| 4.7.4 | Single duct | |
|
| ||
Single duct, | In single duct applications, the controller controls an actuator (valve, damper, VAV | ||
heating or cooling | system, etc) | ||
| – | in heating/cooling mode with changeover (automatic or manual), | |
| – | heating only mode, | |
| – | or cooling only mode. |
Cooling only is factory set (P01=1).
The output signal for the air flow can be limited to a minimum and maximum value if required (see section 4.6 "additional features").
Modulating control 3-position, PWM or DC 0 … 10 V
The diagram below shows the control sequence for continuous PI control.
Heating only (P01 = 0) |
| ||
Y10 | XpH |
| |
| H |
| |
100% |
|
| |
|
|
| |
Vmax |
|
| max |
|
|
| |
Vmin |
|
| min |
|
|
| |
0% |
| W | TR [°C] |
|
|
Changeover (P01 = 2, 3) |
| |||
|
| Changeover |
| |
Y10 | XpH | XpC |
| |
| H | C | ||
100% |
|
| ||
|
|
|
| |
Vmax |
|
|
| max |
|
|
|
| |
Vmin |
|
|
| min |
|
|
|
| |
0% |
| W |
| TR [°C] |
|
|
|
Cooling only (P01 = 1) |
| |
Y10 |
| |
XpC | C | |
100% | ||
| ||
Vmax | max | |
| ||
Vmin | min | |
| ||
0% |
| |
W | TR [°C] |
T[°C] | Room temperature | XpH | Proportional band “Heating” |
w | Room temperature setpoint | XpC | Proportional band “Cooling” |
Y10 | Control command “Valve” | Vmin | Min. limitation for output |
|
| Vmax | Max. limitation for output |
Note The diagrams show the PI controller’s proportional part only.
Setting the sequence and the control outputs
Refer to sections 4.5 (applications), 4.7.1 (sequences) and 4.7.3 (outputs).
|