Siemens RDG400 External / return air, Temperature sensor, Floor heating, Limitation function

Page 15

 

 

X2

T

X2

Contact open

heating mode

 

 

 

 

 

M

M

 

 

 

 

 

 

 

 

QAH11.1

Contact closed

cooling mode

 

 

 

 

3076Z03

 

 

 

 

 

 

 

 

 

 

 

T °C

 

 

 

 

 

 

 

 

The sensor or switch can be connected to the input terminal X2 (factory setting) or

 

X1 or D1 (switch only), depending on the commissioning of the inputs (P38, P40,

 

P42).

 

 

 

 

 

 

 

 

See also section 4.9 “Multifunctional input”.

 

 

 

 

 

External / return air

The thermostat acquires the room temperature via built-in sensor, external room

temperature sensor

temperature sensor (QAA32), or external return air temperature sensor (QAH11.1)

 

connected to multifunctional input X1 or X2.

 

 

 

 

 

 

Inputs X1 or X2 need to be commissioned accordingly. See section 4.9 “Multi-

 

functional input”.

 

 

 

 

 

 

 

Floor heating

Application "Single duct and radiator" can also be used for floor heating.

Floor heating

The temperature should be limited for two reasons: comfort and protection of the

limitation function

floor. It is only available with application "Single duct and radiator".

 

 

 

 

 

The floor temperature sensor, connected to multifunctional input X1 or X2,

 

 

 

 

 

measures the floor temperature. If the temperature exceeds the parameterized limit

 

 

 

 

 

(parameter P51), the heating valve is fully closed until the floor temperature drops

 

 

 

 

 

to 2K below the parameterized limit.

 

 

 

 

 

 

 

 

 

This function is factory-set to OFF (disabled).

 

 

 

 

 

 

 

 

Input X1 or X2 must be commissioned accordingly (P38 or P40 = 1).

 

 

 

 

 

See section 4.9 “Multifunctional input”.

 

 

 

 

Recommended values

Living rooms:

 

 

 

 

for P51:

 

up to 26 °C for long term presence, up to 28 °C for short time presence

 

 

 

 

 

Bath rooms:

 

 

 

 

 

 

 

 

 

 

 

up to 28 °C for long term presence, up to 30 °C for short time presence

 

 

 

 

 

The table below shows the relation between parameter, temperature source and

 

 

 

 

 

temperature display:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parameter P51

 

External temp.

 

Source for display of room

 

Output control according

Floor temp. limit

 

 

 

 

sensor available

 

temperature

 

to

function

 

 

 

 

 

 

 

 

 

 

OFF

No

 

 

Built-in sensor

 

Built-in sensor

Not active

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Yes

 

 

External temp. sensor

 

External temp. sensor

Not active

 

 

 

 

 

 

 

 

 

 

 

 

 

10...50˚C

No

 

 

Built-in sensor

 

Built-in sensor

Not active

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10…50˚C

Yes

 

 

Built-in sensor

 

Built-in sensor + limit by

Active

 

 

 

 

 

external sensor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Dewpoint monitoring

Dewpoint monitoring is essential to prevent condensation on the cooling coil.

 

 

 

 

 

It helps avoid associated damage to the building.

 

 

 

 

 

 

 

 

A dewpoint sensor with a potential-free contact is connected to multifunctional input

 

 

 

 

 

X1, X2 or D1. If there is condensation, the cooling valve is fully closed until no

 

 

 

 

 

more condensation is detected, and the cooling output is disabled temporarily.

 

 

 

 

 

The condensation symbol is displayed during temporary override.

 

 

 

 

 

The input must be commissioned accordingly (P38, P40, P42).

 

 

 

 

 

 

 

 

See section 4.9 “Multifunctional input”.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15 / 42

 

 

 

 

 

 

 

 

 

 

 

 

Siemens

 

RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation

CE1P3182en

 

Building Technologies

 

Functions

 

 

 

28 May 2009

Image 15
Contents Edition CE1P3182en 28 May Building TechnologiesTable of contents Before you start About this documentRevision history Reference documentsDocument use / request to the reader Brief description Types and featuresFeatures SummaryEquipment combinations SSA81 SSP81… SSB81 SSD81 SQS85… AccessoriesUse OrderingDescribed in section Temperature controlFunctions General noteOperating modes Comfort mode Energy Saving Protection modeSetpoints Single duct With Electrical Heater Comfort mode Energy Saving Protection mode ApplicationSetpoints and sequence Single duct With min/max LimitationWith heating Cooling coil Comfort mode Energy Saving mode ApplicationHeating mode Cooling mode Single duct Protection mode Heating mode Cooling modeApplications overview Additional features Limitation function Temperature sensorExternal / return air Floor heatingComf Extension Prot Absence Not available Eco Sec after the last adjustmentButton lock Locked or unlocked by pressing the right button for 3 secApplications and sequences Sequences overview setting via parameter P01Parameter P01 = Sequence Mode Control sequencesPosition Function of the control outputs is set via DIP switches 4Single-duct heating / cooling coil DIP Y10 = … 10 10 … 0 V invertedModulating control 3-position, PWM or DC 0 … 10 Setting the sequence and the control outputsSingle duct Heating or coolingSingle duct with electrical heater SequencesModulating electrical heater Modulating radiator / floor heating Single duct with radiator or floor heatingSingle duct with heating / cooling coil Control sequenceModulating heating / cooling coil Control outputs Control output for air flowSynchronization ON/OFF control signal Parameter P44 Y1 and Y2 SignalPosition control Position actuatorAI/DI Multifunctional input, Digital inputRange Handling of faultsDIP switches Temperature outParameter setting Control parametersChange the parameters as follows Service level Parameters Service levelExpert level Parameters Expert level, diagnostics & testDiagnostics & test Mounting Mounting and installationWiring HandlingUser action OperationLayout Button operationLCD display DisposalConnection terminals EngineeringConnection diagrams Dimensions Mechanical designGeneral Power supply Outputs Inputs Operational data Technical dataPage Automatic heating/cooling changeover Index