Honeywell UDC3200 manual Mounting Method, Step Action

Page 14

Mounting Method

Before mounting the controller, refer to the nameplate on the outside of the case and make a note of the model number. It will help later when selecting the proper wiring configuration.

Mounting clips

Attach screws and washers here for

water protection

Figure 2-3 Mounting Methods

Mounting Procedure

Table 2-3 Mounting Procedure

Step

1

2

3

4

Action

Mark and cut out the controller hole in the panel according to the dimension information in Figure 2-2.

Orient the case properly and slide it through the panel hole from the front. Remove the mounting kit from the shipping container and install the kit as follows:

For normal installation two mounting clips are required. Insert the prongs of the clips into the two holes in the top and bottom center of the case

For water-protected installation four mounting clips are required. There are two options of where to install the mounting clips:

1)Insert the prongs of the clips into the two holes on the left and right side of the top and bottom of the case or

2)on the center on each of the four sides.

Tighten screws to 2 lb-inch (22 Ncm) to secure the case against the panel. CAUTION: Over tightening will cause distortion and the unit may not seal properly.

For water-protected installation, install four screws with washers into the four recessed areas in the corners of the front bezel (Figure 2-3). Push the point of the screw through the center piercing the elastomeric material and then tighten screws to 5 lb-in (56 Ncm).

8

UDC3200 Universal Digital Controller Operator Manual

04/08

Image 14
Contents UDC3200 Universal Digital Controller Operator Manual World Wide Web WARRANTY/REMEDYContacts TelephoneSymbol Definitions Symbol DefinitionContents TROUBLESHOOTING/SERVICE Page Function of Displays and Keys Operator InterfaceFunction of Displays and Keys CE Conformity Europe Keys and FunctionsUDC3200 Universal Digital Controller Operator Manual Page Pre-installation Information Model Number InterpretationAlarm Relay Contact Information Control and Alarm Relay Contact InformationAlarm Relays Control RelaysPhysical Considerations Overall DimensionsMounting Mounting Method Step ActionWiring Bundle No Wire Functions Wiring DiagramsPermissible Wiring Bundling Universal Output Functionality and RestrictionsINU Details Wiring the ControllerCallout Line Neutral Voltage L2/N Earth Ground HotAC/DC Input #1 RTDInput #2 Input 2 ConnectionsTime Simplex Time DuplexPower Load Relay Load L2/N PowerSupply Power Relay Load10 Open Collector Output Time Duplex with a Dual Relay Board L2/N Relay LoadUDC3200 Universal Digital Controller Operator Manual 04/08 15 RS-422/485 Communications Option Connections 17 Auxiliary Output and Digital Inputs Option Connections Digital Inputs26 + 12 +Configuration Configuration Prompt HierarchyConfiguration Procedure Configuration ProcedureProcedure IntroductionTuning Set Up Group 02 to Configuration is CompleteRSET2MIN RSET2RPM CYC SEC CYC SX3 CYC2 SEC CYC2 SX3 Security LockoutSP SEL Auto MAN Disable Enable RUN HoldDisable Enable SP Ramp Set Up Group SP Prog KeyresetEU/HR DN Strt SEG END SEGSEG4 SP SEG4TIME SEG2TIMESEG3RATE SEG5RATE SEG6 SP SEG6TIMEAT Error Accutune Set Up GroupFuzzy Disable Enable Accutune Tune Algorithm Set Up Group ALG ON-OFFTimer ALG PD+MR000 to Start KEY Alarm LOW Disp TI REM TimePeriod INP ALG1Input LOW Select with Ratio and BIAS- This selection Summer with Ratio and BIAS-The following formulaInput High Select with Ratio and BIAS-This selection Multiplier Divider with Square Root -The followingCalc HI FCCMath K Calc LOPCT CO ALG1 INBALG1 INC ALG1 BiasOUT RNG Output Set Up GroupOUT ALG Rlystate RLY TypeLOW VAL Motor TICUR OUT High VALInput 1 Set Up Group IN1 TypeRatio XmitterIN1 LOW Bias IN101 to Burnout NoneEMISSIV1 XMITTER2 Input 2 Set Up GroupIN2 Type Bias IN2 IN2 HighIN2 LOW Burnout Burnout Protection Sensor BreakEMISSIV2 Input Input Algorithm Control Set Up GroupPV Source Input ALG1 PID Sets PID Sets 2PV SWSP Track PWR ModeRSP SRC None Input ALG1 Autobias PWR OUTPCT/M UP ActionOUT Rate PCT/M DNFailmode Failsafe ModeDeadband MAN OUTRPM MinutesAuxiliary Output Selection Options GroupAUX OUT No Auxiliary OutputWas not previously started via DIG INP1No Digital Input Selections To RUN DIG2COMB DIG 1COMBDIG INP2 Digital Input 2 Selections Digital Input 2 CombinationsCommunications Group CSP Rato Shed SPUnits CSP BiasAlarms Set Up Group A1S1 EV High AlarmLOW Alarm Beginning of SegmentA2S1 EV A1S2 EVA2S1TYPE A2S2TYPEALARM12 DiagnostDisplay Set Up Group Page Entering a Security Code Operator InterfaceIndividual key lockout Procedure to Enter a Security CodeKey error ALM 1 OUT 1 DI 1 Or MAN None, F or C Monitoring Your Controller 4.4.1 AnnunciatorsAnnunciators Viewing the operating parameters Lower Display Key Parameter PromptsDescription Diagnostic MessagesDiagnostic Messages Functional Overview Block Diagram of the UDC3200 Controller Accutune Configuration checkTuning indicators Operation Procedure for Starting TuneTune for Simplex Outputs Step Operation Press ResultConfiguration Check for Duplex Tune for Duplex Heat/CoolUsing Automatic Tune at start-up for Duplex Heat/Cool Using Blended Tune at start-up for Duplex Heat/Cool Using Manual Tune at start-up for Duplex Heat/CoolStep Operation Press Result 11 Accutune Error Codes Error Codes10 Procedure for Accessing Accutune Error Codes Aborting AccutuneHow it works ConfigurationFuzzy Overshoot Suppression EE Fail Background TestsBackground Tests INP1 RNGCAL MTR RV LimitSegerr CurfailController Failure Symptoms Other symptomsSales and Service Page Http//hpsweb.honeywell.com