Honeywell UDC3200 manual Background Tests, EE Fail, INP1 RNG, INP2 RNG

Page 85

5Troubleshooting/Service

5.1Background Tests

The UDC3200 performs ongoing background tests to verify data and memory integrity. If there is a malfunction, a diagnostic message will be displayed (blinking) in the lower display. In the case of simultaneous malfunctions, the messages will appear in sequence in the lower display.

Diagnostic messages may be suppressed (stop the blinking) by pressing the RUN/HOLD key. The messages will still be available for viewing by pressing the LOWER DISPLAY key.

Table 5-1 Background Tests

Lower

 

Reason for Failure

Display

 

 

EE FAIL

Unable to write to non-volatile memory.

 

Anytime you change a parameter and it is

 

not accepted, you will see E FAIL.

 

 

FAILSAFE

This error message shows whenever the

 

controller goes into a failsafe mode of

 

operation. This will happen if:

 

RAM test failed

 

Configuration test failed

 

Calibration test failed

 

Burnout configured for none and

 

 

the input failed.

 

 

INP1 RNG

Input 1 out of range. The process input is

 

outside the range limits.

INP1FAIL

Two consecutive failures of input 1

 

integration; i.e., cannot make analog to

 

digital conversion. This will happen if:

 

• Upscale or Downscale burnout is

 

selected and the input is open

 

• Input not configured correctly for the

 

sensor being used

 

• Input source is grossly out of range.

INP2 RNG

Input 2 out of range. The remote input is

 

outside the range limits.

 

 

INP2FAIL

Two consecutive failures of input 2

 

integration. i.e., cannot make analog to

 

digital conversion.

CONF ERR

• PV low limit is > PV high limit

 

• SP low limit is > SP high limit

 

• Output low limit > Output high limit

How to Correct the Problem

1.Check the accuracy of the parameter and re-enter.

2.Try to change something in configuration.

3.Run through Read STATUS tests to re-write to

EEPROM.

1.Run through STATUS check to determine the reason for the failure.

2.Press the SET UP key until STATUS appears in the lower display.

3.Press the FUNCTION key to see whether the tests pass or fail, then run through the STATUS codes a second time to see if the error cleared.

1.Make sure the range and actuation are configured properly.

2.Check the input source.

3.Restore the factory calibration.

4.Field calibrate.

1.Make sure the actuation is configured correctly. See Section 3 - Configuration.

2.Make sure the input is correct and that it has not burned-out (opened).

3.Check for gross over-ranging with a multimeter.

4.Restore factory calibration.

Same as INP1RNG above.

Same as INP1FAIL above.

1.Check the configuration for each item and reconfigure if necessary.

04/08

UDC3200 Universal Digital Controller Operator Manual

79

Image 85
Contents UDC3200 Universal Digital Controller Operator Manual Contacts WARRANTY/REMEDYWorld Wide Web TelephoneSymbol Definition Symbol DefinitionsContents TROUBLESHOOTING/SERVICE Page Function of Displays and Keys Operator InterfaceFunction of Displays and Keys Keys and Functions CE Conformity EuropeUDC3200 Universal Digital Controller Operator Manual Page Model Number Interpretation Pre-installation InformationAlarm Relays Control and Alarm Relay Contact InformationAlarm Relay Contact Information Control RelaysMounting Overall DimensionsPhysical Considerations Step Action Mounting MethodWiring Permissible Wiring Bundling Wiring DiagramsBundle No Wire Functions Universal Output Functionality and RestrictionsINU Callout Wiring the ControllerDetails AC/DC Earth Ground HotLine Neutral Voltage L2/N RTD Input #1Input 2 Connections Input #2Time Duplex Time SimplexSupply Power L2/N PowerPower Load Relay Load Relay Load10 Open Collector Output L2/N Relay Load Time Duplex with a Dual Relay BoardUDC3200 Universal Digital Controller Operator Manual 04/08 15 RS-422/485 Communications Option Connections Digital Inputs 17 Auxiliary Output and Digital Inputs Option Connections12 + 26 +Configuration Prompt Hierarchy ConfigurationProcedure Configuration ProcedureConfiguration Procedure IntroductionTuning Set Up Group RSET2MIN Configuration is Complete02 to RSET2RPM CYC SEC CYC SX3 CYC2 SEC CYC2 SX3 Security LockoutDisable Enable Auto MAN Disable Enable RUN HoldSP SEL SP Ramp Set Up Group EU/HR DN KeyresetSP Prog Strt SEG END SEGSEG3RATE SEG2TIMESEG4 SP SEG4TIME SEG5RATE SEG6 SP SEG6TIMEFuzzy Disable Enable Accutune Tune Accutune Set Up GroupAT Error ALG ON-OFF Algorithm Set Up GroupALG PD+MR TimerPeriod Start KEY Alarm LOW Disp TI REM Time000 to INP ALG1Input High Select with Ratio and BIAS-This selection Summer with Ratio and BIAS-The following formulaInput LOW Select with Ratio and BIAS- This selection Multiplier Divider with Square Root -The followingMath K FCCCalc HI Calc LOALG1 INC ALG1 INBPCT CO ALG1 BiasOUT ALG Output Set Up GroupOUT RNG RLY Type RlystateCUR OUT Motor TILOW VAL High VALIN1 Type Input 1 Set Up GroupIN1 LOW XmitterRatio Bias IN1EMISSIV1 Burnout None01 to IN2 Type Input 2 Set Up GroupXMITTER2 IN2 LOW IN2 HighBias IN2 Burnout Burnout Protection Sensor BreakEMISSIV2 PV Source Input ALG1 PID Sets Control Set Up GroupInput Input Algorithm PID Sets 2PV SWRSP SRC None Input ALG1 Autobias PWR ModeSP Track PWR OUTOUT Rate ActionPCT/M UP PCT/M DNDeadband Failsafe ModeFailmode MAN OUTMinutes RPMAUX OUT Options GroupAuxiliary Output Selection No Auxiliary OutputNo Digital Input Selections DIG INP1Was not previously started via To RUN DIG INP2 DIG 1COMBDIG2COMB Digital Input 2 Selections Digital Input 2 CombinationsCommunications Group Units Shed SPCSP Rato CSP BiasAlarms Set Up Group LOW Alarm High AlarmA1S1 EV Beginning of SegmentA2S1TYPE A1S2 EVA2S1 EV A2S2TYPEDiagnost ALARM12Display Set Up Group Page Operator Interface Entering a Security CodeKey error Procedure to Enter a Security CodeIndividual key lockout Annunciators Monitoring Your Controller 4.4.1 AnnunciatorsALM 1 OUT 1 DI 1 Or MAN None, F or C Lower Display Key Parameter Prompts Viewing the operating parametersDiagnostic Messages Diagnostic MessagesDescription Functional Overview Block Diagram of the UDC3200 Controller Tuning indicators Configuration checkAccutune Tune for Simplex Outputs Procedure for Starting TuneOperation Step Operation Press ResultTune for Duplex Heat/Cool Configuration Check for DuplexUsing Automatic Tune at start-up for Duplex Heat/Cool Using Manual Tune at start-up for Duplex Heat/Cool Using Blended Tune at start-up for Duplex Heat/Cool Step Operation Press Result 10 Procedure for Accessing Accutune Error Codes Error Codes11 Accutune Error Codes Aborting AccutuneFuzzy Overshoot Suppression ConfigurationHow it works Background Tests Background TestsEE Fail INP1 RNGSegerr RV LimitCAL MTR CurfailOther symptoms Controller Failure SymptomsSales and Service Page Http//hpsweb.honeywell.com