Honeywell UDC3200 manual A1S2 EV, A2S1TYPE, A2S1 EV, A2S2TYPE, A2S2 EV, Alhyst, ALM OUT1, Block

Page 67

Function

Selections or

 

 

 

 

Parameter Definition

Prompt

Range of Setting

 

 

 

 

 

Lower Display

Upper Display

 

 

 

 

 

A1S2 EV

BEGIN

ALARM 1 SEGMENT EVENT 2—Same as A1S1 EV.

 

END

 

 

 

 

 

 

 

 

 

 

A2S1TYPE

Same as A1S1

ALARM 2 SETPOINT 1 TYPE—Select what you want Setpoint 1

 

TYPE

of Alarm 2 to represent.

 

 

The selections are the same as A1S1TYPE.

 

 

 

 

 

 

Not available with Relay Duplex or Position

 

 

 

ATTENTION

 

 

 

Proportional

output types unless using Dual Relay PWA.

 

 

 

 

 

 

A2S1 H L

HIGH

 

ALARM 2 SETPOINT 1 STATE—Same as A1S1 H L.

 

LOW

 

 

 

 

 

A2S1 EV

BEGIN

ALARM 2 SEGMENT EVENT 1—Same as A1S1 EV.

 

END

 

 

 

 

 

 

 

 

 

A2S2TYPE

Same as A1S1

ALARM 2 SETPOINT 2 TYPE—Select what you want Setpoint 2

 

TYPE

of Alarm 2 to represent.

 

 

The selections are the same as A1S1TYPE.

 

 

 

 

 

Not applicable with Relay Duplex or Position

 

 

 

ATTENTION

 

 

 

Proportional

output types unless using Dual Relay PWA.

 

 

 

 

 

A2S2 H L

HIGH

 

ALARM 2 SETPOINT 2 STATE—Same as A1S1 H L.

 

LOW

 

 

 

 

 

A2S2 EV

BEGIN

ALARM 2 SEGMENT EVENT 2—Same as

 

END

A1S1 EV.

 

 

 

 

ALHYST

0.0 to 100.0 % of

ALARM HYSTERESIS—A single adjustable hysteresis is

 

span or full output

provided on alarms such that when the alarm is OFF it activates

 

as appropriate

at exactly the alarm setpoint; when the alarm is ON, it will not

 

 

deactivate until the variable is 0.0 % to 100 % away from the

 

 

alarm setpoint.

 

 

Configure the hysteresis of the alarms based on INPUT signals

 

 

as a % of input range span.

 

 

Configure the hysteresis of the alarm based on OUTPUT signals

 

 

as a % of the full scale output range.

 

 

 

 

ALM OUT1

 

LATCHING ALARM OUTPUT 1—Alarm output 1 can be

 

 

configured to be Latching or Non-latching.

 

NoLATCH

NoLATCH —Non-latching

 

LATCH

LATCH—Latching

 

 

 

 

When configured for latching, the alarm will stay

 

 

 

ATTENTION

 

 

 

active after the alarm condition ends until the RUN/HOLD key is

 

 

 

pressed.

 

 

 

 

BLOCK

 

 

ALARM BLOCKING—Prevents nuisance alarms when the

 

 

 

controller is first powered up. The alarm is suppressed until the

 

 

 

parameter gets to the non-alarm limit or band. Alarm blocking

 

 

 

affects both alarm setpoints.

 

 

 

 

 

 

 

04/08

UDC3200 Universal Digital Controller Operator Manual

61

Image 67
Contents UDC3200 Universal Digital Controller Operator Manual Telephone WARRANTY/REMEDYContacts World Wide WebSymbol Definition Symbol DefinitionsContents TROUBLESHOOTING/SERVICE Page Function of Displays and Keys Operator InterfaceFunction of Displays and Keys Keys and Functions CE Conformity EuropeUDC3200 Universal Digital Controller Operator Manual Page Model Number Interpretation Pre-installation InformationControl Relays Control and Alarm Relay Contact InformationAlarm Relays Alarm Relay Contact InformationMounting Overall DimensionsPhysical Considerations Step Action Mounting MethodWiring Universal Output Functionality and Restrictions Wiring DiagramsPermissible Wiring Bundling Bundle No Wire FunctionsINU Callout Wiring the ControllerDetails AC/DC Earth Ground HotLine Neutral Voltage L2/N RTD Input #1Input 2 Connections Input #2Time Duplex Time SimplexRelay Load L2/N PowerSupply Power Power Load Relay Load10 Open Collector Output L2/N Relay Load Time Duplex with a Dual Relay BoardUDC3200 Universal Digital Controller Operator Manual 04/08 15 RS-422/485 Communications Option Connections Digital Inputs 17 Auxiliary Output and Digital Inputs Option Connections12 + 26 +Configuration Prompt Hierarchy ConfigurationIntroduction Configuration ProcedureProcedure Configuration ProcedureTuning Set Up Group RSET2RPM CYC SEC CYC SX3 CYC2 SEC CYC2 SX3 Security Lockout Configuration is CompleteRSET2MIN 02 toDisable Enable Auto MAN Disable Enable RUN HoldSP SEL SP Ramp Set Up Group Strt SEG END SEG KeyresetEU/HR DN SP ProgSEG5RATE SEG6 SP SEG6TIME SEG2TIMESEG3RATE SEG4 SP SEG4TIMEFuzzy Disable Enable Accutune Tune Accutune Set Up GroupAT Error ALG ON-OFF Algorithm Set Up GroupALG PD+MR TimerINP ALG1 Start KEY Alarm LOW Disp TI REM TimePeriod 000 toMultiplier Divider with Square Root -The following Summer with Ratio and BIAS-The following formulaInput High Select with Ratio and BIAS-This selection Input LOW Select with Ratio and BIAS- This selectionCalc LO FCCMath K Calc HIALG1 Bias ALG1 INBALG1 INC PCT COOUT ALG Output Set Up GroupOUT RNG RLY Type RlystateHigh VAL Motor TICUR OUT LOW VALIN1 Type Input 1 Set Up GroupBias IN1 XmitterIN1 LOW RatioEMISSIV1 Burnout None01 to IN2 Type Input 2 Set Up GroupXMITTER2 Burnout Burnout Protection Sensor Break IN2 HighIN2 LOW Bias IN2EMISSIV2 PID Sets 2PV SW Control Set Up GroupPV Source Input ALG1 PID Sets Input Input AlgorithmPWR OUT PWR ModeRSP SRC None Input ALG1 Autobias SP TrackPCT/M DN ActionOUT Rate PCT/M UPMAN OUT Failsafe ModeDeadband FailmodeMinutes RPMNo Auxiliary Output Options GroupAUX OUT Auxiliary Output SelectionNo Digital Input Selections DIG INP1Was not previously started via To RUN Digital Input 2 Selections Digital Input 2 Combinations DIG 1COMBDIG INP2 DIG2COMBCommunications Group CSP Bias Shed SP Units CSP RatoAlarms Set Up Group Beginning of Segment High AlarmLOW Alarm A1S1 EVA2S2TYPE A1S2 EVA2S1TYPE A2S1 EVDiagnost ALARM12Display Set Up Group Page Operator Interface Entering a Security CodeKey error Procedure to Enter a Security CodeIndividual key lockout Annunciators Monitoring Your Controller 4.4.1 AnnunciatorsALM 1 OUT 1 DI 1 Or MAN None, F or C Lower Display Key Parameter Prompts Viewing the operating parametersDiagnostic Messages Diagnostic MessagesDescription Functional Overview Block Diagram of the UDC3200 Controller Tuning indicators Configuration checkAccutune Step Operation Press Result Procedure for Starting TuneTune for Simplex Outputs OperationTune for Duplex Heat/Cool Configuration Check for DuplexUsing Automatic Tune at start-up for Duplex Heat/Cool Using Manual Tune at start-up for Duplex Heat/Cool Using Blended Tune at start-up for Duplex Heat/CoolStep Operation Press Result Aborting Accutune Error Codes10 Procedure for Accessing Accutune Error Codes 11 Accutune Error CodesFuzzy Overshoot Suppression ConfigurationHow it works INP1 RNG Background TestsBackground Tests EE FailCurfail RV LimitSegerr CAL MTROther symptoms Controller Failure SymptomsSales and Service Page Http//hpsweb.honeywell.com