

 

 

 

U1

Signal converter SEM61.4

(see data sheet N5102)

 

 

Y1

Current valve SEA45.1

(see data sheet N4937)

 

 

K…

Safety "chain", e.g. safety thermostat and high-temperature cut-out

 

 

FF

Very fast-acting fuse

 

 

 

F…

Overcurrent trip

 

 

24 / 42

 

 

 

 

 

 

 

Siemens

RDG100…/RDG110…/RDG140.../RDG160… Basic Documentation

CE1P3182en

Building Technologies

Functions

 

28 May 2009

Image 24
Contents Building Technologies Edition CE1P3182en 28 MayTable of contents About this document Revision historyReference documents Before you startDocument use / request to the reader Types and features FeaturesSummary Brief descriptionEquipment combinations Accessories UseOrdering SSA81 SSP81… SSB81 SSD81 SQS85…Temperature control FunctionsGeneral note Described in sectionComfort mode Energy Saving Protection mode Operating modesSetpoints Comfort mode Energy Saving Protection mode Application Setpoints and sequenceSingle duct With min/max Limitation Single duct With Electrical HeaterComfort mode Energy Saving mode Application Heating mode Cooling mode Single ductProtection mode Heating mode Cooling mode With heating Cooling coilApplications overview Additional features Temperature sensor External / return airFloor heating Limitation functionSec after the last adjustment Button lockLocked or unlocked by pressing the right button for 3 sec Comf Extension Prot Absence Not available EcoSequences overview setting via parameter P01 Parameter P01 = Sequence ModeControl sequences Applications and sequencesFunction of the control outputs is set via DIP switches 4 Single-duct heating / cooling coilDIP Y10 = … 10 10 … 0 V inverted PositionSetting the sequence and the control outputs Single ductHeating or cooling Modulating control 3-position, PWM or DC 0 … 10Single duct with electrical heater SequencesModulating electrical heater Single duct with radiator or floor heating Modulating radiator / floor heatingSingle duct with heating / cooling coil Control sequenceModulating heating / cooling coil Control outputs Control output for air flowSynchronization ON/OFF control signal Signal Position controlPosition actuator Parameter P44 Y1 and Y2Multifunctional input, Digital input AI/DIHandling of faults DIP switchesTemperature out RangeParameter setting Control parametersChange the parameters as follows Parameters Service level Service levelParameters Expert level, diagnostics & test Expert levelDiagnostics & test Mounting and installation WiringHandling MountingOperation LayoutButton operation User actionDisposal LCD displayEngineering Connection terminalsConnection diagrams Dimensions Mechanical designGeneral Technical data Power supply Outputs Inputs Operational dataPage Index Automatic heating/cooling changeover