4.7Control sequences

4.7.1Applications and sequences

Application VAV

Sequences

 

 

Single duct

h ( \ ), c ( / )

Single duct & electrical heater

el.h + c (

\

/

)

Single duct & radiator

rad + c (

r\

/

),

Single duct with heat/cool coil

h + c ( \

/ )

 

 

4.7.2Sequences overview (setting via parameter P01)

The sequence can be set via parameter P01, if available.

The thermostats can be used in systems featuring:

Heating only mode (P01=0)

Cooling only mode (P01=1)

Manual heating/cooling changeover (P01=2)

Automatic heating/cooling changeover (P01=3)

Heating and cooling mode (e.g. 4-pipe system) (P01=4)

The available modes depend on the application (selected via DIP switch, see section 4.5).

Parameter

P01 = 0

P01 = 1

Sequence

 

 

 

 

 

 

 

T °C

T °C

Mode

 

 

Heating mode

Cooling mode

Available for:

 

 

 

 

 

 

 

 

 

Single duct

 

 

 

 

 

 

 

Single duct &

3)

3)

electrical heater

 

 

 

 

Single duct &

3)

3)

radiator

 

 

 

 

Single duct with

 

 

 

 

heat/cool coil

 

 

 

 

P01 = 2

T °C

Manually select heating or cooling mode

1)

3)

3)

2)

P01 = 3

T

T °C

Automatic

heating/cooling

changeover via

external water

temperature

sensor or

remote switch

1)

3)

3)

2)

Notes 1) Changeover air

2)Changeover water; heat/cool coil

3)The controller operates in heating AND cooling mode. P01 is not available

 

 

17 / 42

 

 

 

Siemens

RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation

CE1P3182en

Building Technologies

Functions

28 May 2009

Image 17
Contents Edition CE1P3182en 28 May Building TechnologiesTable of contents Revision history About this documentReference documents Before you startDocument use / request to the reader Features Types and featuresSummary Brief descriptionEquipment combinations Use AccessoriesOrdering SSA81 SSP81… SSB81 SSD81 SQS85…Functions Temperature controlGeneral note Described in sectionOperating modes Comfort mode Energy Saving Protection modeSetpoints Setpoints and sequence Comfort mode Energy Saving Protection mode ApplicationSingle duct With min/max Limitation Single duct With Electrical HeaterHeating mode Cooling mode Single duct Comfort mode Energy Saving mode ApplicationProtection mode Heating mode Cooling mode With heating Cooling coilApplications overview Additional features External / return air Temperature sensorFloor heating Limitation functionButton lock Sec after the last adjustmentLocked or unlocked by pressing the right button for 3 sec Comf Extension Prot Absence Not available EcoParameter P01 = Sequence Mode Sequences overview setting via parameter P01Control sequences Applications and sequencesSingle-duct heating / cooling coil Function of the control outputs is set via DIP switches 4DIP Y10 = … 10 10 … 0 V inverted PositionSingle duct Setting the sequence and the control outputsHeating or cooling Modulating control 3-position, PWM or DC 0 … 10Modulating electrical heater Single duct with electrical heaterSequences Modulating radiator / floor heating Single duct with radiator or floor heatingModulating heating / cooling coil Single duct with heating / cooling coilControl sequence Synchronization Control outputsControl output for air flow ON/OFF control signal Position control SignalPosition actuator Parameter P44 Y1 and Y2AI/DI Multifunctional input, Digital inputDIP switches Handling of faultsTemperature out RangeChange the parameters as follows Parameter settingControl parameters Service level Parameters Service levelExpert level Parameters Expert level, diagnostics & testDiagnostics & test Wiring Mounting and installationHandling MountingLayout OperationButton operation User actionLCD display DisposalConnection terminals EngineeringConnection diagrams General DimensionsMechanical design Power supply Outputs Inputs Operational data Technical dataPage Automatic heating/cooling changeover Index