Siemens RDG400 manual Additional features

Page 14

4.6Additional features

Output signal inversion

Min / Max air flow

The output signals DC 0…10V can be inverted by means of DIP switch 4 (see section 4.7.3).

To ensure a minimum or maximum supply air volume, the output signal for the air flow (DC 0...10V or 3-position) can be limited to a minimum value via parameter P63 and to a maximum value via parameter P64.

Both values can be set between 0% and 100%.

 

 

Changeover

 

T

Y10

 

 

 

XpH

XpC

 

Y10

 

H

C

100%

 

 

w

 

 

 

 

Vmax

 

 

 

max

XpH

 

 

 

 

XpC

 

 

 

 

 

Vmin

 

 

 

 

Vmin

 

 

 

min

Vmax

 

 

 

 

0%

 

 

W

TR [°C]

 

 

 

 

 

Room temperature Control output

Room temperature setpoint Proportional band Heating Proportional band Cooling Minimum limitation air flow Maximum limitation air flow

If Vmin is not set >0, then a minimum air flow of Vmin is assured in Comfort and Energy Saving modes. In Protected mode, Vmin is 0.

Comfort or Energy Saving mode with Vmin

Y

 

 

 

100%

H

 

C

Vmax

 

 

max

 

 

 

Vmin

 

YV

 

 

min

 

 

 

0%

SpHComf/Eco

SpCComf/Eco

TR [°C]

 

Protection mode (Vmin = 0)

Y

 

 

 

100%

H

 

C

Vmax

 

 

max

 

 

 

Vmin

 

 

YV

 

 

min

 

 

 

0%

SpHProt

SpCProt

TR [°C]

 

Automatic H/C

The water temperature acquired by the changeover sensor (QAH11.1 + ARG86.3)

changeover

is used to change over from heating to cooling mode and vice-versa. When the

 

water temperature is above 28 °C (parameter P37), the thermostat changes over to

 

heating mode, and to cooling mode when below 16 °C (parameter P36).

 

If the water temperature is between the 2 changeover points immediately after

 

power-up, the thermostat starts in heating mode.

 

The water temperature is acquired at 30-second intervals and the operating state is

 

updated accordingly.

 

 

 

 

 

 

M

 

Tw[°C]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

28

 

 

MOperating mode Tw Water temperature

Cooling mode Heating mode

Remote heating/

The QAH11.1 cable temperature sensor for automatic heating/cooling changeover

cooling changeover

can be replaced by an external switch for manual, remote changeover:

 

14 / 42

 

 

 

 

 

Siemens

RDG100…/RDG110…/RDG140.../RDG160… Basic Documentation

CE1P3182en

Building Technologies

Functions

28 May 2009

Image 14
Contents Building Technologies Edition CE1P3182en 28 MayTable of contents Reference documents About this documentRevision history Before you startDocument use / request to the reader Summary Types and featuresFeatures Brief descriptionEquipment combinations Ordering AccessoriesUse SSA81 SSP81… SSB81 SSD81 SQS85…General note Temperature controlFunctions Described in sectionComfort mode Energy Saving Protection mode Operating modesSetpoints Single duct With min/max Limitation Comfort mode Energy Saving Protection mode ApplicationSetpoints and sequence Single duct With Electrical HeaterProtection mode Heating mode Cooling mode Comfort mode Energy Saving mode ApplicationHeating mode Cooling mode Single duct With heating Cooling coilApplications overview Additional features Floor heating Temperature sensorExternal / return air Limitation functionLocked or unlocked by pressing the right button for 3 sec Sec after the last adjustmentButton lock Comf Extension Prot Absence Not available EcoControl sequences Sequences overview setting via parameter P01Parameter P01 = Sequence Mode Applications and sequencesDIP Y10 = … 10 10 … 0 V inverted Function of the control outputs is set via DIP switches 4Single-duct heating / cooling coil PositionHeating or cooling Setting the sequence and the control outputsSingle duct Modulating control 3-position, PWM or DC 0 … 10Modulating electrical heater Single duct with electrical heaterSequences Single duct with radiator or floor heating Modulating radiator / floor heatingModulating heating / cooling coil Single duct with heating / cooling coilControl sequence Synchronization Control outputsControl output for air flow ON/OFF control signal Position actuator SignalPosition control Parameter P44 Y1 and Y2Multifunctional input, Digital input AI/DITemperature out Handling of faultsDIP switches RangeChange the parameters as follows Parameter settingControl parameters Parameters Service level Service levelParameters Expert level, diagnostics & test Expert levelDiagnostics & test Handling Mounting and installationWiring MountingButton operation OperationLayout User actionDisposal LCD displayEngineering Connection terminalsConnection diagrams General DimensionsMechanical design Technical data Power supply Outputs Inputs Operational dataPage Index Automatic heating/cooling changeover