Siemens RDG400 Single duct, Heating or cooling, Modulating control 3-position, PWM or DC 0 … 10

Page 19

 

4.7.4

Single duct

 

 

Single duct,

In single duct applications, the controller controls an actuator (valve, damper, VAV

heating or cooling

system, etc)

 

in heating/cooling mode with changeover (automatic or manual),

 

heating only mode,

 

or cooling only mode.

Cooling only is factory set (P01=1).

The output signal for the air flow can be limited to a minimum and maximum value if required (see section 4.6 "additional features").

Modulating control 3-position, PWM or DC 0 … 10 V

The diagram below shows the control sequence for continuous PI control.

Heating only (P01 = 0)

 

Y10

XpH

 

 

H

 

100%

 

 

 

 

 

Vmax

 

 

max

 

 

 

Vmin

 

 

min

 

 

 

0%

 

W

TR [°C]

 

 

Changeover (P01 = 2, 3)

 

 

 

Changeover

 

Y10

XpH

XpC

 

 

H

C

100%

 

 

 

 

 

 

Vmax

 

 

 

max

 

 

 

 

Vmin

 

 

 

min

 

 

 

 

0%

 

W

 

TR [°C]

 

 

 

Cooling only (P01 = 1)

 

Y10

 

XpC

C

100%

 

Vmax

max

 

Vmin

min

 

0%

 

W

TR [°C]

T[°C]

Room temperature

XpH

Proportional band “Heating”

w

Room temperature setpoint

XpC

Proportional band “Cooling”

Y10

Control command “Valve”

Vmin

Min. limitation for output

 

 

Vmax

Max. limitation for output

Note The diagrams show the PI controller’s proportional part only.

Setting the sequence and the control outputs

Refer to sections 4.5 (applications), 4.7.1 (sequences) and 4.7.3 (outputs).

 

 

19 / 42

 

 

 

Siemens

RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation

CE1P3182en

Building Technologies

Functions

28 May 2009

Image 19
Contents Edition CE1P3182en 28 May Building TechnologiesTable of contents Before you start About this documentRevision history Reference documentsDocument use / request to the reader Brief description Types and featuresFeatures SummaryEquipment combinations SSA81 SSP81… SSB81 SSD81 SQS85… AccessoriesUse OrderingDescribed in section Temperature controlFunctions General noteOperating modes Comfort mode Energy Saving Protection modeSetpoints Single duct With Electrical Heater Comfort mode Energy Saving Protection mode ApplicationSetpoints and sequence Single duct With min/max LimitationWith heating Cooling coil Comfort mode Energy Saving mode ApplicationHeating mode Cooling mode Single duct Protection mode Heating mode Cooling modeApplications overview Additional features Limitation function Temperature sensorExternal / return air Floor heatingComf Extension Prot Absence Not available Eco Sec after the last adjustmentButton lock Locked or unlocked by pressing the right button for 3 secApplications and sequences Sequences overview setting via parameter P01Parameter P01 = Sequence Mode Control sequencesPosition Function of the control outputs is set via DIP switches 4Single-duct heating / cooling coil DIP Y10 = … 10 10 … 0 V invertedModulating control 3-position, PWM or DC 0 … 10 Setting the sequence and the control outputsSingle duct Heating or coolingSequences Single duct with electrical heaterModulating electrical heater Modulating radiator / floor heating Single duct with radiator or floor heatingControl sequence Single duct with heating / cooling coilModulating heating / cooling coil Control output for air flow Control outputsSynchronization ON/OFF control signal Parameter P44 Y1 and Y2 SignalPosition control Position actuatorAI/DI Multifunctional input, Digital inputRange Handling of faultsDIP switches Temperature outControl parameters Parameter settingChange the parameters as follows Service level Parameters Service levelExpert level Parameters Expert level, diagnostics & testDiagnostics & test Mounting Mounting and installationWiring HandlingUser action OperationLayout Button operationLCD display DisposalConnection terminals EngineeringConnection diagrams Mechanical design DimensionsGeneral Power supply Outputs Inputs Operational data Technical dataPage Automatic heating/cooling changeover Index