| X2 | T | X2 | Contact open | heating mode |
|
|
|
|
| M | M |
|
|
| |||
|
|
| |||||||
|
| QAH11.1 | Contact closed | cooling mode |
| ||||
|
|
| 3076Z03 |
| |||||
|
|
|
|
|
|
|
| ||
|
| T °C |
|
|
|
|
|
|
|
| The sensor or switch can be connected to the input terminal X2 (factory setting) or | ||||||||
| X1 or D1 (switch only), depending on the commissioning of the inputs (P38, P40, | ||||||||
| P42). |
|
|
|
|
|
|
| |
| See also section 4.9 “Multifunctional input”. |
|
|
|
|
| |||
External / return air | The thermostat acquires the room temperature via | ||||||||
temperature sensor | temperature sensor (QAA32), or external return air temperature sensor (QAH11.1) | ||||||||
| connected to multifunctional input X1 or X2. |
|
|
|
|
| |||
| Inputs X1 or X2 need to be commissioned accordingly. See section 4.9 “Multi- | ||||||||
| functional input”. |
|
|
|
|
|
|
| |
Floor heating | Application "Single duct and radiator" can also be used for floor heating. | ||||||||
Floor heating | The temperature should be limited for two reasons: comfort and protection of the | ||||||||
limitation function | floor. It is only available with application "Single duct and radiator". |
|
|
|
|
| The floor temperature sensor, connected to multifunctional input X1 or X2, | |||||||
|
|
|
|
| measures the floor temperature. If the temperature exceeds the parameterized limit | |||||||
|
|
|
|
| (parameter P51), the heating valve is fully closed until the floor temperature drops | |||||||
|
|
|
|
| to 2K below the parameterized limit. |
|
|
|
| |||
|
|
|
|
| This function is |
|
|
| ||||
|
|
|
|
| Input X1 or X2 must be commissioned accordingly (P38 or P40 = 1). | |||||||
|
|
|
|
| See section 4.9 “Multifunctional input”. |
|
|
|
| |||
Recommended values | Living rooms: |
|
|
|
| |||||||
for P51: |
| up to 26 °C for long term presence, up to 28 °C for short time presence | ||||||||||
|
|
|
|
| Bath rooms: |
|
|
|
|
|
| |
|
|
|
|
| up to 28 °C for long term presence, up to 30 °C for short time presence | |||||||
|
|
|
|
| The table below shows the relation between parameter, temperature source and | |||||||
|
|
|
|
| temperature display: |
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
| |
|
| Parameter P51 |
| External temp. |
| Source for display of room |
| Output control according | Floor temp. limit |
| ||
|
|
| sensor available |
| temperature |
| to | function |
| |||
|
|
|
|
|
|
| ||||||
|
| OFF | No |
|
|
| Not active |
| ||||
|
|
|
|
|
|
|
|
|
|
| ||
|
| OFF | Yes |
|
| External temp. sensor |
| External temp. sensor | Not active | |||
|
|
|
|
|
|
|
|
|
|
| ||
|
| 10...50˚C | No |
|
|
| Not active | |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 10…50˚C | Yes |
|
|
| Active | |||||
|
|
|
|
| external sensor | |||||||
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| |||||
| Dewpoint monitoring | Dewpoint monitoring is essential to prevent condensation on the cooling coil. | ||||||||||
|
|
|
|
| It helps avoid associated damage to the building. |
|
|
| ||||
|
|
|
|
| A dewpoint sensor with a | |||||||
|
|
|
|
| X1, X2 or D1. If there is condensation, the cooling valve is fully closed until no | |||||||
|
|
|
|
| more condensation is detected, and the cooling output is disabled temporarily. | |||||||
|
|
|
|
| The condensation symbol is displayed during temporary override. | |||||||
|
|
|
|
| The input must be commissioned accordingly (P38, P40, P42). |
|
|
| ||||
|
|
|
|
| See section 4.9 “Multifunctional input”. |
|
|
|
| |||
|
|
|
|
|
|
|
|
|
| 15 / 42 | ||
|
|
|
|
|
|
|
|
|
|
| ||
| Siemens |
| RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation | CE1P3182en | ||||||||
| Building Technologies |
| Functions |
|
|
| 28 May 2009 |