3.11 Options Group

 

Function

Selections or

 

Prompt

Range of Setting

 

Lower Display

Upper Display

 

AUX OUT

 

 

 

 

 

 

ATTENTION

 

 

Prompts for the

 

 

Auxiliary

 

 

Output

 

 

Selection

 

 

appear only if

 

 

one of the

 

 

Auxiliary

 

 

Output boards

 

 

is installed.

 

 

 

 

DISABLE

 

 

 

INPUT 1

 

 

 

INPUT 2

 

 

 

PV

 

 

 

 

 

 

 

Parameter

Definition

AUXILIARY OUTPUT SELECTION

This selection provides an mA output representing one of several control parameters. The display for auxiliary output viewing will be in engineering units for all but output. Output will be displayed in percent.

ATTENTION Other prompts affected by these selections: 4mA VAL and 20mA VAL.

ATTENTION Output cannot be configured when Three Position Step Control is used.

NO AUXILIARY OUTPUT

INPUT 1—This represents the configured range of input 1.

INPUT 2 represents the value of the configured range of input 2.

PROCESS VARIABLE—Represents the value of the Process Variable. PV = Input XxRatioX + BiasX

DEV

OUTPUT

SP

LSP 1

RSP

IN ALG1

CO RANGE 4-20mA

0-20mA

DEVIATION (PROCESS VARIABLE MINUS SETPOINT)— Represents –100 % to +100 % of the selected PV span in engineering units.

Zero deviation will produce a center scale (12 mA or 50 %) output. A negative deviation equal in magnitude to the Auxiliary Output High Scaling Factor will produce a low end output (4 mA or 0 %) output. A positive deviation equal in magnitude to the Auxiliary Output Low Scaling Factor will produce a high end output (20 mA or 100 %).

OUTPUT—Represents the displayed controller output in percent

(%). Cannot be used with Three Position Step Control.

SETPOINT—Represents the value of the setpoint currently in use (LSP1, LSP2, LSP3, RSP or CSP) and is shown in the same units as those used by the PV.

LOCAL SETPOINT ONE—Auxiliary output represents Local Setpoint 1 regardless of active setpoint.

REMOTE SETPOINT – Represents the configured RSP regardless of the active SetPoint.

INPUT ALGORITHM 1 OUTPUT—Represents the output from input algorithm 1.

AUXILIARY CURRENT OUTPUT RANGE—Allows the user to easily select 4-20mA output or 0-20mA output operation without the need for recalibration of the instrument.

ATTENTION Changing the Auxiliary Current Output Range will result in the loss of Field Calibration values and will restore Factory Calibration values.

04/08

UDC3200 Universal Digital Controller Operator Manual

53

Image 59
Contents UDC3200 Universal Digital Controller Operator Manual Telephone WARRANTY/REMEDYContacts World Wide WebSymbol Definition Symbol DefinitionsContents TROUBLESHOOTING/SERVICE Page Function of Displays and Keys Operator InterfaceFunction of Displays and Keys Keys and Functions CE Conformity EuropeUDC3200 Universal Digital Controller Operator Manual Page Model Number Interpretation Pre-installation InformationControl Relays Control and Alarm Relay Contact InformationAlarm Relays Alarm Relay Contact InformationPhysical Considerations Overall DimensionsMounting Step Action Mounting MethodWiring Universal Output Functionality and Restrictions Wiring DiagramsPermissible Wiring Bundling Bundle No Wire FunctionsINU Details Wiring the ControllerCallout Line Neutral Voltage L2/N Earth Ground HotAC/DC RTD Input #1Input 2 Connections Input #2Time Duplex Time SimplexRelay Load L2/N PowerSupply Power Power Load Relay Load10 Open Collector Output L2/N Relay Load Time Duplex with a Dual Relay BoardUDC3200 Universal Digital Controller Operator Manual 04/08 15 RS-422/485 Communications Option Connections Digital Inputs 17 Auxiliary Output and Digital Inputs Option Connections12 + 26 +Configuration Prompt Hierarchy ConfigurationIntroduction Configuration ProcedureProcedure Configuration ProcedureTuning Set Up Group RSET2RPM CYC SEC CYC SX3 CYC2 SEC CYC2 SX3 Security Lockout Configuration is CompleteRSET2MIN 02 toSP SEL Auto MAN Disable Enable RUN HoldDisable Enable SP Ramp Set Up Group Strt SEG END SEG KeyresetEU/HR DN SP ProgSEG5RATE SEG6 SP SEG6TIME SEG2TIMESEG3RATE SEG4 SP SEG4TIMEAT Error Accutune Set Up GroupFuzzy Disable Enable Accutune Tune ALG ON-OFF Algorithm Set Up GroupALG PD+MR TimerINP ALG1 Start KEY Alarm LOW Disp TI REM TimePeriod 000 toMultiplier Divider with Square Root -The following Summer with Ratio and BIAS-The following formulaInput High Select with Ratio and BIAS-This selection Input LOW Select with Ratio and BIAS- This selectionCalc LO FCCMath K Calc HIALG1 Bias ALG1 INBALG1 INC PCT COOUT RNG Output Set Up GroupOUT ALG RLY Type RlystateHigh VAL Motor TICUR OUT LOW VALIN1 Type Input 1 Set Up GroupBias IN1 XmitterIN1 LOW Ratio01 to Burnout NoneEMISSIV1 XMITTER2 Input 2 Set Up GroupIN2 Type Burnout Burnout Protection Sensor Break IN2 HighIN2 LOW Bias IN2EMISSIV2 PID Sets 2PV SW Control Set Up GroupPV Source Input ALG1 PID Sets Input Input AlgorithmPWR OUT PWR ModeRSP SRC None Input ALG1 Autobias SP TrackPCT/M DN ActionOUT Rate PCT/M UPMAN OUT Failsafe ModeDeadband FailmodeMinutes RPMNo Auxiliary Output Options GroupAUX OUT Auxiliary Output SelectionWas not previously started via DIG INP1No Digital Input Selections To RUN Digital Input 2 Selections Digital Input 2 Combinations DIG 1COMBDIG INP2 DIG2COMBCommunications Group CSP Bias Shed SPUnits CSP RatoAlarms Set Up Group Beginning of Segment High AlarmLOW Alarm A1S1 EVA2S2TYPE A1S2 EVA2S1TYPE A2S1 EVDiagnost ALARM12Display Set Up Group Page Operator Interface Entering a Security CodeIndividual key lockout Procedure to Enter a Security CodeKey error ALM 1 OUT 1 DI 1 Or MAN None, F or C Monitoring Your Controller 4.4.1 AnnunciatorsAnnunciators Lower Display Key Parameter Prompts Viewing the operating parametersDescription Diagnostic MessagesDiagnostic Messages Functional Overview Block Diagram of the UDC3200 Controller Accutune Configuration checkTuning indicators Step Operation Press Result Procedure for Starting TuneTune for Simplex Outputs OperationTune for Duplex Heat/Cool Configuration Check for DuplexUsing Automatic Tune at start-up for Duplex Heat/Cool Using Manual Tune at start-up for Duplex Heat/Cool Using Blended Tune at start-up for Duplex Heat/CoolStep Operation Press Result Aborting Accutune Error Codes10 Procedure for Accessing Accutune Error Codes 11 Accutune Error CodesHow it works ConfigurationFuzzy Overshoot Suppression INP1 RNG Background TestsBackground Tests EE FailCurfail RV LimitSegerr CAL MTROther symptoms Controller Failure SymptomsSales and Service Page Http//hpsweb.honeywell.com